Study guide
5.4 ACCA Manual N Commercial Load Calculation
North Carolina HVAC Contractor License Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: North Carolina HVAC Licensing Framework & Board Jurisprudence
1.1 NC Dual-Board Regulatory Structure & General Statutes 1.2 Heating Classifications, Groups & Scopes 1.3 Examination Prerequisites, Qualifier Responsibilities & Disciplinary Rules 1.4 Examination Logistics, Reference Books & Code Editions
2 Chapter 2: North Carolina Business Organizations, Contracts & Lien Law
2.1 Construction Contracts, Project Management & Bidding 2.2 North Carolina Mechanics' Lien Law & Bond Claims 2.3 Business Organizations, Financial Management & Taxation
3 Chapter 3: Construction Safety, Electrical Safety & EPA 608
3.1 OSHA 1926 Construction Safety & Job Site Protocols 3.2 Electrical Safety, NFPA 70E & Lockout/Tagout (LOTO) 3.3 EPA Section 608 & Refrigerant Transition Regulations
4 Chapter 4: Thermodynamics, Refrigeration Cycle & Psychrometrics
4.1 Fundamentals of Thermodynamics & Heat Transfer 4.2 The Mechanical Refrigeration Cycle & Component Dynamics 4.3 Psychrometric Properties, Air Processes & Chart Navigation
5 Chapter 5: ACCA Manual J & Manual N Load Calculations
5.1 Manual J Design Conditions & Thermal Parameters 5.2 Fenestration, Opaque Envelope & Internal Heat Gains 5.3 Infiltration, Duct Losses & Total Block Load Synthesis 5.4 ACCA Manual N Commercial Load Calculation
6 Chapter 6: ACCA Manual D & Manual Q Duct Design & Air Distribution
6.1 Fan Laws, Airflow Dynamics & Total External Static Pressure 6.2 ACCA Manual D Sizing Protocol & Friction Rate Calculation 6.3 SMACNA Duct Construction, Fittings & Air Balancing 6.4 ACCA Manual Q Commercial Low-Pressure Duct Design
7 Chapter 7: Forced Air Heating, Gas Furnaces & Fuel Piping
7.1 Natural Gas & Propane Combustion Fundamentals 7.2 Gas Furnace Operation, Sequence of Control & Diagnostics 7.3 Fuel Oil Heating Systems & Code-Compliant Fuel Gas Piping
8 Chapter 8: Heat Pumps, Inverters & Commercial System Selection (Manual CS)
8.1 Heat Pump Operating Principles, Reversing Valves & Physics 8.2 Defrost Controls, Supplemental Electric Heat & Balance Points 8.3 Inverter Mini-Splits & Variable Refrigerant Flow (VRF) Systems 8.4 Manual CS: Commercial Applications, Systems & Equipment
9 Chapter 9: Hydronic Heating, Steam Systems & Boilers (H1)
9.1 Hydronic Fundamentals, Boiler Classifications & Steam Systems 9.2 Hydronic Piping Layouts, Circulator Pumps & Head Loss Calculations 9.3 Boiler Trim, Expansion Tanks, Air Elimination & Safety Controls 9.4 The NC Uniform Boiler & Pressure Vessel Act (H1 Reference)
10 Chapter 10: Commercial Refrigeration & NC Board Regulations
10.1 NC State Board of Refrigeration Contractors Statutes & Licensure 10.2 Commercial Refrigeration Systems, Multiplex Racks & Defrost Protocols 10.3 Walk-In Coolers, Freezers, Evaporator Pressure Regulators & Valves
11 Chapter 11: NC Administration, Mechanical, Fuel Gas & Energy Codes
11.1 North Carolina Mechanical Code: Equipment Access, Clearances & Condensate 11.2 Ventilation Rates, Exhaust Systems & Duct Smoke Detection 11.3 NC Fuel Gas Code: Combustion Air, Venting & Gas Appliance Installation 11.4 NC Energy Conservation Code: Duct Testing, Envelope & Efficiency Standards 11.5 NC Administrative Code & Policies: Permits, Inspections & Plan Review
12 Chapter 12: Electrical Fundamentals, Motor Controls & Diagnostics
12.1 HVAC Electrical Fundamentals, Circuit Schematics & Power Distribution 12.2 Electric Motors, Capacitors & Motor Controls 12.3 Systematic HVAC Diagnostics, Superheat/Subcooling & Airflow Troubleshooting 12.4 System Commissioning, Testing, Adjusting & Balancing (TAB)
5.4 ACCA Manual N Commercial Load Calculation
Key Takeaways Explain This Topic AI
ACCA Manual N (Commercial Load Calculation for Small Commercial Buildings, 5th Edition) is a required reference book for the Heating Group 1 Class I, Heating Group 2 and Heating Group 3 Class I examinations; Manual J is the residential companion and does not cover commercial internal or ventilation loads.
