Study guide

12.3 Systematic HVAC Diagnostics, Superheat/Subcooling & Airflow Troubleshooting

North Carolina HVAC Contractor License Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: North Carolina HVAC Licensing Framework & Board Jurisprudence

1.1 NC Dual-Board Regulatory Structure & General Statutes 1.2 Heating Classifications, Groups & Scopes 1.3 Examination Prerequisites, Qualifier Responsibilities & Disciplinary Rules 1.4 Examination Logistics, Reference Books & Code Editions

2 Chapter 2: North Carolina Business Organizations, Contracts & Lien Law

2.1 Construction Contracts, Project Management & Bidding 2.2 North Carolina Mechanics' Lien Law & Bond Claims 2.3 Business Organizations, Financial Management & Taxation

3 Chapter 3: Construction Safety, Electrical Safety & EPA 608

3.1 OSHA 1926 Construction Safety & Job Site Protocols 3.2 Electrical Safety, NFPA 70E & Lockout/Tagout (LOTO) 3.3 EPA Section 608 & Refrigerant Transition Regulations

4 Chapter 4: Thermodynamics, Refrigeration Cycle & Psychrometrics

4.1 Fundamentals of Thermodynamics & Heat Transfer 4.2 The Mechanical Refrigeration Cycle & Component Dynamics 4.3 Psychrometric Properties, Air Processes & Chart Navigation

5 Chapter 5: ACCA Manual J & Manual N Load Calculations

5.1 Manual J Design Conditions & Thermal Parameters 5.2 Fenestration, Opaque Envelope & Internal Heat Gains 5.3 Infiltration, Duct Losses & Total Block Load Synthesis 5.4 ACCA Manual N Commercial Load Calculation

6 Chapter 6: ACCA Manual D & Manual Q Duct Design & Air Distribution

6.1 Fan Laws, Airflow Dynamics & Total External Static Pressure 6.2 ACCA Manual D Sizing Protocol & Friction Rate Calculation 6.3 SMACNA Duct Construction, Fittings & Air Balancing 6.4 ACCA Manual Q Commercial Low-Pressure Duct Design

7 Chapter 7: Forced Air Heating, Gas Furnaces & Fuel Piping

7.1 Natural Gas & Propane Combustion Fundamentals 7.2 Gas Furnace Operation, Sequence of Control & Diagnostics 7.3 Fuel Oil Heating Systems & Code-Compliant Fuel Gas Piping

8 Chapter 8: Heat Pumps, Inverters & Commercial System Selection (Manual CS)

8.1 Heat Pump Operating Principles, Reversing Valves & Physics 8.2 Defrost Controls, Supplemental Electric Heat & Balance Points 8.3 Inverter Mini-Splits & Variable Refrigerant Flow (VRF) Systems 8.4 Manual CS: Commercial Applications, Systems & Equipment

9 Chapter 9: Hydronic Heating, Steam Systems & Boilers (H1)

9.1 Hydronic Fundamentals, Boiler Classifications & Steam Systems 9.2 Hydronic Piping Layouts, Circulator Pumps & Head Loss Calculations 9.3 Boiler Trim, Expansion Tanks, Air Elimination & Safety Controls 9.4 The NC Uniform Boiler & Pressure Vessel Act (H1 Reference)

10 Chapter 10: Commercial Refrigeration & NC Board Regulations

10.1 NC State Board of Refrigeration Contractors Statutes & Licensure 10.2 Commercial Refrigeration Systems, Multiplex Racks & Defrost Protocols 10.3 Walk-In Coolers, Freezers, Evaporator Pressure Regulators & Valves

11 Chapter 11: NC Administration, Mechanical, Fuel Gas & Energy Codes

11.1 North Carolina Mechanical Code: Equipment Access, Clearances & Condensate 11.2 Ventilation Rates, Exhaust Systems & Duct Smoke Detection 11.3 NC Fuel Gas Code: Combustion Air, Venting & Gas Appliance Installation 11.4 NC Energy Conservation Code: Duct Testing, Envelope & Efficiency Standards 11.5 NC Administrative Code & Policies: Permits, Inspections & Plan Review

