7.2 Fuel Gas Pipe Sizing: Longest Length & Branch Sizing Methods
North Carolina Plumbing Contractor Exam Class I & Class II
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Administration & General Code Regulations
1.1 NC Plumbing Licensing, Board Rules & Exam Structure 1.2 General Regulations, Piping Support, Trenching & Protection 1.3 Plumbing Mathematics, Grade Calculations & Isometric Plan Reading 1.4 Permits, Plan Review, Required Inspections & Code-Mandated Tests 1.5 Approved Materials, Standards, Joints & Connections
2 Chapter 2: Fixtures, Faucets, Fixture Fittings & Water Heaters
2.1 Minimum Fixture Requirements, Accessibility (ADA) & Rough-In Spacing 2.2 Fixture Installation, Setting Clearances & Flushometer Valves 2.3 Water Heater Sizing, Temperature & Pressure Relief (T&P) Valves & Safety Devices
3 Chapter 3: Water Supply and Distribution & Backflow Prevention
3.1 Water Service Sizing, Materials & Pressure Regulation 3.2 Water Supply Fixture Units (WSFU) & Pipe Sizing Methods 3.3 Cross-Connection Control, Backflow Prevention Devices & Hazards 3.4 Hot and Cold Water Distribution Design & Pressure Loss Calculations
4 Chapter 4: Sanitary Drainage, Indirect Waste, Sumps & Ejectors
4.1 Drainage System Principles, Flow Velocities & Minimum Slope Requirements 4.2 Drainage Fixture Unit (DFU) Sizing for Building Drains, Sewers & Stacks 4.3 Cleanout Sizing, Locations, Clearances & Installation Standards 4.4 Sewage Sumps, Macerating Systems & Indirect/Special Waste 4.5 Building Sewers, Sewer Connections & Private Sewage Disposal
5 Chapter 5: Vents and Venting Systems
5.1 Venting Principles, Termination & Minimum Sizing 5.2 Wet Venting, Common Venting & Stack Vent Systems 5.3 Circuit & Loop Venting, Combination Waste & Vent Systems 5.4 Island Fixture Venting & Air Admittance Valves (AAVs)
6 Chapter 6: Traps, Interceptors, Separators & Storm Drainage
6.1 Trap Design, Prohibited Traps & Trap Arm Developed Lengths 6.2 Grease Interceptors, Oil Separators & Sand Traps 6.3 Storm Drainage Sizing, Roof Drains & Secondary (Emergency) Overflow Systems
7 Chapter 7: Fuel Gas Piping & Appliance Venting (NC IFGC)
7.1 Fuel Gas Fundamentals, Materials, Jointing & Mandatory Pressure Testing 7.2 Fuel Gas Pipe Sizing: Longest Length & Branch Sizing Methods 7.3 Combustion Air Requirements: Indoor, Outdoor & Engineered Openings 7.4 Fuel Gas Appliance Venting: Category I–IV Systems, Chimneys & Clearances
8 Chapter 8: Safety, Excavation & Jobsite Practices (OSHA 1926)
8.1 OSHA Standards for Plumbing: PPE, Fall Protection & Hazard Communication 8.2 Trenching, Shoring, Soil Classifications & Confined Space Safety 8.3 Soldering, Brazing, Hot Work Permits & Jobsite Fire Prevention
9 Chapter 9: NC Contractor Business Law, Project Management & Liens (NASCLA / 21 NCAC 50)
9.1 NC Board Laws (NCGS 87-2), Administrative Rules (21 NCAC 50) & Disciplinary Actions 9.2 Estimating, Job Costing, Bidding & Contract Administration 9.3 North Carolina Mechanics' Lien Laws, Payment Bonds & Dispute Resolution 9.4 Financial Management, Tax Compliance, Workers' Compensation & Business Insurance 9.5 Business Formation, Entity Licensing & Startup Compliance in North Carolina 9.6 Employment Law, Payroll Compliance & Workforce Management 9.7 Project Management: Scheduling, Submittals, Documentation & Closeout 9.8 Surety Bonding, Risk Transfer & Claims Management 9.9 Environmental, Erosion Control & Jobsite Regulatory Compliance
10 Chapter 10: NC Residential Code Plumbing (Class II & Dwelling Practice)
10.1 NC Residential Code Scope, Administration, Materials & Water Supply for Dwellings 10.2 NC Residential Code DWV, Venting, Traps & Fuel Gas Provisions for Dwellings
7.2 Fuel Gas Pipe Sizing: Longest Length & Branch Sizing Methods
Key Takeaways Explain This Topic AI
Fuel gas distribution systems must be sized to deliver peak aggregate demand without exceeding an allowable pressure drop of 0.5 inch water column (0.5" w.c.) for standard low-pressure natural gas systems (< 0.5 psi / 7" w.c. inlet).
