4.3 Psychrometric Properties, Air Processes & Chart Navigation
North Carolina HVAC Contractor License Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: North Carolina HVAC Licensing Framework & Board Jurisprudence
1.1 NC Dual-Board Regulatory Structure & General Statutes 1.2 Heating Classifications, Groups & Scopes 1.3 Examination Prerequisites, Qualifier Responsibilities & Disciplinary Rules 1.4 Examination Logistics, Reference Books & Code Editions
2 Chapter 2: North Carolina Business Organizations, Contracts & Lien Law
2.1 Construction Contracts, Project Management & Bidding 2.2 North Carolina Mechanics' Lien Law & Bond Claims 2.3 Business Organizations, Financial Management & Taxation
3 Chapter 3: Construction Safety, Electrical Safety & EPA 608
3.1 OSHA 1926 Construction Safety & Job Site Protocols 3.2 Electrical Safety, NFPA 70E & Lockout/Tagout (LOTO) 3.3 EPA Section 608 & Refrigerant Transition Regulations
4 Chapter 4: Thermodynamics, Refrigeration Cycle & Psychrometrics
4.1 Fundamentals of Thermodynamics & Heat Transfer 4.2 The Mechanical Refrigeration Cycle & Component Dynamics 4.3 Psychrometric Properties, Air Processes & Chart Navigation
5 Chapter 5: ACCA Manual J & Manual N Load Calculations
5.1 Manual J Design Conditions & Thermal Parameters 5.2 Fenestration, Opaque Envelope & Internal Heat Gains 5.3 Infiltration, Duct Losses & Total Block Load Synthesis 5.4 ACCA Manual N Commercial Load Calculation
6 Chapter 6: ACCA Manual D & Manual Q Duct Design & Air Distribution
6.1 Fan Laws, Airflow Dynamics & Total External Static Pressure 6.2 ACCA Manual D Sizing Protocol & Friction Rate Calculation 6.3 SMACNA Duct Construction, Fittings & Air Balancing 6.4 ACCA Manual Q Commercial Low-Pressure Duct Design
7 Chapter 7: Forced Air Heating, Gas Furnaces & Fuel Piping
7.1 Natural Gas & Propane Combustion Fundamentals 7.2 Gas Furnace Operation, Sequence of Control & Diagnostics 7.3 Fuel Oil Heating Systems & Code-Compliant Fuel Gas Piping
8 Chapter 8: Heat Pumps, Inverters & Commercial System Selection (Manual CS)
8.1 Heat Pump Operating Principles, Reversing Valves & Physics 8.2 Defrost Controls, Supplemental Electric Heat & Balance Points 8.3 Inverter Mini-Splits & Variable Refrigerant Flow (VRF) Systems 8.4 Manual CS: Commercial Applications, Systems & Equipment
9 Chapter 9: Hydronic Heating, Steam Systems & Boilers (H1)
9.1 Hydronic Fundamentals, Boiler Classifications & Steam Systems 9.2 Hydronic Piping Layouts, Circulator Pumps & Head Loss Calculations 9.3 Boiler Trim, Expansion Tanks, Air Elimination & Safety Controls 9.4 The NC Uniform Boiler & Pressure Vessel Act (H1 Reference)
10 Chapter 10: Commercial Refrigeration & NC Board Regulations
10.1 NC State Board of Refrigeration Contractors Statutes & Licensure 10.2 Commercial Refrigeration Systems, Multiplex Racks & Defrost Protocols 10.3 Walk-In Coolers, Freezers, Evaporator Pressure Regulators & Valves
11 Chapter 11: NC Administration, Mechanical, Fuel Gas & Energy Codes
11.1 North Carolina Mechanical Code: Equipment Access, Clearances & Condensate 11.2 Ventilation Rates, Exhaust Systems & Duct Smoke Detection 11.3 NC Fuel Gas Code: Combustion Air, Venting & Gas Appliance Installation 11.4 NC Energy Conservation Code: Duct Testing, Envelope & Efficiency Standards 11.5 NC Administrative Code & Policies: Permits, Inspections & Plan Review
12 Chapter 12: Electrical Fundamentals, Motor Controls & Diagnostics
12.1 HVAC Electrical Fundamentals, Circuit Schematics & Power Distribution 12.2 Electric Motors, Capacitors & Motor Controls 12.3 Systematic HVAC Diagnostics, Superheat/Subcooling & Airflow Troubleshooting 12.4 System Commissioning, Testing, Adjusting & Balancing (TAB)
4.3 Psychrometric Properties, Air Processes & Chart Navigation
Key Takeaways Explain This Topic AI
The psychrometric chart graphically interrelates seven fundamental moist air properties: dry-bulb, wet-bulb, dew point, relative humidity, humidity ratio, specific volume, and enthalpy; establishing any two coordinates completely fixes the thermodynamic state point.