Commercial loads add three components Manual J largely ignores: occupant sensible and latent gain, lighting and appliance/equipment gain, and a code-mandated outdoor ventilation load that is imposed on the equipment rather than on the space.
Electrical gains convert at 3.412 BTU/h per watt, so lighting load equals 3.412 x installed watts x ballast factor x use factor and equipment load equals 3.412 x connected watts x diversity factor.
Ventilation air is treated as a coil load: sensible = 1.08 x CFM x delta-T, latent = 0.68 x CFM x delta-grains, and total = 4.5 x CFM x delta-enthalpy at standard air conditions.
Block loads size the equipment while zone and room loads size the air distribution; because a commercial building's peak may occur late in the afternoon rather than at solar noon, Manual N requires the designer to test more than one hour of the day.
Last updated: August 2026
ACCA Manual N Commercial Load Calculation
Why it is on the exam: the Board's reference book list places Manual N — Commercial Load Calculation for Small Commercial Buildings, 5th Edition on the H1 Class I, H2 and H3 Class I lists. Heating Group 2 candidates do not carry Manual J at all — for them, Manual N is the load calculation manual.
1. What Changes When the Building Stops Being a House
A residence is envelope-dominated: skin loads and infiltration drive the peak, occupancy is sparse, and outdoor air is small. A small commercial building inverts that relationship.
- Load Component Residential (Manual J) Small Commercial (Manual N)
- Envelope conduction Dominant Present but often secondary
- Solar gain through glass Significant Significant, and frequently sets the peak hour
People 1 occupant per bedroom + 1, latent modest Density-driven — a 60-seat restaurant or classroom can exceed the envelope load
Lighting Small, ignored in many cases Major sensible gain, especially in retail
Appliances / equipment Kitchen allowance Cooking, refrigeration cases, servers, motors — often the largest single gain
- Ventilation air Mechanical ventilation rate Code-mandated outdoor air , and it is a coil load, not a room load
- Peak hour Usually mid-afternoon Must be tested at several hours; internal gains shift the peak
- 2. Internal Gains
- People
Manual N tabulates sensible and latent gain per person by activity. Representative values used throughout the manual and ASHRAE Fundamentals:
- Activity / Occupancy Sensible (BTU/h per person) Latent (BTU/h per person)
- Seated at theater / moderately active office work 245 – 250 155 – 200
- Standing, light work; walking (retail) 250 200 – 250
- Seated, eating (restaurant) 275 275
- Light bench work / moderate dancing 275 – 305 475 – 545
Heavy work, athletics 580 – 635 870 – 1,090 q people, sensible = N people × sensible gain per person q_{\text{people, sensible}} = N_{\text{people}} \times \text{sensible gain per person} q people, sensible = N people × sensible gain per person q people, latent = N people × latent gain per person q_{\text{people, latent}} = N_{\text{people}} \times \text{latent gain per person} q people, latent = N people × latent gain per person
Occupant count comes from the actual design occupancy where known, otherwise from the default occupant density in the ventilation table.
Lighting and Equipment
Every watt dissipated inside the envelope becomes sensible heat: 1 watt = 3.412 BTU/h 1\text{ watt} = 3.412\text{ BTU/h} 1 watt = 3.412 BTU/h q lighting = 3.412 × W installed × B F × U F q_{\text{lighting}} = 3.412 \times W_{\text{installed}} \times BF \times UF q lighting = 3.412 × W installed × BF × U F
where B F BF BF is the ballast/driver factor (1.20 for older magnetic-ballast fluorescent, ≈1.0 for LED drivers) and U F UF U F is the use factor (fraction actually energized at the design hour). q equipment = 3.412 × W connected × diversity factor q_{\text{equipment}} = 3.412 \times W_{\text{connected}} \times \text{diversity factor} q equipment = 3.412 × W connected × diversity factor
Hooded commercial cooking appliances transfer a reduced fraction to the space because the hood captures the rest; unhooded appliances contribute both sensible and latent gain.