12 Chapter 12: Electrical Fundamentals, Motor Controls & Diagnostics

12.1 HVAC Electrical Fundamentals, Circuit Schematics & Power Distribution 12.2 Electric Motors, Capacitors & Motor Controls 12.3 Systematic HVAC Diagnostics, Superheat/Subcooling & Airflow Troubleshooting 12.4 System Commissioning, Testing, Adjusting & Balancing (TAB)

12.3 Systematic HVAC Diagnostics, Superheat/Subcooling & Airflow Troubleshooting

Key Takeaways Explain This Topic AI

Systematic troubleshooting follows a logical isolation methodology: verifying high-voltage power supply, confirming 24VAC control transformer output, checking safety interlocks in series, and testing individual loads under dynamic conditions.

The thermodynamic diagnostic matrix cross-references Suction Pressure, Head Pressure, Superheat (SH), Subcooling (SC), and Compressor Amperage to differentiate between undercharge, overcharge, liquid line restrictions, low airflow, and defective compressor valves.

A liquid line restriction (such as a clogged filter-drier) produces Low Suction Pressure, High Superheat, Low-to-Normal Head Pressure, High Subcooling upstream, and a measurable temperature drop (> 2°F - 3°F) across the filter-drier body.

Compressor electrical diagnostics require verifying winding resistance symmetry (R_SR = R_CS + R_CR) and performing DC insulation resistance testing with a megohmmeter (Megger), where readings below 20-50 Megohms indicate severe moisture/acid contamination and below 1 Megohm indicates a grounded winding.

Hopscotch voltage troubleshooting isolates open switches in a series safety string (high pressure, low pressure, freeze stat, limit switches) by holding one meter lead on common (C) and stepping the other lead sequentially across each switch terminal.

Last updated: August 2026

Systematic HVAC Diagnostics, Superheat/Subcooling & Airflow Troubleshooting

Diagnostic Philosophy: Systematic troubleshooting separates elite HVAC contractors from "parts changers." Rather than guessing or swapping components, a technician systematically gathers quantitative electrical, thermodynamic, and psychrometric measurements, compares them to thermodynamic physics and manufacturer specifications, and isolates the precise root cause of system failure.

The Thermodynamic Diagnostic Matrix: Superheat & Subcooling Analysis

Refrigeration system operating health is verified by simultaneously measuring four primary parameters:

Evaporating (Suction) Saturation Temperature & Pressure ( T evap sat , P suction T_{\text{evap sat}}, P_{\text{suction}} T evap sat ​ , P suction ​ )

Condensing (Liquid) Saturation Temperature & Pressure ( T cond sat , P liquid T_{\text{cond sat}}, P_{\text{liquid}} T cond sat ​ , P liquid ​ )

Total Superheat ( S H SH S H ): S H = T suction line − T evap sat SH = T_{\text{suction line}} - T_{\text{evap sat}} S H = T suction line ​ − T evap sat ​ (Evaluates evaporator refrigerant loading and protects compressor from liquid floodback)

Subcooling ( S C SC SC ): S C = T cond sat − T liquid line SC = T_{\text{cond sat}} - T_{\text{liquid line}} SC = T cond sat ​ − T liquid line ​ (Evaluates condenser refrigerant liquid packing and ensures a solid column of liquid enters the metering device) +-----------------------------------------------------------------------------------------------------------------+

| THE 8-POINT HVAC THERMODYNAMIC DIAGNOSTIC MATRIX |

+------------------------------------+------------------+---------------+-------------+------------+--------------+

| System Operating Fault | Suction Pressure | Head Pressure | Superheat | Subcooling | Comp Current |

+------------------------------------+------------------+---------------+-------------+------------+--------------+