Appliance input ratings are converted to volumetric flow rate in Cubic Feet per Hour using the formula: C F H = Total BTU/hr Input / Heating Value of Gas CFH = \text{Total BTU/hr Input} / \text{Heating Value of Gas} CF H = Total BTU/hr Input / Heating Value of Gas (1,000 BTU/cu ft for Natural Gas; 2,500 BTU/cu ft for LP Gas).
Under the Longest Length Method (IFGC 402.4.1), the total equivalent developed length from the gas meter to the most hydraulically remote appliance determines the SINGLE length column used from the sizing table for every pipe segment in the system.
Intermediate hybrid 2-psi gas distribution systems utilize elevated pressure to significantly reduce pipe diameters and eliminate cumulative pressure loss over long runs, utilizing line pressure regulators at point-of-use manifolds to step down pressure to 7"–11" w.c.
Last updated: September 2026
7.2 Fuel Gas Pipe Sizing: Longest Length & Branch Sizing Methods
Quick Answer: Under the North Carolina Fuel Gas Code (IFGC Chapter 4) , fuel gas distribution piping is sized using either the Longest Length Method (IFGC 402.4.1) or the Branch Length Method . Appliance input ratings are converted into Cubic Feet per Hour ( C F H = BTU/hr / 1 , 000 BTU/cu ft CFH = \text{BTU/hr} / 1,000\text{ BTU/cu ft} CF H = BTU/hr /1 , 000 BTU/cu ft for Natural Gas) . In the Longest Length Method, the plumber measures the total equivalent developed length from the utility meter/regulator to the single most hydraulically remote appliance . That specific length column in the IFGC sizing table (e.g., Schedule 40 Metallic Pipe, Natural Gas, < 0.5 psi < 0.5\text{ psi} < 0.5 psi inlet, 0.5 in. w.c. 0.5\text{ in. w.c.} 0.5 in. w.c. pressure drop, 0.60 SG 0.60\text{ SG} 0.60 SG ) is used across the entire piping network to size every main trunk, branch header, and appliance drop based on the cumulative load flowing through that segment.
Principles of Fuel Gas Hydraulics & Pressure Drop
Gas flows through a pipe because of a pressure differential ( Δ P \Delta P Δ P ) between the supply source (utility meter or second-stage propane regulator) and the appliance burner. If piping is undersized, the friction loss over length creates excessive pressure drop, leading to burner starvation, delayed ignition, sooting, carbon monoxide generation, and nuisance appliance lockouts when multiple fixtures fire simultaneously. [Meter Delivery: 7.0" w.c.] ────► [Piping Friction Loss: Max 0.5" w.c.] ────► [Appliance Burner: Min 6.5" w.c.]
Core Design Parameters for Standard Low-Pressure Natural Gas Systems
Inlet Supply Pressure: Less than 0.5 psig 0.5\text{ psig} 0.5 psig (typically 7.0 inches w.c. 7.0\text{ inches w.c.} 7.0 inches w.c. / 0.25 psi 0.25\text{ psi} 0.25 psi ). Standard propane systems deliver 11.0 inches w.c. 11.0\text{ inches w.c.} 11.0 inches w.c. ( 0.397 psi 0.397\text{ psi} 0.397 psi ).
