2.3 AC Fundamentals, Reactance & Magnetism

NCCER Commercial Electrician COMELEC26_01

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Electrical Safety, OSHA & NFPA 70E

1.1 OSHA Regulations & Subpart S Compliance 1.2 NFPA 70E Standards & Arc-Flash Protection 1.3 Lockout/Tagout (LOTO) & Absence-of-Voltage Verification 1.4 Jobsite Hazard Recognition & Fall/Trench Safety

2 Chapter 2: Electrical Theory & AC/DC Fundamentals

2.1 DC Fundamentals, Ohm's Law & Power 2.2 Series, Parallel & Combination Circuits 2.3 AC Fundamentals, Reactance & Magnetism 2.4 Impedance, Power Triangles & Power Factor

3 Chapter 3: NEC Layout, General Requirements & Services

3.1 NEC Structure, Navigation & Article 100 Definitions 3.2 NEC Article 110: General Requirements for Electrical Installations 3.3 NEC Article 230: Services & Service Equipment

4 Chapter 4: Branch Circuits, Feeders & Overcurrent Protection

4.1 Branch Circuits & Feeders 4.2 Commercial Load Calculations 4.3 Overcurrent Protection & Coordination

5 Chapter 5: Conductors, Insulation & Sizing Calculations

5.1 Conductor Construction, Materials & Insulation 5.2 Ampacity Determination & Table 310.16 5.3 Ampacity Derating & Adjustment Calculations 5.4 Conductor Installation, Pulling Tension & Splices

6 Chapter 6: Raceways, Boxes & Conduit Bending

6.1 Raceway Systems & Support Rules 6.2 Conduit Bending Principles & Mathematics 6.3 Raceway Fill Calculations 6.4 Box Sizing & Cable Tray Systems

7 Chapter 7: Commercial Wiring Methods, Devices & Special Occupancies

7.1 Commercial Wiring Devices & Receptacles 7.2 Switching Circuits & Commercial Controls 7.3 Commercial Lighting & Emergency Power Systems 7.4 Hazardous (Classified) Locations

8 Chapter 8: Motors, Motor Circuits & Overload Protection

8.1 Motor Principles & Nameplate Interpretation 8.2 Motor Feeder & Branch-Circuit Conductor Sizing 8.3 Motor Overload & Branch-Circuit Short-Circuit Protection

9 Chapter 9: Motor Controls, Ladder Logic & Industrial Drives

9.1 Magnetic Contactors, Starters & Relays 9.2 Control Circuits & Ladder Logic Schematics 9.3 Variable Frequency Drives (VFDs) & PLC Applications

10 Chapter 10: Transformers & Separately Derived Systems

10.1 Transformer Theory, Ratios & Single-Phase Connections 10.2 Three-Phase Transformer Configurations & Calculations 10.3 Transformer Sizing, Protection & Grounding

11 Chapter 11: Grounding & Bonding Systems (NEC Article 250)

11.1 Fundamental Concepts: Grounding vs. Bonding 11.2 Grounding Electrode System & GEC Sizing 11.3 Equipment Grounding Conductors (EGC) 11.4 Main, System & Supply-Side Bonding Jumpers

12 Chapter 12: Electrical Testing, Troubleshooting & Print Reading

12.1 Electrical Test Instruments & CAT Ratings 12.2 Systematic Circuit Troubleshooting & Fault Analysis 12.3 Electrical Drawings, Specifications & One-Line Diagrams 12.4 Fire Alarm Systems & Specialized Low-Voltage Wiring

2.3 AC Fundamentals, Reactance & Magnetism

Key Takeaways Explain This Topic AI

Faraday's Law of Induction states that induced electromotive force is directly proportional to the rate of change of magnetic flux ( e = − N Δ Φ Δ t e = -N \frac{\Delta\Phi}{\Delta t} e = − N Δ t ΔΦ ​ ), with the induced polarity opposing the change per Lenz's Law.