Standard air heat transfer equations quantify thermal exchange: Sensible Heat (qs = 1.08 × CFM × ΔT), Latent Heat (ql = 0.68 × CFM × ΔW_grains), and Total Heat (qt = 4.5 × CFM × Δh).
Sensible Heat Ratio (SHR = qs / qt) establishes the slope of the coil process line on the psychrometric chart, dictating the necessary coil Apparatus Dew Point (ADP) and airflow volume for effective moisture removal.
Adiabatic mixing of return air and outdoor ventilation air establishes a mixed air state situated along the straight connecting line in exact inverse proportion to the mass airflow fractions.
Evaporative cooling (adiabatic humidification) follows lines of constant enthalpy and constant wet-bulb temperature, reducing dry-bulb temperature while increasing relative humidity without external thermal energy transfer.
Last updated: August 2026
Psychrometric Properties, Air Processes & Chart Navigation
Core Principle: Psychrometrics is the study of the thermodynamic properties of moist air (a mixture of dry air and water vapor) and the effects of atmospheric conditions on human thermal comfort and materials. In HVAC design and diagnostics, knowing any two independent psychrometric properties allows a technician or engineer to locate the precise state point on the psychrometric chart and determine all remaining five properties.
The Seven Fundamental Psychrometric Properties +-----------------------------------------------------------------------------------+
- | THE 7 FUNDAMENTAL PSYCHROMETRIC PROPERTIES |
- +-----------------------------------------------------------------------------------+
- | 1. Dry-Bulb Temperature (DB): Sensible air temp | Bottom axis, vertical lines |
- | 2. Wet-Bulb Temperature (WB): Evaporative cooling | Saturation line, diagonals |
- | 3. Dew Point Temperature (DP): Condensation temp | Saturation line, horizontals |
- | 4. Relative Humidity (RH): Vapor pressure % | Curved lines (0% to 100%) |
- | 5. Humidity Ratio (W): Grains or lbs moisture / lb dry air | Right axis |
- | 6. Specific Volume (v): Cubic feet / lb dry air | Steep diagonal lines |
- | 7. Enthalpy (h): Total heat content (BTU/lb dry air) | Outer scale |
- +-----------------------------------------------------------------------------------+
- 1. Dry-Bulb Temperature ( D B / T db DB / T_{\text{db}} D B / T db )
Definition: The sensible temperature of air measured by a standard thermometer shielded from direct solar radiation and moisture.
Chart Representation: Located on the horizontal baseline axis at the bottom of the chart. Lines of constant dry-bulb extend vertically straight upward .
2. Wet-Bulb Temperature ( W B / T wb WB / T_{\text{wb}} W B / T wb )
Definition: The dynamic equilibrium temperature reached by a water-wetted thermometer wick exposed to rapid air movement ( > 900 FPM > 900\text{ FPM} > 900 FPM ). Reflects the evaporative cooling capacity of the surrounding air.
Chart Representation: Read along the curved saturation curve (100% RH line) on the upper left. Lines of constant wet-bulb extend diagonally downward to the right .
Diagnostic Rule: In unsaturated air, wet-bulb is always lower than dry-bulb due to evaporative cooling ( W B < D B WB < DB W B < D B ). At 100% saturation, D B = W B = D P DB = WB = DP D B = W B = D P .