Allowable Design Pressure Drop: Maximum 0.5 inches w.c. 0.5\text{ inches w.c.} 0.5 inches w.c. ( 125 Pa 125\text{ Pa} 125 Pa ) or 0.3 inches w.c. 0.3\text{ inches w.c.} 0.3 inches w.c. depending on municipal utility supply pressure.
Specific Gravity: 0.60 0.60 0.60 for Natural Gas; 1.50 1.50 1.50 for LP / Propane.
Appliance Manifold Requirement: Standard natural gas appliances require a minimum burner manifold pressure of 3.5 to 4.0 inches w.c. 3.5\text{ to }4.0\text{ inches w.c.} 3.5 to 4.0 inches w.c. ; with a 7.0 in. w.c. 7.0\text{ in. w.c.} 7.0 in. w.c. inlet and a 0.5 in. w.c. 0.5\text{ in. w.c.} 0.5 in. w.c. line drop, the appliance receives 6.5 in. w.c. 6.5\text{ in. w.c.} 6.5 in. w.c. , comfortably satisfying the internal control valve's minimum threshold.
Converting Appliance Ratings to Cubic Feet per Hour (CFH)
Gas pipe sizing tables are calibrated in volumetric capacity ( Cubic Feet per Hour / CFH ). To size a system, all connected appliances must have their input ratings converted from British Thermal Units per Hour (BTU/hr) to CFH: C F H = Appliance Input Rating (BTU/hr) Heating Value of Gas (BTU/cu ft) \mathbf{CFH} = \frac{\text{Appliance Input Rating (BTU/hr)}}{\text{Heating Value of Gas (BTU/cu ft)}} CFH = Heating Value of Gas (BTU/cu ft) Appliance Input Rating (BTU/hr) Natural Gas Demand (CFH) = Appliance Input Rating (BTU/hr) 1 , 000 BTU/cu ft \text{Natural Gas Demand (CFH)} = \frac{\text{Appliance Input Rating (BTU/hr)}}{\mathbf{1,000\text{ BTU/cu ft}}} Natural Gas Demand (CFH) = 1 , 000 BTU/cu ft Appliance Input Rating (BTU/hr) Propane / LP Demand (CFH) = Appliance Input Rating (BTU/hr) 2 , 500 BTU/cu ft \text{Propane / LP Demand (CFH)} = \frac{\text{Appliance Input Rating (BTU/hr)}}{\mathbf{2,500\text{ BTU/cu ft}}} Propane / LP Demand (CFH) = 2 , 500 BTU/cu ft Appliance Input Rating (BTU/hr)
Typical Residential Appliance Gas Loads
Residential Appliance Category Nominal Input Rating (BTU/hr) Natural Gas Demand (CFH @ 1,000 BTU/cu ft) LP / Propane Demand (CFH @ 2,500 BTU/cu ft)
High-Efficiency Condensing Furnace 80 , 000 BTU/hr 80,000\text{ BTU/hr} 80 , 000 BTU/hr 80 CFH 80\text{ CFH} 80 CFH 32 CFH 32\text{ CFH} 32 CFH
Whole-House Tankless Water Heater 199 , 000 BTU/hr 199,000\text{ BTU/hr} 199 , 000 BTU/hr 199 CFH 199\text{ CFH} 199 CFH 79.6 CFH 79.6\text{ CFH} 79.6 CFH
Standard 50-Gal Storage Water Heater 40 , 000 BTU/hr 40,000\text{ BTU/hr} 40 , 000 BTU/hr 40 CFH 40\text{ CFH} 40 CFH 16 CFH 16\text{ CFH} 16 CFH