Root-Mean-Square (RMS) voltage represents the effective heating value of an alternating sine wave, equivalent to DC: V r m s = V p 2 ≈ 0.707 × V p V_{rms} = \frac{V_p}{\sqrt{2}} \approx 0.707 \times V_p V r m s ​ = 2 ​ V p ​ ​ ≈ 0.707 × V p ​ , while peak voltage is V p ≈ 1.414 × V r m s V_p \approx 1.414 \times V_{rms} V p ​ ≈ 1.414 × V r m s ​ .

Inductive reactance ( X L = 2 π f L X_L = 2\pi f L X L ​ = 2 π f L ) opposes current flow due to counter-EMF and increases linearly with frequency; in a pure inductor, voltage leads current by 90° (ELI).

Capacitive reactance ( X C = 1 2 π f C X_C = \frac{1}{2\pi f C} X C ​ = 2 π f C 1 ​ ) opposes AC voltage changes and decreases inversely with frequency; in a pure capacitor, current leads voltage by 90° (ICE).

Direct current operates at zero frequency ( f = 0 Hz f = 0\text{ Hz} f = 0 Hz ), resulting in zero inductive reactance ( X L = 0 Ω X_L = 0\ \Omega X L ​ = 0 Ω ) and infinite capacitive reactance ( X C = ∞ Ω X_C = \infty\ \Omega X C ​ = ∞ Ω , completely blocking DC).

Last updated: October 2026

2.3 AC Fundamentals, Reactance & Magnetism

Alternating current (AC) is the global standard for commercial and industrial electric power distribution. Unlike direct current, which maintains unidirectional charge drift, alternating current periodically reverses direction and continuously modulates its instantaneous amplitude. Understanding how alternating magnetic and electric fields interact with inductive and capacitive circuit components is crucial for commercial electrical construction, motor installations, and power quality analysis.

Principles of Electromagnetism & Induction

Every electrical current produces an associated magnetic field. When current flows through a straight conductor, concentric lines of magnetic flux ( Φ \Phi Φ ) circulate around the wire per the right-hand rule (pointing the right thumb in the direction of conventional current curls the fingers in the direction of the magnetic field).

Core Magnetic Quantities

Magnetic Flux ( Φ \Phi Φ ): The total quantity of magnetic field lines, measured in Webers (Wb) ( 1 Wb = 10 8 magnetic lines or Maxwells 1\text{ Wb} = 10^8\text{ magnetic lines or Maxwells} 1 Wb = 1 0 8 magnetic lines or Maxwells ). In imperial trade contexts, lines of flux are often termed Maxwells.

Magnetic Flux Density ( B B B ): The concentration of flux lines per unit area perpendicular to the field, measured in Teslas (T) ( 1 Tesla = 1 Wb/m 2 = 10 , 000 Gauss 1\text{ Tesla} = 1\text{ Wb/m}^2 = 10,000\text{ Gauss} 1 Tesla = 1 Wb/m 2 = 10 , 000 Gauss ): B = Φ A B = \frac{\Phi}{A} B = A Φ ​

Magnetomotive Force (MMF or F \mathcal{F} F ): The magnetic potential created by a coil to establish flux, measured in ampere-turns (A-t) : MMF = N × I \text{MMF} = N \times I MMF = N × I Where N N N is the number of coil turns and I I I is current in Amperes.

Permeability ( μ \mu μ ): The ease with which a magnetic material accommodates magnetic flux. Ferromagnetic materials (iron, electrical steel) have relative permeabilities hundreds to thousands of times higher than air, concentrating flux within transformer and motor stator cores.

Reluctance ( R \mathcal{R} R ): The opposition a magnetic circuit offers to magnetic flux, analogous to electrical resistance (Ohm's Law for magnetic circuits: Φ = MMF R \Phi = \frac{\text{MMF}}{\mathcal{R}} Φ = R MMF ​ ).