3. Dew Point Temperature ( D P / T dp DP / T_{\text{dp}} D P / T dp )
Definition: The temperature to which air must be cooled at constant pressure and constant moisture content to reach 100% saturation, at which point water vapor begins to condense into liquid water.
Chart Representation: Read along the saturation curve . From any state point, move horizontally to the left to the 100% saturation curve to read dew point temperature.
HVAC Significance: Any surface (cooling coil, uninsulated ductwork, basement wall) whose temperature is below the surrounding air's dew point will form surface condensation.
4. Relative Humidity ( R H / ϕ RH / \phi R H / ϕ )
Definition: The ratio of the actual partial vapor pressure of water ( p v p_v p v ) to the saturation water vapor pressure ( p ws p_{\text{ws}} p ws ) at the same dry-bulb temperature, expressed as a percentage: R H = ( p v p ws ) T db × 100 % RH = \left( \frac{p_v}{p_{\text{ws}}} \right)_{T_{\text{db}}} \times 100\% R H = ( p ws p v ) T db × 100%
Chart Representation: Represented by curvilinear lines arching from the lower-left to the upper-right. The outermost curve represents 100% RH (Saturation Line) . Human comfort guidelines (ASHRAE Standard 55) recommend maintaining indoor relative humidity between 30 % 30\% 30% and 60 % 60\% 60% (ideally 45 % 45\% 45% to 50 % 50\% 50% ) to inhibit mold proliferation and dust mite growth.
5. Humidity Ratio ( W W W / Specific Humidity)
Definition: The actual mass of water vapor present per unit mass of dry air, expressed as pounds of moisture per pound of dry air ( lb w / lb d a \text{lb}_w/\text{lb}_{da} lb w / lb d a ) or grains of moisture per pound of dry air ( grains/lb \text{grains/lb} grains/lb ): 1 pound of water = 7 , 000 grains of moisture 1\text{ pound of water} = 7,000\text{ grains of moisture} 1 pound of water = 7 , 000 grains of moisture
Chart Representation: Located on the vertical axis on the far right side of the chart. Lines of constant humidity ratio run horizontally across the chart.
6. Specific Volume ( v v v )
Definition: The volume occupied by one pound of dry air plus its associated water vapor, expressed in cubic feet per pound of dry air ( ft 3 / lb d a \text{ft}^3/\text{lb}_{da} ft 3 / lb d a ).
Chart Representation: Represented by steep diagonal lines sloping upward to the left (typically ranging from 13.0 to 15.0 ft 3 / lb 13.0\text{ to }15.0\text{ ft}^3/\text{lb} 13.0 to 15.0 ft 3 / lb ).
Standard Air Density ( ρ std \rho_{\text{std}} ρ std ): At standard sea-level barometric conditions ( 29.92 in. Hg 29.92\text{ in. Hg} 29.92 in. Hg , 70 ∘ F 70^\circ\text{F} 7 0 ∘ F dry-bulb, standard density), specific volume is v = 13.33 ft 3 / lb v = 13.33\text{ ft}^3/\text{lb} v = 13.33 ft 3 / lb , yielding standard air density: ρ std = 1 v std = 1 13.333 ft 3 / lb = 0.075 lbs/ft 3 \rho_{\text{std}} = \frac{1}{v_{\text{std}}} = \frac{1}{13.333\text{ ft}^3/\text{lb}} = \mathbf{0.075\text{ lbs/ft}^3} ρ std = v std 1 = 13.333 ft 3 / lb 1 = 0.075 lbs/ft 3
7. Enthalpy ( h h h )
Definition: The total thermal energy content of the moist air mixture per unit mass of dry air, including the sensible heat of air and vapor plus the latent heat of the water vapor, expressed in BTU per pound of dry air \text{BTU per pound of dry air} BTU per pound of dry air ( BTU/lb d a \text{BTU/lb}_{da} BTU/lb d a ).