Commercial-Style Gas Cooktop / Range 65 , 000 BTU/hr 65,000\text{ BTU/hr} 65 , 000 BTU/hr 65 CFH 65\text{ CFH} 65 CFH 26 CFH 26\text{ CFH} 26 CFH
Domestic Gas Clothes Dryer 35 , 000 BTU/hr 35,000\text{ BTU/hr} 35 , 000 BTU/hr 35 CFH 35\text{ CFH} 35 CFH 14 CFH 14\text{ CFH} 14 CFH
Direct-Vent Gas Fireplace / Log Set 30 , 000 BTU/hr 30,000\text{ BTU/hr} 30 , 000 BTU/hr 30 CFH 30\text{ CFH} 30 CFH 12 CFH 12\text{ CFH} 12 CFH
Outdoor Gas Grill (Dedicated Connection) 50 , 000 BTU/hr 50,000\text{ BTU/hr} 50 , 000 BTU/hr 50 CFH 50\text{ CFH} 50 CFH 20 CFH 20\text{ CFH} 20 CFH
IFGC Sizing Capacity Table: Schedule 40 Metallic Pipe
The following capacity table is extracted from IFGC Table 402.4(2) / NC Fuel Gas Code for Natural Gas at Inlet Pressure < 0.5 psi < 0.5\text{ psi} < 0.5 psi , Pressure Drop 0.5 in. w.c. 0.5\text{ in. w.c.} 0.5 in. w.c. , and Specific Gravity 0.60 0.60 0.60 :
Table: Maximum Pipe Capacity in CFH for Schedule 40 Black Steel Pipe
Developed Length (Feet) 1/2" (0.622" ID) 3/4" (0.824" ID) 1" (1.049" ID) 1-1/4" (1.380" ID) 1-1/2" (1.610" ID) 2" (2.067" ID)
10 ft 172 CFH 172\text{ CFH} 172 CFH 360 CFH 360\text{ CFH} 360 CFH 678 CFH 678\text{ CFH} 678 CFH 1 , 390 CFH 1,390\text{ CFH} 1 , 390 CFH 2 , 090 CFH 2,090\text{ CFH} 2 , 090 CFH 4 , 020 CFH 4,020\text{ CFH} 4 , 020 CFH
20 ft 118 CFH 118\text{ CFH} 118 CFH 247 CFH 247\text{ CFH} 247 CFH 466 CFH 466\text{ CFH} 466 CFH 957 CFH 957\text{ CFH} 957 CFH 1 , 430 CFH 1,430\text{ CFH} 1 , 430 CFH 2 , 760 CFH 2,760\text{ CFH} 2 , 760 CFH
30 ft 95 CFH 95\text{ CFH} 95 CFH 199 CFH 199\text{ CFH} 199 CFH 374 CFH 374\text{ CFH} 374 CFH 768 CFH 768\text{ CFH} 768 CFH 1 , 150 CFH 1,150\text{ CFH} 1 , 150 CFH 2 , 220 CFH 2,220\text{ CFH} 2 , 220 CFH
40 ft 81 CFH 81\text{ CFH} 81 CFH 170 CFH 170\text{ CFH} 170 CFH 320 CFH 320\text{ CFH} 320 CFH 657 CFH 657\text{ CFH} 657 CFH 985 CFH 985\text{ CFH} 985 CFH 1 , 900 CFH 1,900\text{ CFH} 1 , 900 CFH
50 ft 72 CFH 72\text{ CFH} 72 CFH 151 CFH 151\text{ CFH} 151 CFH 284 CFH 284\text{ CFH} 284 CFH 583 CFH 583\text{ CFH} 583 CFH 873 CFH 873\text{ CFH} 873 CFH 1 , 680 CFH 1,680\text{ CFH} 1 , 680 CFH
60 ft 65 CFH 65\text{ CFH} 65 CFH 137 CFH 137\text{ CFH} 137 CFH 257 CFH 257\text{ CFH} 257 CFH 528 CFH 528\text{ CFH} 528 CFH 791 CFH 791\text{ CFH} 791 CFH 1 , 520 CFH 1,520\text{ CFH} 1 , 520 CFH
70 ft 60 CFH 60\text{ CFH} 60 CFH 126 CFH 126\text{ CFH} 126 CFH 237 CFH 237\text{ CFH} 237 CFH 486 CFH 486\text{ CFH} 486 CFH 728 CFH 728\text{ CFH} 728 CFH 1 , 400 CFH 1,400\text{ CFH} 1 , 400 CFH