Faraday's Law & Lenz's Law

In 1831, Michael Faraday established Faraday's Law of Electromagnetic Induction : whenever the magnetic flux linking an electrical conductor changes over time, an electromotive force (voltage) is induced across the conductor terminals:

e = − N Δ Φ Δ t e = -N \frac{\Delta\Phi}{\Delta t} e = − N Δ t ΔΦ ​

Where:

e = instantaneous induced voltage (Volts) e = \text{instantaneous induced voltage (Volts)} e = instantaneous induced voltage (Volts)

N = number of turns in the conductor coil N = \text{number of turns in the conductor coil} N = number of turns in the conductor coil

Δ Φ Δ t = time rate of change of magnetic flux (Webers per second) \frac{\Delta\Phi}{\Delta t} = \text{time rate of change of magnetic flux (Webers per second)} Δ t ΔΦ ​ = time rate of change of magnetic flux (Webers per second)

The negative sign represents Lenz's Law : the polarity of the induced EMF always opposes the original change in magnetic flux that produced it. In motors and transformers, this induced potential is termed Counter-Electromotive Force (CEMF) or back-EMF, which acts as a self-regulating electrical brake restricting current flow.

Generation and Metrics of AC Sinusoidal Waveforms

When a single rectangular conductive loop rotates at a constant angular velocity ( ω = 2 π f \omega = 2\pi f ω = 2 π f ) within a uniform stationary magnetic field, the instantaneous voltage induced along its conductors is proportional to the sine of the rotation angle ( θ = ω t \theta = \omega t θ = ω t ):

v ( t ) = V p sin ⁡ ( 2 π f t ) v(t) = V_p \sin(2\pi f t) v ( t ) = V p ​ sin ( 2 π f t )

At 0 ∘ 0^\circ 0 ∘ , the conductor moves parallel to magnetic flux lines; rate of flux cutting is zero, generating 0 Volts 0\text{ Volts} 0 Volts .

At 90 ∘ 90^\circ 9 0 ∘ , the conductor cuts perpendicularly through maximum flux density, generating positive peak voltage ( + V p +V_p + V p ​ ).

At 180 ∘ 180^\circ 18 0 ∘ , motion is again parallel to flux, returning to 0 Volts 0\text{ Volts} 0 Volts .

At 270 ∘ 270^\circ 27 0 ∘ , the conductor cuts flux in the opposite direction, generating negative peak voltage ( − V p -V_p − V p ​ ).

  • At 360 ∘ 360^\circ 36 0 ∘ , the cycle completes. Voltage
  • +Vp | ***
  • | * *
  • 0 +----*---------*---------*---- Time (t)
  • | * *
  • Vp | ***
  • 0° 90° 180° 270° 360°
  • |<------- 1 Cycle (T) -------->|
  • Sinusoidal Parameters

Cycle: One complete positive alternation and one complete negative alternation ( 360 ∘ 360^\circ 36 0 ∘ or 2 π 2\pi 2 π radians).

Frequency ( f f f ): The number of complete cycles occurring per second, measured in Hertz (Hz) . North American commercial power operates at 60 Hz 60\text{ Hz} 60 Hz . In an AC alternator, frequency depends on rotational speed ( N N N in RPM) and number of field poles ( P P P ): f = P × N 120 f = \frac{P \times N}{120} f = 120 P × N ​

Period ( T T T ): The duration in seconds required to complete one full cycle: T = 1 f T = \frac{1}{f} T = f 1 ​ At 60 Hz 60\text{ Hz} 60 Hz : T = 1 60 ≈ 0.01667 seconds = 16.67 milliseconds T = \frac{1}{60} \approx 0.01667\text{ seconds} = 16.67\text{ milliseconds} T = 60 1 ​ ≈ 0.01667 seconds = 16.67 milliseconds .

Peak Voltage ( V p V_p V p ​ or V p e a k V_{peak} V p e ak ​ ): Maximum instantaneous voltage measured from the zero axis to the crest.