Chart Representation: Read on the external diagonal scale on the upper left periphery of the chart, running roughly parallel to lines of constant wet-bulb. Total Air Enthalpy ( h ) ≈ 0.240 ⋅ T db + W lbs ⋅ ( 1 , 061 + 0.444 ⋅ T db ) ( BTU/lb ) \text{Total Air Enthalpy } (h) \approx 0.240 \cdot T_{\text{db}} + W_{\text{lbs}} \cdot (1,061 + 0.444 \cdot T_{\text{db}}) \quad (\text{BTU/lb}) Total Air Enthalpy ( h ) ≈ 0.240 ⋅ T db + W lbs ⋅ ( 1 , 061 + 0.444 ⋅ T db ) ( BTU/lb )
Fundamental HVAC Airflow & Heat Transfer Equations
All HVAC air-side load calculations, psychrometric balancing, and capacity verifications rely on three standard equations derived from air density ( ρ = 0.075 lbs/ft 3 \rho = 0.075\text{ lbs/ft}^3 ρ = 0.075 lbs/ft 3 ) and specific heat ( c p = 0.240 BTU / ( lb ⋅ ∘ F ) c_p = 0.240\text{ BTU}/(\text{lb}\cdot^\circ\text{F}) c p = 0.240 BTU / ( lb ⋅ ∘ F ) ):
1. The Sensible Air Heat Equation q s = 1.08 × CFM × Δ T db ( BTU/hr ) q_s = 1.08 \times \text{CFM} \times \Delta T_{\text{db}} \quad (\text{BTU/hr}) q s = 1.08 × CFM × Δ T db ( BTU/hr )
Mathematical Derivation: q s = m ˙ × c p × Δ T = ( CFM × 60 min/hr × 0.075 lbs/ft 3 ) × 0.240 BTU / ( lb ⋅ ∘ F ) × Δ T q_s = \dot{m} \times c_p \times \Delta T = (\text{CFM} \times 60\text{ min/hr} \times 0.075\text{ lbs/ft}^3) \times 0.240\text{ BTU}/(\text{lb}\cdot^\circ\text{F}) \times \Delta T q s = m ˙ × c p × Δ T = ( CFM × 60 min/hr × 0.075 lbs/ft 3 ) × 0.240 BTU / ( lb ⋅ ∘ F ) × Δ T 60 × 0.075 × 0.240 = 1.08 60 \times 0.075 \times 0.240 = \mathbf{1.08} 60 × 0.075 × 0.240 = 1.08
2. The Latent Air Heat Equation q l = 0.68 × CFM × Δ W grains ( BTU/hr ) q_l = 0.68 \times \text{CFM} \times \Delta W_{\text{grains}} \quad (\text{BTU/hr}) q l = 0.68 × CFM × Δ W grains ( BTU/hr ) q l = 4 , 840 × CFM × Δ W lbs ( BTU/hr ) q_l = 4,840 \times \text{CFM} \times \Delta W_{\text{lbs}} \quad (\text{BTU/hr}) q l = 4 , 840 × CFM × Δ W lbs ( BTU/hr )
Mathematical Derivation: q l = ( CFM × 60 × 0.075 ) × 1 , 061 BTU/lb (latent heat) 7 , 000 grains/lb × Δ W grains q_l = (\text{CFM} \times 60 \times 0.075) \times \frac{1,061\text{ BTU/lb (latent heat)}}{7,000\text{ grains/lb}} \times \Delta W_{\text{grains}} q l = ( CFM × 60 × 0.075 ) × 7 , 000 grains/lb 1 , 061 BTU/lb (latent heat) × Δ W grains 60 × 0.075 × 1 , 061 7 , 000 = 0.682 ≈ 0.68 \frac{60 \times 0.075 \times 1,061}{7,000} = \mathbf{0.682} \approx \mathbf{0.68} 7 , 000 60 × 0.075 × 1 , 061 = 0.682 ≈ 0.68
3. The Total Air Heat Equation (Enthalpy Method) q t = 4.5 × CFM × Δ h ( BTU/hr ) q_t = 4.5 \times \text{CFM} \times \Delta h \quad (\text{BTU/hr}) q t = 4.5 × CFM × Δ h ( BTU/hr )
Mathematical Derivation: q t = m ˙ × Δ h = ( CFM × 60 min/hr × 0.075 lbs/ft 3 ) × Δ h q_t = \dot{m} \times \Delta h = (\text{CFM} \times 60\text{ min/hr} \times 0.075\text{ lbs/ft}^3) \times \Delta h q t = m ˙ × Δ h = ( CFM × 60 min/hr × 0.075 lbs/ft 3 ) × Δ h 60 × 0.075 = 4.5 60 \times 0.075 = \mathbf{4.5} 60 × 0.075 = 4.5
4. Sensible Heat Ratio ( S H R SHR S H R )
The Sensible Heat Ratio defines the proportion of total cooling load that is sensible (temperature reduction) versus latent (moisture dehumidification): SHR = q s q t = q s q s + q l \text{SHR} = \frac{q_s}{q_t} = \frac{q_s}{q_s + q_l} SHR = q t q s = q s + q l q s
Typical Residential Load in NC: Sensible Heat Ratio typically ranges from 0.70 to 0.80 0.70\text{ to }0.80 0.70 to 0.80 (70% sensible cooling, 30% latent dehumidification).