80 ft 56 CFH 56\text{ CFH} 56 CFH 117 CFH 117\text{ CFH} 117 CFH 220 CFH 220\text{ CFH} 220 CFH 452 CFH 452\text{ CFH} 452 CFH 677 CFH 677\text{ CFH} 677 CFH 1 , 300 CFH 1,300\text{ CFH} 1 , 300 CFH
90 ft 52 CFH 52\text{ CFH} 52 CFH 110 CFH 110\text{ CFH} 110 CFH 207 CFH 207\text{ CFH} 207 CFH 424 CFH 424\text{ CFH} 424 CFH 635 CFH 635\text{ CFH} 635 CFH 1 , 220 CFH 1,220\text{ CFH} 1 , 220 CFH
100 ft 50 CFH 50\text{ CFH} 50 CFH 104 CFH 104\text{ CFH} 104 CFH 195 CFH 195\text{ CFH} 195 CFH 400 CFH 400\text{ CFH} 400 CFH 600 CFH 600\text{ CFH} 600 CFH 1 , 160 CFH 1,160\text{ CFH} 1 , 160 CFH
125 ft 44 CFH 44\text{ CFH} 44 CFH 92 CFH 92\text{ CFH} 92 CFH 173 CFH 173\text{ CFH} 173 CFH 355 CFH 355\text{ CFH} 355 CFH 532 CFH 532\text{ CFH} 532 CFH 1 , 020 CFH 1,020\text{ CFH} 1 , 020 CFH
150 ft 40 CFH 40\text{ CFH} 40 CFH 83 CFH 83\text{ CFH} 83 CFH 157 CFH 157\text{ CFH} 157 CFH 322 CFH 322\text{ CFH} 322 CFH 482 CFH 482\text{ CFH} 482 CFH 928 CFH 928\text{ CFH} 928 CFH
Sizing Methodologies: Longest Length vs. Branch Length
Loading diagram...
The Longest Length Method (IFGC 402.4.1) — Step-by-Step Rules
Determine Gas Demand of Each Appliance: Convert all BTU/hr ratings to CFH.
Measure Developed Lengths: Measure the actual physical length from the meter/regulator outlet along the pipe centerline to each individual appliance inlet.
Identify the Longest Run: Locate the appliance with the greatest total developed length from the meter. If the exact measured distance falls between standard table rows, round up to the next larger length column (e.g., a 64-foot longest run is evaluated using the 70-foot column ).
Size Every Pipe Segment Using That Single Column:
Main Supply Trunk: Must carry the sum of all downstream appliances . Find the capacity in the selected length column equal to or greater than this total demand.
Intermediate Headers / Branch Runs: Size based on the cumulative load of only the appliances served downstream of that junction point, still using the same longest length column .
Individual Appliance Drops: Size based on the appliance's individual CFH, still using the same longest length column .
Exam Trap: On the North Carolina exam, candidates often make the mistake of switching length columns for each branch (e.g., using the 20-foot column for an appliance 20 feet away). In the Longest Length Method , you MUST NOT SWITCH COLUMNS —every section of pipe in the entire house is sized using the column corresponding to the single furthest appliance!