  • | 1. Refrigerant Undercharge | LOW | LOW | HIGH (>20°F)| LOW (<4°F) | LOW |
  • | 2. Refrigerant Overcharge | HIGH | HIGH | LOW (<8°F) | HIGH (>15°F| HIGH |
  • | 3. Low Indoor Airflow / Dirty Coil | LOW | LOW | LOW (<8°F) | NORMAL/HIGH| LOW / NORMAL |
  • | 4. Low Outdoor Airflow/Dirty Cond. | HIGH | HIGH | NORMAL | NORMAL/HIGH| HIGH |
  • | 5. Liquid Line Restriction (Drier) | LOW | LOW / NORMAL | HIGH (>20°F)| HIGH (>15°F| LOW |
  • | 6. Inefficient Compressor (Valves) | HIGH | LOW | HIGH (>20°F)| LOW (<5°F) | LOW |
  • | 7. TXV Stuck Open (Overfeeding) | HIGH | NORMAL / LOW | VERY LOW(0-4| NORMAL | NORMAL / HIGH|
  • | 8. TXV Stuck Closed (Underfeeding) | LOW | NORMAL / LOW | VERY HIGH | HIGH | LOW |

+------------------------------------+------------------+---------------+-------------+------------+--------------+

  • Critical Diagnostic Distinctions
  • Differentiating Undercharge from Liquid Line Restriction

Both faults produce low suction pressure, high superheat, and low compressor amperage. However:

Refrigerant Undercharge: Has LOW Subcooling ( < 4 ∘ F < 4^\circ\text{F} < 4 ∘ F ) because there is insufficient refrigerant mass in the system to pack the bottom tubes of the condenser coil.

Liquid Line Restriction: Has HIGH Subcooling ( > 15 ∘ F − 20 ∘ F > 15^\circ\text{F} - 20^\circ\text{F} > 1 5 ∘ F − 2 0 ∘ F ) because refrigerant backs up behind the restriction in the condenser coil, while starved refrigerant downstream evaporates rapidly to create high superheat. Furthermore, a restricted filter-drier will exhibit a temperature drop Δ T ≥ 2 ∘ F − 3 ∘ F \Delta T \ge 2^\circ\text{F} - 3^\circ\text{F} Δ T ≥ 2 ∘ F − 3 ∘ F between its inlet and outlet copper lines.

Differentiating Low Indoor Airflow from Inefficient Compressor

Low Indoor Airflow (Dirty Filter/Coil, Slow Blower): Causes low suction pressure and LOW Superheat ( 0 ∘ F − 5 ∘ F 0^\circ\text{F} - 5^\circ\text{F} 0 ∘ F − 5 ∘ F ) because the coil lacks heat load to boil the liquid refrigerant, creating risk of compressor liquid floodback.

Inefficient Compressor (Leaking Internal Discharge Valves / Blown Gasket / Scroll Bypass): Causes HIGH Suction Pressure and LOW Head Pressure (compressed gas bypasses internally back to suction), high superheat, low amp draw, and a very low compression ratio.

Hopscotch Voltage Troubleshooting Across Safety Circuits

The Hopscotch Method is a systematic voltage measurement procedure used to isolate an open switch, blown limit, or broken conductor in a 24VAC safety interlock circuit without disconnecting any wires. [ 24VAC Transformer Secondary ]

  • (R) --------------------- (C) [Common Reference Lead]
  • | |
  • v |
  • [ 3A Fuse ] |
  • | |
  • v |
  • (1) [ High-Pressure Switch ] |
  • | |
  • v |
  • (2) [ Low-Pressure Switch ] |
  • | |
  • v |
  • (3) [ Freeze Stat Switch ] |
  • | |
  • v |
  • (4) [ Time Delay Relay ] |
  • | |
  • v |
  • (5) [ Contactor Coil ] ------------+
  • Step-by-Step Hopscotch Procedure

Establish Common Reference: Place the digital multimeter's black test lead permanently on the 24VAC Common ("C") terminal of the control transformer or terminal strip.

Verify Source Voltage: Place the red test lead on the "R" terminal . The meter must read 24 VAC − 28 VAC 24\text{VAC} - 28\text{VAC} 24 VAC − 28 VAC . If 0 V 0\text{V} 0 V , the transformer primary power is lost, the transformer is burned out, or the secondary fuse is blown.