High Latent Loads: In humid coastal North Carolina climates with high ventilation rates, the SHR may drop to 0.60 to 0.65 0.60\text{ to }0.65 0.60 to 0.65 , requiring lower airflow rates ( 325 to 350 CFM/ton 325\text{ to }350\text{ CFM/ton} 325 to 350 CFM/ton ) to drop coil surface temperature below the dew point for enhanced dehumidification.
5. Moisture Removal Rate & Condensate Generation Condensate Mass Rate = q l 1 , 061 BTU/lb = 0.68 × CFM × Δ W grains 1 , 061 ( lbs/hr ) \text{Condensate Mass Rate} = \frac{q_l}{1,061\text{ BTU/lb}} = \frac{0.68 \times \text{CFM} \times \Delta W_{\text{grains}}}{1,061} \quad (\text{lbs/hr}) Condensate Mass Rate = 1 , 061 BTU/lb q l = 1 , 061 0.68 × CFM × Δ W grains ( lbs/hr ) Condensate Volume Rate (Gallons/Hour) = Condensate (lbs/hr) 8.34 lbs/gal \text{Condensate Volume Rate (Gallons/Hour)} = \frac{\text{Condensate (lbs/hr)}}{8.34\text{ lbs/gal}} Condensate Volume Rate (Gallons/Hour) = 8.34 lbs/gal Condensate (lbs/hr)
Psychrometric Air Processes & Chart Navigation
Air conditioning processes represent directional vector movements across the psychrometric chart: Psychrometric Process Vector Map
- HUMIDIFYING (Up: +W)
- ^
- |
- EVAPORATIVE COOLING | HEATING & HUMIDIFYING
- (Up-Left: -DB, +W, =h)| (Up-Right: +DB, +W, +h)
- \ | /
- \ | /
- \ | /
- SENSIBLE <----------+----------> SENSIBLE
- COOLING | HEATING
- (Left: -DB, =W, =DP) | (Right: +DB, =W, =DP)
- / | \
- / | \
- / | \
- COOLING & | CHEMICAL DEHUMIDIFICATION
- DEHUMIDIFYING | (Down-Right: +DB, -W)
- (Down-Left: -DB, -W) v
- DEHUMIDIFYING (Down: -W)
- Analysis of Standard Psychrometric Processes
Process Vector Direction Dry-Bulb ( D B DB D B ) Humidity Ratio ( W W W ) Dew Point ( D P DP D P ) Enthalpy ( h h h ) Relative Humidity ( R H RH R H )
- Sensible Heating Pure Horizontal Right Increases Constant Constant Increases Decreases
- Sensible Cooling Pure Horizontal Left Decreases Constant Constant Decreases Increases
Cooling & Dehumidification Diagonal Down-Left Decreases Decreases Decreases Decreases Increases toward saturation
Heating & Humidification Diagonal Up-Right Increases Increases Increases Increases Variable
Evaporative Cooling (Adiabatic) Diagonal Up-Left (along constant W B / h WB/h W B / h ) Decreases Increases Increases Constant Increases
Chemical Dehumidification Diagonal Down-Right (along constant h h h ) Increases Decreases Decreases Constant Decreases
Coil Bypass Factor ( B F BF BF ) & Apparatus Dew Point ( A D P ADP A D P )
When air passes through a cooling coil, not all air molecules make physical contact with the cold coil fins:
Apparatus Dew Point ( A D P ADP A D P ): The effective surface temperature of the cooling coil tubes and fins.