Worked Residential Gas Sizing Calculation [RESIDENTIAL GAS PIPING SCHEMATIC]
- Meter [A]
- │
- ├── (10 ft) ── Junction [B]
- │ │
- │ ├── (20 ft) ──► Tankless Water Heater [WH] (199,000 BTU/hr)
- │ │ (Total length from meter = 10 + 20 = 30 ft)
- │ │
- │ (15 ft) ── Junction [C]
- │ │
- │ ├── (25 ft) ──► Central Furnace [F] (80,000 BTU/hr)
- │ │ (Total length from meter = 10 + 15 + 25 = 50 ft)
- │ │
- │ (15 ft) ── Junction [D]
- │ │
- │ ├── (20 ft) ──► Gas Range [R] (65,000 BTU/hr)
- │ │ (Total length from meter = 10 + 15 + 15 + 20 = 60 ft)
- │ │
- │ └── (30 ft) ──► Gas Dryer [D] (35,000 BTU/hr)
- │ (Total length from meter = 10 + 15 + 15 + 30 = 70 ft)
- Step 1: Calculate Individual Appliance CFH Demands
Tankless Water Heater: 199 , 000 BTU/hr / 1 , 000 = 199 CFH 199,000\text{ BTU/hr} / 1,000 = \mathbf{199\text{ CFH}} 199 , 000 BTU/hr /1 , 000 = 199 CFH
Central Gas Furnace: 80 , 000 BTU/hr / 1 , 000 = 80 CFH 80,000\text{ BTU/hr} / 1,000 = \mathbf{80\text{ CFH}} 80 , 000 BTU/hr /1 , 000 = 80 CFH
Gas Cooktop / Range: 65 , 000 BTU/hr / 1 , 000 = 65 CFH 65,000\text{ BTU/hr} / 1,000 = \mathbf{65\text{ CFH}} 65 , 000 BTU/hr /1 , 000 = 65 CFH
Gas Clothes Dryer: 35 , 000 BTU/hr / 1 , 000 = 35 CFH 35,000\text{ BTU/hr} / 1,000 = \mathbf{35\text{ CFH}} 35 , 000 BTU/hr /1 , 000 = 35 CFH
Total System Peak Demand: 199 + 80 + 65 + 35 = 379 CFH 199 + 80 + 65 + 35 = \mathbf{379\text{ CFH}} 199 + 80 + 65 + 35 = 379 CFH
Step 2: Determine Developed Lengths & Identify the Longest Run
Distance to Water Heater: 10 ft + 20 ft = 30 ft 10\text{ ft} + 20\text{ ft} = 30\text{ ft} 10 ft + 20 ft = 30 ft
Distance to Furnace: 10 ft + 15 ft + 25 ft = 50 ft 10\text{ ft} + 15\text{ ft} + 25\text{ ft} = 50\text{ ft} 10 ft + 15 ft + 25 ft = 50 ft
Distance to Range: 10 ft + 15 ft + 15 ft + 20 ft = 60 ft 10\text{ ft} + 15\text{ ft} + 15\text{ ft} + 20\text{ ft} = 60\text{ ft} 10 ft + 15 ft + 15 ft + 20 ft = 60 ft
Distance to Clothes Dryer: 10 ft + 15 ft + 15 ft + 30 ft = 70 ft 10\text{ ft} + 15\text{ ft} + 15\text{ ft} + 30\text{ ft} = \mathbf{70\text{ ft}} 10 ft + 15 ft + 15 ft + 30 ft = 70 ft
Longest Run = 70 Feet. We will use the 70-Foot Column from the Schedule 40 Black Steel Table for sizing every single pipe segment in the building.
- Step 3: Size Each Segment Using the 70-Foot Column Values
- (Reference 70-Foot Column Capacities: 1/2" = 60 CFH; 3/4" = 126 CFH; 1" = 237 CFH; 1-1/4" = 486 CFH)
Main Supply Segment A–B (Carries WH + F + R + D):
Total Demand = 379 CFH = 379\text{ CFH} = 379 CFH .
At 70 ft: 1 " = 237 CFH 1" = 237\text{ CFH} 1" = 237 CFH (Too small); 1 − 1 / 4 " = 486 CFH 1-1/4" = 486\text{ CFH} 1 − 1/4" = 486 CFH (Sufficient).
Select: 1-1/4" Pipe .
Branch B–WH (Carries Tankless Water Heater):
Demand = 199 CFH = 199\text{ CFH} = 199 CFH .
At 70 ft: 3 / 4 " = 126 CFH 3/4" = 126\text{ CFH} 3/4" = 126 CFH (Too small); 1 " = 237 CFH 1" = 237\text{ CFH} 1" = 237 CFH (Sufficient).