Hopscotch Down the Circuit Rung: Probe each terminal connection sequentially from upstream power toward the load (Contactor Coil):

Probe Terminal 1 (Inlet of High-Pressure Switch) → 24 VAC \rightarrow 24\text{VAC} → 24 VAC (Power reaching switch).

Probe Terminal 2 (Outlet of High-Pressure Switch) → 24 VAC \rightarrow 24\text{VAC} → 24 VAC (Switch is closed/passing power).

Probe Terminal 3 (Inlet of Low-Pressure Switch) → 24 VAC \rightarrow 24\text{VAC} → 24 VAC .

Probe Terminal 4 (Outlet of Low-Pressure Switch) → 0 VAC \rightarrow 0\text{VAC} → 0 VAC !

Root Cause Conclusion: Voltage drops from 24 VAC 24\text{VAC} 24 VAC to 0 VAC 0\text{VAC} 0 VAC across the Low-Pressure Switch. The Low-Pressure Switch is OPEN (either tripped due to lost refrigerant charge, low ambient temperature, or a defective switch mechanism).

Note

Direct Voltage Drop Test: If a technician measures voltage directly across the two terminals of any single switch in a series circuit while power is applied and demand is present:

0 Volts AC 0\text{ Volts AC} 0 Volts AC across switch contacts: Switch is CLOSED (normal closed circuit with zero resistance).

24 Volts AC 24\text{ Volts AC} 24 Volts AC across switch contacts: Switch is OPEN (full circuit potential difference appears across open contacts).

Electric Motor & Compressor Winding Diagnostics

When a compressor trips its circuit breaker, hums without starting, or fails to run, the technician must perform three distinct winding tests using an ohmmeter and a megohmmeter (Megger). Single-Phase Compressor Winding Terminal Geometry:

  • [ COMMON (C) ]
  • / \
  • / \
  • R_CS (Start Winding) R_CR (Run Winding)
  • (Higher Resistance) (Lower Resistance)
  • / \
  • / \
  • [ START (S) ] ----------- [ RUN (R) ]
  • R_SR (Total Winding Series)
  • (R_SR = R_CS + R_CR)
  • 1. Winding Resistance Symmetry Test (Unpowered Ohms)

Disconnect all wiring from the compressor terminals (C, S, R). Measure resistance across all three terminal pairs with a calibrated digital ohmmeter:

Run Winding Resistance ( R C R R_{CR} R CR ​ ): Common to Run (typically 0.5 Ω − 3.0 Ω 0.5\,\Omega - 3.0\,\Omega 0.5 Ω − 3.0 Ω on residential compressors; lowest resistance because of heavier gauge wire).

Start Winding Resistance ( R C S R_{CS} R CS ​ ): Common to Start (typically 1.5 Ω − 7.0 Ω 1.5\,\Omega - 7.0\,\Omega 1.5 Ω − 7.0 Ω ; higher resistance due to thinner, multi-turn wire).

Series Resistance ( R S R R_{SR} R SR ​ ): Start to Run. Mathematical Law: R S R = R C S + R C R R_{SR} = R_{CS} + R_{CR} R SR ​ = R CS ​ + R CR ​

Diagnostic Winding Interpretation

Measured Condition Diagnostic Meaning Action Required

R S R = R C S + R C R R_{SR} = R_{CS} + R_{CR} R SR ​ = R CS ​ + R CR ​ Windings Electrically Intact: Normal winding continuity. Test insulation resistance and mechanical components.

Infinity ( ∞ Ω \infty\,\Omega ∞ Ω / O.L.) on C − S C-S C − S and C − R C-R C − R , but normal on S − R S-R S − R Internal Thermal Overload Open: Compressor motor is overheated. Allow compressor to cool down with wet towels; retest when switch resets.

Infinity ( ∞ Ω \infty\,\Omega ∞ Ω / O.L.) across any pair after fully cooled Open Winding: Internal copper conductor has burned open. Replace compressor.

R S R < R C S + R C R R_{SR} < R_{CS} + R_{CR} R SR ​ < R CS ​ + R CR ​ (or abnormally low ohms) Turn-to-Turn Short: Insulation burned, shorting turns. Replace compressor.