Peak-to-Peak Voltage ( V p − p V_{p-p} V p − p ​ ): Total voltage difference between positive and negative crests: V p − p = 2 × V p V_{p-p} = 2 \times V_p V p − p ​ = 2 × V p ​

Root-Mean-Square (RMS) Voltage ( V r m s V_{rms} V r m s ​ ): The effective value of an AC wave. RMS represents the equivalent DC potential that delivers exactly the same heating power ( I 2 R I^2R I 2 R ) to a pure resistance: V r m s = V p 2 ≈ 0.7071 × V p V p = 2 × V r m s ≈ 1.4142 × V r m s V_{rms} = \frac{V_p}{\sqrt{2}} \approx 0.7071 \times V_p \qquad V_p = \sqrt{2} \times V_{rms} \approx 1.4142 \times V_{rms} V r m s ​ = 2 ​ V p ​ ​ ≈ 0.7071 × V p ​ V p ​ = 2 ​ × V r m s ​ ≈ 1.4142 × V r m s ​ AC meters normally display an RMS or RMS-calibrated value, but an average-responding meter is accurate only for the waveform for which it is calibrated. A true-RMS meter is required for reliable measurements of distorted waveforms. A nominal 120 V 120\text{V} 120 V sinusoidal AC receptacle has a peak voltage of 120 × 1.4142 ≈ 169.7 V 120 \times 1.4142 \approx 169.7\text{ V} 120 × 1.4142 ≈ 169.7 V and a peak-to-peak voltage of 339.4 V 339.4\text{ V} 339.4 V .

Average Voltage ( V a v g V_{avg} V a vg ​ ): The arithmetic mean of all instantaneous values over one half-cycle alternation: V a v g = 2 π × V p ≈ 0.637 × V p = 0.900 × V r m s V_{avg} = \frac{2}{\pi} \times V_p \approx 0.637 \times V_p = 0.900 \times V_{rms} V a vg ​ = π 2 ​ × V p ​ ≈ 0.637 × V p ​ = 0.900 × V r m s ​

Parameter Formula from Peak ( V p V_p V p ​ ) Formula from RMS ( V r m s V_{rms} V r m s ​ ) Nominal 120V System Nominal 277V System

Peak ( V p V_p V p ​ ) V p V_p V p ​ 1.4142 × V r m s 1.4142 \times V_{rms} 1.4142 × V r m s ​ 169.7 V 169.7\text{ V} 169.7 V 391.7 V 391.7\text{ V} 391.7 V

Peak-to-Peak ( V p − p V_{p-p} V p − p ​ ) 2 × V p 2 \times V_p 2 × V p ​ 2.8284 × V r m s 2.8284 \times V_{rms} 2.8284 × V r m s ​ 339.4 V 339.4\text{ V} 339.4 V 783.5 V 783.5\text{ V} 783.5 V

RMS ( V r m s V_{rms} V r m s ​ ) 0.7071 × V p 0.7071 \times V_p 0.7071 × V p ​ V r m s V_{rms} V r m s ​ 120.0 V 120.0\text{ V} 120.0 V 277.0 V 277.0\text{ V} 277.0 V

Average ( V a v g V_{avg} V a vg ​ ) 0.6370 × V p 0.6370 \times V_p 0.6370 × V p ​ 0.9003 × V r m s 0.9003 \times V_{rms} 0.9003 × V r m s ​ 108.0 V 108.0\text{ V} 108.0 V 249.4 V 249.4\text{ V} 249.4 V

Purely Resistive AC Circuits

In an AC circuit containing only pure non-inductive resistance (e.g., baseboard electric strip heaters, incandescent filament lamps):

Voltage and current are completely in phase (phase angle θ = 0 ∘ \theta = 0^\circ θ = 0 ∘ ).

Both waveforms pass through zero and peak at the exact same instant.