Worked Example — Internal Gains for a 2,400 sq ft Retail Suite
Lighting: 2.0 W/sq ft LED, use factor 1.0 → 3.412 × ( 2.0 × 2,400 ) × 1.0 = 16,378 BTU/h 3.412 \times (2.0 \times 2{,}400) \times 1.0 = 16{,}378\text{ BTU/h} 3.412 × ( 2.0 × 2 , 400 ) × 1.0 = 16 , 378 BTU/h sensible
Equipment (registers, displays, back-office): 4,500 W connected, diversity 0.75 → 3.412 × 4,500 × 0.75 = 11,516 BTU/h 3.412 \times 4{,}500 \times 0.75 = 11{,}516\text{ BTU/h} 3.412 × 4 , 500 × 0.75 = 11 , 516 BTU/h sensible
People: retail density 15 per 1,000 sq ft → 36 people at 250 sensible / 200 latent → 9,000 BTU/h sensible and 7,200 BTU/h latent q internal, sensible = 16,378 + 11,516 + 9,000 = 36,894 BTU/h q_{\text{internal, sensible}} = 16{,}378 + 11{,}516 + 9{,}000 = 36{,}894\text{ BTU/h} q internal, sensible = 16 , 378 + 11 , 516 + 9 , 000 = 36 , 894 BTU/h q internal, latent = 7,200 BTU/h q_{\text{internal, latent}} = 7{,}200\text{ BTU/h} q internal, latent = 7 , 200 BTU/h
At roughly 3.1 tons of internal gain alone , the lights and people in this suite outweigh a well-insulated envelope — which is exactly why a residential rule of thumb collapses on commercial work.
3. The Ventilation Load
Outdoor air is introduced deliberately, so its load lands on the coil , not on the room. The three standard-air constants are the ones to memorize: q sensible = 1.08 × CFM × Δ T ( ∘ F ) q_{\text{sensible}} = 1.08 \times \text{CFM} \times \Delta T\ (^\circ\text{F}) q sensible = 1.08 × CFM × Δ T ( ∘ F ) q latent = 0.68 × CFM × Δ W ( grains/lb ) q_{\text{latent}} = 0.68 \times \text{CFM} \times \Delta W\ (\text{grains/lb}) q latent = 0.68 × CFM × Δ W ( grains/lb ) q total = 4.5 × CFM × Δ h ( BTU/lb ) q_{\text{total}} = 4.5 \times \text{CFM} \times \Delta h\ (\text{BTU/lb}) q total = 4.5 × CFM × Δ h ( BTU/lb )
The constants derive from standard air at 0.075 lb/ft 3 0.075\text{ lb/ft}^3 0.075 lb/ft 3 : 1.08 = 60 × 0.075 × 0.24 1.08 = 60 \times 0.075 \times 0.24 1.08 = 60 × 0.075 × 0.24 ; 0.68 = 60 × 0.075 × 1,061 ÷ 7,000 0.68 = 60 \times 0.075 \times 1{,}061 \div 7{,}000 0.68 = 60 × 0.075 × 1 , 061 ÷ 7 , 000 ; 4.5 = 60 × 0.075 4.5 = 60 \times 0.075 4.5 = 60 × 0.075 .