2. Insulation Resistance Testing (Megohmmeter / Megger)

A standard multimeter applies only 3 V − 9 V 3\text{V} - 9\text{V} 3 V − 9 V DC, which cannot detect microscopic insulation breakdown under operating high voltages. A Megohmmeter applies a test potential of 500 V or 1 , 000 V 500\text{V}\text{ or }1,000\text{V} 500 V or 1 , 000 V DC to measure winding insulation resistance to earth ground: Megohmmeter Insulation Resistance Interpretation Table:

├── > 100 Megohms (> 100 MΩ): PERFECT - Factory-grade winding insulation.

├── 50 to 100 Megohms (50-100 MΩ): GOOD - Normal operating aged equipment.

├── 20 to 50 Megohms (20-50 MΩ): CAUTION - Severe moisture, acid, or insulation degradation.

├── 1 to 20 Megohms (1-20 MΩ): FAILING - Imminent catastrophic failure; motor burnout likely.

└── < 1 Megohm (< 1 MΩ): DEAD SHORT / GROUNDED - Replace compressor immediately.

Psychrometric & Airflow Diagnostics: Temperature Splits

Verifying sensible and latent heat transfer across indoor and outdoor coils requires checking operating temperature splits.

1. Evaporator Air Temperature Drop ( Δ T evap \Delta T_{\text{evap}} Δ T evap ​ ) Δ T evap = T Return Air Dry Bulb − T Supply Air Dry Bulb \Delta T_{\text{evap}} = T_{\text{Return Air Dry Bulb}} - T_{\text{Supply Air Dry Bulb}} Δ T evap ​ = T Return Air Dry Bulb ​ − T Supply Air Dry Bulb ​

Target Split under standard conditions ( 75 ∘ F 75^\circ\text{F} 7 5 ∘ F indoor dry bulb, 50 % 50\% 50% relative humidity / 63 ∘ F 63^\circ\text{F} 6 3 ∘ F wet bulb): 18 ∘ F − 22 ∘ F 18^\circ\text{F} - 22^\circ\text{F} 1 8 ∘ F − 2 2 ∘ F .

High Temperature Drop ( Δ T > 24 ∘ F \Delta T > 24^\circ\text{F} Δ T > 2 4 ∘ F ): Indicates Low Airflow (restricted air filter, undersized ductwork, slipping blower belt, closed dampers, or dirty evaporator coil).

Low Temperature Drop ( Δ T < 15 ∘ F \Delta T < 15^\circ\text{F} Δ T < 1 5 ∘ F ): Indicates High Airflow , low refrigerant charge, restricted metering device, or inefficient compressor valves.

2. Condenser Temperature Difference (CTD / Condenser Split) CTD = T Condensing Saturation − T Ambient Entering Air \text{CTD} = T_{\text{Condensing Saturation}} - T_{\text{Ambient Entering Air}} CTD = T Condensing Saturation ​ − T Ambient Entering Air ​

Standard Efficiency Systems (10 - 13 SEER): CTD ≈ 25 ∘ F − 30 ∘ F \text{CTD} \approx 25^\circ\text{F} - 30^\circ\text{F} CTD ≈ 2 5 ∘ F − 3 0 ∘ F

High Efficiency Systems (14 - 16+ SEER2): CTD ≈ 15 ∘ F − 20 ∘ F \text{CTD} \approx 15^\circ\text{F} - 20^\circ\text{F} CTD ≈ 1 5 ∘ F − 2 0 ∘ F

Microchannel / Ultra-High Inverter Systems: CTD ≈ 8 ∘ F − 12 ∘ F \text{CTD} \approx 8^\circ\text{F} - 12^\circ\text{F} CTD ≈ 8 ∘ F − 1 2 ∘ F

  • Step-by-Step Worked Technical Examples
  • Example 1: Refrigerant Diagnostic Case Study (Restriction vs Undercharge)

Problem: A technician in Raleigh, NC inspects an R-410A split-system AC operating on an 85 ∘ F 85^\circ\text{F} 8 5 ∘ F summer afternoon and records:

Suction Line Pressure: 95.0 psig 95.0\text{ psig} 95.0 psig ( T evap sat = 29.0 ∘ F T_{\text{evap sat}} = 29.0^\circ\text{F} T evap sat ​ = 29. 0 ∘ F )

Suction Line Temperature: 64.0 ∘ F 64.0^\circ\text{F} 64. 0 ∘ F

Liquid Line Pressure: 290.0 psig 290.0\text{ psig} 290.0 psig ( T cond sat = 94.0 ∘ F T_{\text{cond sat}} = 94.0^\circ\text{F} T cond sat ​ = 94. 0 ∘ F )

Liquid Line Temperature entering TXV: 72.0 ∘ F 72.0^\circ\text{F} 72. 0 ∘ F

Filter-Drier Inlet Temp: 88.0 ∘ F 88.0^\circ\text{F} 88. 0 ∘ F , Filter-Drier Outlet Temp: 74.0 ∘ F 74.0^\circ\text{F} 74. 0 ∘ F

Compressor Amperage: 9.8 A 9.8\text{ A} 9.8 A (Nameplate RLA: 16.5 A 16.5\text{ A} 16.5 A )

Calculate: (1) Total Superheat, (2) Subcooling, and (3) Identify the exact fault and required corrective action.

Solution:

Calculate Total Superheat: S H = T suction line − T evap sat = 64.0 ∘ F − 29.0 ∘ F = 35.0 ∘ F ( Target: 8 ∘ F − 12 ∘ F ) SH = T_{\text{suction line}} - T_{\text{evap sat}} = 64.0^\circ\text{F} - 29.0^\circ\text{F} = 35.0^\circ\text{F} \quad (\text{Target: } 8^\circ\text{F} - 12^\circ\text{F}) S H = T suction line ​ − T evap sat ​ = 64. 0 ∘ F − 29. 0 ∘ F = 35. 0 ∘ F ( Target: 8 ∘ F − 1 2 ∘ F )

Calculate Subcooling: S C = T cond sat − T liquid line = 94.0 ∘ F − 72.0 ∘ F = 22.0 ∘ F ( Target: 10 ∘ F ± 2 ∘ F ) SC = T_{\text{cond sat}} - T_{\text{liquid line}} = 94.0^\circ\text{F} - 72.0^\circ\text{F} = 22.0^\circ\text{F} \quad (\text{Target: } 10^\circ\text{F} \pm 2^\circ\text{F}) SC = T cond sat ​ − T liquid line ​ = 94. 0 ∘ F − 72. 0 ∘ F = 22. 0 ∘ F ( Target: 1 0 ∘ F ± 2 ∘ F )

Analyze Diagnostic Indicators:

Suction Pressure is LOW ( 95 psig 95\text{ psig} 95 psig / 29 ∘ F 29^\circ\text{F} 2 9 ∘ F saturation; freezing risk).

Superheat is VERY HIGH ( 35 ∘ F 35^\circ\text{F} 3 5 ∘ F ).

Subcooling is VERY HIGH ( 22 ∘ F 22^\circ\text{F} 2 2 ∘ F ).

Filter-drier temperature drop: Δ T drier = 88.0 ∘ F − 74.0 ∘ F = 14.0 ∘ F \Delta T_{\text{drier}} = 88.0^\circ\text{F} - 74.0^\circ\text{F} = 14.0^\circ\text{F} Δ T drier ​ = 88. 0 ∘ F − 74. 0 ∘ F = 14. 0 ∘ F ! (Allowable: < 2.0 ∘ F < 2.0^\circ\text{F} < 2. 0 ∘ F ).

Diagnosis: Severe Liquid Line Filter-Drier Restriction . Refrigerant is backing up into the condenser (elevating subcooling), while the evaporator is starved of liquid (driving up superheat and dropping suction pressure). The filter-drier is acting as a secondary expansion device. Corrective Action: Recover refrigerant, replace liquid line filter-drier, pull a 500-micron vacuum, and recharge to factory nameplate weight.