Select: 1" Pipe .
Trunk Segment B–C (Carries F + R + D):
Total Demand = 80 + 65 + 35 = 180 CFH = 80 + 65 + 35 = 180\text{ CFH} = 80 + 65 + 35 = 180 CFH .
At 70 ft: 3 / 4 " = 126 CFH 3/4" = 126\text{ CFH} 3/4" = 126 CFH (Too small); 1 " = 237 CFH 1" = 237\text{ CFH} 1" = 237 CFH (Sufficient).
Select: 1" Pipe .
Branch C–F (Carries Furnace):
Demand = 80 CFH = 80\text{ CFH} = 80 CFH .
At 70 ft: 1 / 2 " = 60 CFH 1/2" = 60\text{ CFH} 1/2" = 60 CFH (Too small); 3 / 4 " = 126 CFH 3/4" = 126\text{ CFH} 3/4" = 126 CFH (Sufficient).
Select: 3/4" Pipe .
Trunk Segment C–D (Carries R + D):
Total Demand = 65 + 35 = 100 CFH = 65 + 35 = 100\text{ CFH} = 65 + 35 = 100 CFH .
At 70 ft: 1 / 2 " = 60 CFH 1/2" = 60\text{ CFH} 1/2" = 60 CFH (Too small); 3 / 4 " = 126 CFH 3/4" = 126\text{ CFH} 3/4" = 126 CFH (Sufficient).
Select: 3/4" Pipe .
Branch D–R (Carries Range):
Demand = 65 CFH = 65\text{ CFH} = 65 CFH .
At 70 ft: 1 / 2 " = 60 CFH 1/2" = 60\text{ CFH} 1/2" = 60 CFH (Too small); 3 / 4 " = 126 CFH 3/4" = 126\text{ CFH} 3/4" = 126 CFH (Sufficient).
Select: 3/4" Pipe .
Branch D–D (Carries Clothes Dryer):
Demand = 35 CFH = 35\text{ CFH} = 35 CFH .
At 70 ft: 1 / 2 " = 60 CFH 1/2" = 60\text{ CFH} 1/2" = 60 CFH (Sufficient: 60 ≥ 35 60 \ge 35 60 ≥ 35 ).
Select: 1/2" Pipe .
High-Pressure Hybrid 2-PSI CSST Distribution Systems
In modern residential and commercial construction, plumbers frequently utilize 2 psig (13.8 kPa) intermediate gas pressure systems rather than traditional 7" w.c. low-pressure systems. [2 psi Meter] ──► [3/8" or 1/2" CSST Trunk Line] ──► [Manifold & Line Regulator] ──► [Low Pressure (7" w.c.) to Appliances]
Advantages & Code Rules for 2-PSI Systems (IFGC 410)
Reduced Pipe Diameters: Because high pressure compresses the gas and allows a much larger allowable pressure drop (e.g., 1.0 psi 1.0\text{ psi} 1.0 psi drop on a 2.0 psi 2.0\text{ psi} 2.0 psi system vs. 0.5 in. w.c. 0.5\text{ in. w.c.} 0.5 in. w.c. on low pressure), a small 1/2" or 3/4" CSST line can carry 500 , 000 + BTU/hr 500,000+\text{ BTU/hr} 500 , 000 + BTU/hr over 150 feet.
Point-of-Use Line Pressure Regulators (MP Regulators): Maxitrol or similar 2-psi to 7"–11" w.c. line regulators must be installed ahead of the distribution manifold.
Regulator Venting Standards (IFGC 410.3):
Every line regulator must be equipped with an approved factory vent limiter device (which allows indoor installation without an outdoor vent line, provided it vents < 2.5 cu ft/hr < 2.5\text{ cu ft/hr} < 2.5 cu ft/hr upon diaphragm rupture) OR piped with an independent dedicated vent line extending to the outdoor atmosphere.
Regulators with vent limiters must be installed strictly in the upright vertical position as specified by the manufacturer.