Determining the Outdoor Air Rate
The North Carolina Mechanical Code Table 403.3 ventilation rates govern; Manual N uses the same values. The rate is the sum of a people-based term and an area-based term: OA CFM = ( R p × P z ) + ( R a × A z ) \text{OA CFM} = (R_p \times P_z) + (R_a \times A_z) OA CFM = ( R p × P z ) + ( R a × A z )
- Occupancy R p R_p R p (CFM/person) R a R_a R a (CFM/sq ft) Default density (per 1,000 sq ft)
- Office space 5 0.06 5
- Conference / meeting 5 0.06 50
- Retail sales 7.5 0.12 15
- Classroom (age 9 plus) 10 0.12 35
- Restaurant dining room 7.5 0.18 70
Worked Example — Ventilation Load, Same 2,400 sq ft Retail Suite OA CFM = ( 7.5 × 36 ) + ( 0.12 × 2,400 ) = 270 + 288 = 558 CFM \text{OA CFM} = (7.5 \times 36) + (0.12 \times 2{,}400) = 270 + 288 = 558\text{ CFM} OA CFM = ( 7.5 × 36 ) + ( 0.12 × 2 , 400 ) = 270 + 288 = 558 CFM
Cooling design at Raleigh: outdoor 92 ∘ F 92^\circ\text{F} 9 2 ∘ F db / 110 110 110 grains; indoor 75 ∘ F 75^\circ\text{F} 7 5 ∘ F db / 65 65 65 grains. q vent, sensible = 1.08 × 558 × ( 92 − 75 ) = 10,245 BTU/h q_{\text{vent, sensible}} = 1.08 \times 558 \times (92 - 75) = 10{,}245\text{ BTU/h} q vent, sensible = 1.08 × 558 × ( 92 − 75 ) = 10 , 245 BTU/h q vent, latent = 0.68 × 558 × ( 110 − 65 ) = 17,075 BTU/h q_{\text{vent, latent}} = 0.68 \times 558 \times (110 - 65) = 17{,}075\text{ BTU/h} q vent, latent = 0.68 × 558 × ( 110 − 65 ) = 17 , 075 BTU/h
Heating design at 20 ∘ F 20^\circ\text{F} 2 0 ∘ F outdoor, 70 ∘ F 70^\circ\text{F} 7 0 ∘ F indoor: q vent, heating = 1.08 × 558 × ( 70 − 20 ) = 30,132 BTU/h q_{\text{vent, heating}} = 1.08 \times 558 \times (70 - 20) = 30{,}132\text{ BTU/h} q vent, heating = 1.08 × 558 × ( 70 − 20 ) = 30 , 132 BTU/h
The ventilation latent load alone (17,075 BTU/h) exceeds the entire people latent load, and the ventilation heating load is larger than many small commercial envelope losses. Miss it and the equipment is undersized on both seasons.
4. Block Load, Zone Load and the Peak Hour
Room load sizes the outlet CFM for that room.
Zone load sizes the branch or terminal unit serving that thermostat zone.
Block load — the simultaneous peak for everything on one piece of equipment — sizes the equipment .
Because east glass peaks in the morning and west glass in the late afternoon, the block load is always less than the sum of the room peaks . Manual N therefore requires the designer to evaluate the load at more than one hour: an office with heavy west glazing frequently peaks at 4:00 or 5:00 p.m. , when the solar gain is high and the occupancy and lighting are still fully on, not at solar noon. SHR = q sensible q sensible + q latent \text{SHR} = \frac{q_{\text{sensible}}}{q_{\text{sensible}} + q_{\text{latent}}} SHR = q sensible + q latent q sensible
Commercial SHRs run lower than residential — a restaurant or classroom can fall to 0.65 – 0.75 — which forces selection of equipment with the latent capability to match, not simply the nominal tonnage.
Putting the Retail Suite Together
- Component Sensible (BTU/h) Latent (BTU/h)
- Envelope + glass + infiltration 28,400 3,100
- Internal gains (people, lights, equipment) 36,894 7,200
- Ventilation (coil load) 10,245 17,075
Totals 75,539 27,375 q total = 75,539 + 27,375 = 102,914 BTU/h = 8.58 tons q_{\text{total}} = 75{,}539 + 27{,}375 = 102{,}914\text{ BTU/h} = 8.58\text{ tons} q total = 75 , 539 + 27 , 375 = 102 , 914 BTU/h = 8.58 tons SHR = 75,539 102,914 = 0.734 \text{SHR} = \frac{75{,}539}{102{,}914} = 0.734 SHR = 102 , 914 75 , 539 = 0.734
At 8.58 tons this suite stays inside the Heating Group 3 fifteen-ton ceiling — but if the same tenant space is one of four interconnected suites on a common system, 21 NCAC 50 .0501(a) aggregates them and the project becomes Heating Group 2 work.