Contact Factor ( C F CF CF ): The percentage of air that physically contacts the coil surface and is cooled to the A D P ADP A D P .
Bypass Factor ( B F BF BF ): The percentage of air that passes through the coil fins without contacting the surface, remaining unconditioned: B F = 1 − C F = T leaving air − T ADP T entering air − T ADP BF = 1 - CF = \frac{T_{\text{leaving air}} - T_{\text{ADP}}}{T_{\text{entering air}} - T_{\text{ADP}}} BF = 1 − CF = T entering air − T ADP T leaving air − T ADP Modern residential multi-row coils typically achieve a Bypass Factor of 0.05 to 0.15 0.05\text{ to }0.15 0.05 to 0.15 ( 85 % to 95 % 85\%\text{ to }95\% 85% to 95% Contact Factor).
Adiabatic Mixing of Two Airstreams
When two air streams mix adiabatically (without external heat addition or loss), the resulting mixed air condition lies on the straight line connecting the two initial state points on the psychrometric chart, positioned inversely proportional to their mass flow rates: T db, mix = ( CFM 1 × T db, 1 ) + ( CFM 2 × T db, 2 ) CFM total T_{\text{db, mix}} = \frac{(\text{CFM}_1 \times T_{\text{db, 1}}) + (\text{CFM}_2 \times T_{\text{db, 2}})}{\text{CFM}_{\text{total}}} T db, mix = CFM total ( CFM 1 × T db, 1 ) + ( CFM 2 × T db, 2 ) W mix = ( CFM 1 × W 1 ) + ( CFM 2 × W 2 ) CFM total W_{\text{mix}} = \frac{(\text{CFM}_1 \times W_1) + (\text{CFM}_2 \times W_2)}{\text{CFM}_{\text{total}}} W mix = CFM total ( CFM 1 × W 1 ) + ( CFM 2 × W 2 ) h mix = ( CFM 1 × h 1 ) + ( CFM 2 × h 2 ) CFM total h_{\text{mix}} = \frac{(\text{CFM}_1 \times h_1) + (\text{CFM}_2 \times h_2)}{\text{CFM}_{\text{total}}} h mix = CFM total ( CFM 1 × h 1 ) + ( CFM 2 × h 2 )
- Step-by-Step Worked Technical Examples
- Example 1: Adiabatic Air Mixing Calculation
Problem: A commercial rooftop air handler operates with 2 , 000 CFM 2,000\text{ CFM} 2 , 000 CFM total supply airflow . The system mixes 1 , 600 CFM 1,600\text{ CFM} 1 , 600 CFM of Return Air (80%) at 75 ∘ F 75^\circ\text{F} 7 5 ∘ F DB and 63 ∘ F 63^\circ\text{F} 6 3 ∘ F WB ( h RA = 28.5 BTU/lb h_{\text{RA}} = 28.5\text{ BTU/lb} h RA = 28.5 BTU/lb , W RA = 65.0 grains/lb W_{\text{RA}} = 65.0\text{ grains/lb} W RA = 65.0 grains/lb ) with 400 CFM 400\text{ CFM} 400 CFM of Outdoor Ventilation Air (20%) at 95 ∘ F 95^\circ\text{F} 9 5 ∘ F DB and 78 ∘ F 78^\circ\text{F} 7 8 ∘ F WB ( h OA = 41.5 BTU/lb h_{\text{OA}} = 41.5\text{ BTU/lb} h OA = 41.5 BTU/lb , W OA = 118.0 grains/lb W_{\text{OA}} = 118.0\text{ grains/lb} W OA = 118.0 grains/lb ).