Example 2: Compressor Winding Resistance Verification

Problem: A technician measures the terminal resistance of a 3-ton single-phase compressor with an unpowered digital ohmmeter:

  • Terminal A to Terminal B: 1.20 Ω 1.20\,\Omega 1.20 Ω
  • Terminal B to Terminal C: 3.80 Ω 3.80\,\Omega 3.80 Ω
  • Terminal A to Terminal C: 2.60 Ω 2.60\,\Omega 2.60 Ω

Determine: (1) Which pin is Common (C), Start (S), and Run (R), and (2) verify whether the motor windings are electrically normal.

Solution:

Identify Terminals Using Resistance Geometry:

The highest resistance reading ( 3.80 Ω 3.80\,\Omega 3.80 Ω between B and C) is the Start-to-Run ( R S R R_{SR} R SR ​ ) winding series. The remaining terminal is Common (C) = Terminal A .

From Common (Terminal A):

Resistance to Terminal B is 1.20 Ω 1.20\,\Omega 1.20 Ω (lowest reading) ⟹ \implies ⟹ Run (R) = Terminal B ( R C R = 1.20 Ω R_{CR} = 1.20\,\Omega R CR ​ = 1.20 Ω ).

Resistance to Terminal C is 2.60 Ω 2.60\,\Omega 2.60 Ω (higher reading) ⟹ \implies ⟹ Start (S) = Terminal C ( R C S = 2.60 Ω R_{CS} = 2.60\,\Omega R CS ​ = 2.60 Ω ).

Verify Winding Mathematics: R C S + R C R = 2.60 Ω + 1.20 Ω = 3.80 Ω R_{CS} + R_{CR} = 2.60\,\Omega + 1.20\,\Omega = 3.80\,\Omega R CS ​ + R CR ​ = 2.60 Ω + 1.20 Ω = 3.80 Ω R S R = 3.80 Ω R_{SR} = 3.80\,\Omega R SR ​ = 3.80 Ω

Since R S R = R C S + R C R R_{SR} = R_{CS} + R_{CR} R SR ​ = R CS ​ + R CR ​ exactly, the compressor motor windings have perfect electrical continuity and zero turn-to-turn shorts.

Example 3: Hopscotch Voltage Analysis on Packaged Rooftop Unit

Problem: A technician troubleshoots a commercial rooftop unit where the indoor blower runs but the compressor contactor will not pull in. Measuring with black lead on 24VAC Common, the technician measures:

  • Transformer secondary R: 26.2 VAC 26.2\text{ VAC} 26.2 VAC
  • Thermostat Y1 output: 26.1 VAC 26.1\text{ VAC} 26.1 VAC
  • High-Pressure Switch Terminal 1 (Inlet): 26.1 VAC 26.1\text{ VAC} 26.1 VAC
  • High-Pressure Switch Terminal 2 (Outlet): 26.1 VAC 26.1\text{ VAC} 26.1 VAC
  • Discharge Temperature Limit Switch Terminal 1 (Inlet): 26.1 VAC 26.1\text{ VAC} 26.1 VAC
  • Discharge Temperature Limit Switch Terminal 2 (Outlet): 0.0 VAC 0.0\text{ VAC} 0.0 VAC
  • Contactor Coil 24V Terminal: 0.0 VAC 0.0\text{ VAC} 0.0 VAC

Identify the faulted component and state the diagnostic conclusion.

Solution:

Analyze Circuit Continuity:

Power is present ( 26.1 VAC 26.1\text{ VAC} 26.1 VAC ) up to the inlet of the Discharge Temperature Limit Switch.

Voltage on the outlet side of the switch drops to 0.0 VAC 0.0\text{ VAC} 0.0 VAC .

Direct voltage across the switch contacts measures 26.1 VAC − 0.0 VAC = 26.1 VAC 26.1\text{ VAC} - 0.0\text{ VAC} = 26.1\text{ VAC} 26.1 VAC − 0.0 VAC = 26.1 VAC , confirming an open circuit across the switch.

Diagnostic Conclusion:

The Discharge Temperature Limit Switch is OPEN . The technician must inspect for severe compressor overheating, loss of suction vapor cooling, or a failed sensor switch.

Loading diagram... Hopscotch Voltage Troubleshooting Sequence