Calculate: (1) Mixed air dry-bulb temperature ( T db, mix T_{\text{db, mix}} T db, mix ), (2) Mixed air humidity ratio ( W mix W_{\text{mix}} W mix ), and (3) Mixed air enthalpy ( h mix h_{\text{mix}} h mix ).
Solution:
Mixed Air Dry-Bulb Temperature: T db, mix = ( 0.80 × 75 ∘ F ) + ( 0.20 × 95 ∘ F ) = 60.0 + 19.0 = 79.0 ∘ F T_{\text{db, mix}} = (0.80 \times 75^\circ\text{F}) + (0.20 \times 95^\circ\text{F}) = 60.0 + 19.0 = \mathbf{79.0^\circ\text{F}} T db, mix = ( 0.80 × 7 5 ∘ F ) + ( 0.20 × 9 5 ∘ F ) = 60.0 + 19.0 = 79. 0 ∘ F
Mixed Air Humidity Ratio: W mix = ( 0.80 × 65.0 ) + ( 0.20 × 118.0 ) = 52.0 + 23.6 = 75.6 grains/lb W_{\text{mix}} = (0.80 \times 65.0) + (0.20 \times 118.0) = 52.0 + 23.6 = \mathbf{75.6\text{ grains/lb}} W mix = ( 0.80 × 65.0 ) + ( 0.20 × 118.0 ) = 52.0 + 23.6 = 75.6 grains/lb
Mixed Air Enthalpy: h mix = ( 0.80 × 28.5 ) + ( 0.20 × 41.5 ) = 22.8 + 8.3 = 31.1 BTU/lb h_{\text{mix}} = (0.80 \times 28.5) + (0.20 \times 41.5) = 22.8 + 8.3 = \mathbf{31.1\text{ BTU/lb}} h mix = ( 0.80 × 28.5 ) + ( 0.20 × 41.5 ) = 22.8 + 8.3 = 31.1 BTU/lb
Example 2: Cooling Coil Capacity, SHR & Condensate Rate
Problem: An air conditioning evaporator coil receives 1 , 600 CFM 1,600\text{ CFM} 1 , 600 CFM of entering air at 80.0 ∘ F 80.0^\circ\text{F} 80. 0 ∘ F DB and 67.0 ∘ F 67.0^\circ\text{F} 67. 0 ∘ F WB ( h 1 = 31.5 BTU/lb h_1 = 31.5\text{ BTU/lb} h 1 = 31.5 BTU/lb , W 1 = 78.0 grains/lb W_1 = 78.0\text{ grains/lb} W 1 = 78.0 grains/lb ). Air leaves the coil at 55.0 ∘ F 55.0^\circ\text{F} 55. 0 ∘ F DB and 53.5 ∘ F 53.5^\circ\text{F} 53. 5 ∘ F WB ( h 2 = 22.3 BTU/lb h_2 = 22.3\text{ BTU/lb} h 2 = 22.3 BTU/lb , W 2 = 56.0 grains/lb W_2 = 56.0\text{ grains/lb} W 2 = 56.0 grains/lb ).
Calculate: (1) Sensible cooling capacity ( q s q_s q s ), (2) Latent cooling capacity ( q l q_l q l ), (3) Total cooling capacity ( q t q_t q t ), (4) Sensible Heat Ratio ( S H R SHR S H R ), and (5) Hourly condensate removal rate in gallons per hour.
Solution:
Sensible Cooling Capacity: q s = 1.08 × CFM × ( T db, in − T db, out ) q_s = 1.08 \times \text{CFM} \times (T_{\text{db, in}} - T_{\text{db, out}}) q s = 1.08 × CFM × ( T db, in − T db, out ) q s = 1.08 × 1 , 600 CFM × ( 80.0 − 55.0 ) ∘ F = 1.08 × 1 , 600 × 25.0 = 43 , 200 BTU/hr q_s = 1.08 \times 1,600\text{ CFM} \times (80.0 - 55.0)^\circ\text{F} = 1.08 \times 1,600 \times 25.0 = \mathbf{43,200\text{ BTU/hr}} q s = 1.08 × 1 , 600 CFM × ( 80.0 − 55.0 ) ∘ F = 1.08 × 1 , 600 × 25.0 = 43 , 200 BTU/hr
Latent Cooling Capacity: q l = 0.68 × CFM × ( W in − W out ) q_l = 0.68 \times \text{CFM} \times (W_{\text{in}} - W_{\text{out}}) q l = 0.68 × CFM × ( W in − W out ) q l = 0.68 × 1 , 600 CFM × ( 78.0 − 56.0 ) grains/lb = 0.68 × 1 , 600 × 22.0 = 23 , 936 BTU/hr q_l = 0.68 \times 1,600\text{ CFM} \times (78.0 - 56.0)\text{ grains/lb} = 0.68 \times 1,600 \times 22.0 = \mathbf{23,936\text{ BTU/hr}} q l = 0.68 × 1 , 600 CFM × ( 78.0 − 56.0 ) grains/lb = 0.68 × 1 , 600 × 22.0 = 23 , 936 BTU/hr
Total Cooling Capacity (Enthalpy Method): q t = 4.5 × CFM × ( h 1 − h 2 ) q_t = 4.5 \times \text{CFM} \times (h_1 - h_2) q t = 4.5 × CFM × ( h 1 − h 2 ) q t = 4.5 × 1 , 600 CFM × ( 31.5 − 22.3 ) BTU/lb = 4.5 × 1 , 600 × 9.2 = 66 , 240 BTU/hr ( 5.52 Tons ) q_t = 4.5 \times 1,600\text{ CFM} \times (31.5 - 22.3)\text{ BTU/lb} = 4.5 \times 1,600 \times 9.2 = \mathbf{66,240\text{ BTU/hr}} \quad (5.52\text{ Tons}) q t = 4.5 × 1 , 600 CFM × ( 31.5 − 22.3 ) BTU/lb = 4.5 × 1 , 600 × 9.2 = 66 , 240 BTU/hr ( 5.52 Tons )
(Sum of Sensible + Latent: 43 , 200 + 23 , 936 = 67 , 136 BTU/hr 43,200 + 23,936 = 67,136\text{ BTU/hr} 43 , 200 + 23 , 936 = 67 , 136 BTU/hr ; within 1.3 % 1.3\% 1.3% of enthalpy method due to standard density constants).
Sensible Heat Ratio ( S H R SHR S H R ): SHR = q s q s + q l = 43 , 200 43 , 200 + 23 , 936 = 43 , 200 67 , 136 = 0.643 ( 64.3 % Sensible , 35.7 % Latent ) \text{SHR} = \frac{q_s}{q_s + q_l} = \frac{43,200}{43,200 + 23,936} = \frac{43,200}{67,136} = \mathbf{0.643} \quad (64.3\%\text{ Sensible}, 35.7\%\text{ Latent}) SHR = q s + q l q s = 43 , 200 + 23 , 936 43 , 200 = 67 , 136 43 , 200 = 0.643 ( 64.3% Sensible , 35.7% Latent )
Condensate Removal Rate: Condensate Mass Rate = q l 1 , 061 BTU/lb = 23 , 936 BTU/hr 1 , 061 BTU/lb = 22.56 lbs/hr \text{Condensate Mass Rate} = \frac{q_l}{1,061\text{ BTU/lb}} = \frac{23,936\text{ BTU/hr}}{1,061\text{ BTU/lb}} = 22.56\text{ lbs/hr} Condensate Mass Rate = 1 , 061 BTU/lb q l = 1 , 061 BTU/lb 23 , 936 BTU/hr = 22.56 lbs/hr Condensate Volume = 22.56 lbs/hr 8.34 lbs/gal = 2.70 Gallons/Hour \text{Condensate Volume} = \frac{22.56\text{ lbs/hr}}{8.34\text{ lbs/gal}} = \mathbf{2.70\text{ Gallons/Hour}} Condensate Volume = 8.34 lbs/gal 22.56 lbs/hr = 2.70 Gallons/Hour