Ohm's Law and Joule's Law apply directly using RMS values: I r m s = V r m s R P = V r m s × I r m s = I r m s 2 R = V r m s 2 R I_{rms} = \frac{V_{rms}}{R} \qquad P = V_{rms} \times I_{rms} = I_{rms}^2 R = \frac{V_{rms}^2}{R} I r m s ​ = R V r m s ​ ​ P = V r m s ​ × I r m s ​ = I r m s 2 ​ R = R V r m s 2 ​ ​

Inductance ( L L L ) & Inductive Reactance ( X L X_L X L ​ )

Inductance ( L L L , measured in Henries , H) is the property of an electrical circuit that opposes any change in circuit current. A circuit has an inductance of 1 Henry 1\text{ Henry} 1 Henry if a current changing at the rate of 1 Ampere per second 1\text{ Ampere per second} 1 Ampere per second induces a counter-EMF of 1 Volt 1\text{ Volt} 1 Volt across its terminals:

  • V L = L Δ i Δ t V_L = L \frac{\Delta i}{\Delta t} V L ​ = L Δ t Δ i ​
  • Inductive Phase Relationship: ELI

Because counter-EMF directly resists the growth of current, current cannot rise instantaneously when alternating voltage is applied. In a purely inductive circuit, voltage leads current by 90 ∘ 90^\circ 9 0 ∘ (or current lags voltage by 90 ∘ 90^\circ 9 0 ∘ ). This fundamental relationship is captured by the first half of the trade mnemonic:

Note

ELI: In an Inductive circuit ( L L L ), Electromotive force ( E E E ) leads Current ( I I I ) by 90 ∘ 90^\circ 9 0 ∘ .

Inductive Reactance Formula

The opposition to alternating current presented by an inductor is termed Inductive Reactance ( X L X_L X L ​ , measured in Ohms , Ω \Omega Ω ):

X L = 2 π f L X_L = 2\pi f L X L ​ = 2 π f L

Where:

X L = inductive reactance in Ohms ( Ω ) X_L = \text{inductive reactance in Ohms (}\Omega\text{)} X L ​ = inductive reactance in Ohms ( Ω )

  • f = frequency in Hertz (Hz) f = \text{frequency in Hertz (Hz)} f = frequency in Hertz (Hz)
  • L = inductance in Henries (H) L = \text{inductance in Henries (H)} L = inductance in Henries (H)

2 π ≈ 6.2832 2\pi \approx 6.2832 2 π ≈ 6.2832 (the angular frequency constant ω = 2 π f \omega = 2\pi f ω = 2 π f )

Worked Example: Calculate the inductive reactance and current for a 120 mH 120\text{ mH} 120 mH ( 0.12 H 0.12\text{ H} 0.12 H ) solenoid coil connected across a 120 V , 60 Hz 120\text{V}, 60\text{ Hz} 120 V , 60 Hz control circuit.

Calculate X L X_L X L ​ : X L = 2 × π × 60 Hz × 0.12 H ≈ 376.99 × 0.12 ≈ 45.24 Ω X_L = 2 \times \pi \times 60\text{ Hz} \times 0.12\text{ H} \approx 376.99 \times 0.12 \approx 45.24\ \Omega X L ​ = 2 × π × 60 Hz × 0.12 H ≈ 376.99 × 0.12 ≈ 45.24 Ω

Calculate current: I L = V X L = 120 V 45.24 Ω ≈ 2.65 Amps (lagging voltage by 90 ∘ ) I_L = \frac{V}{X_L} = \frac{120\text{ V}}{45.24\ \Omega} \approx 2.65\text{ Amps (lagging voltage by } 90^\circ) I L ​ = X L ​ V ​ = 45.24 Ω 120 V ​ ≈ 2.65 Amps (lagging voltage by 9 0 ∘ )

Capacitance ( C C C ) & Capacitive Reactance ( X C X_C X C ​ )

Capacitance ( C C C , measured in Farads , F) is the property of an electrical circuit that opposes any change in circuit voltage by storing electrostatic energy between conductive plates separated by an insulating dielectric :

C = Q V C = \frac{Q}{V} C = V Q ​

Because the Farad is an exceptionally large unit, craft applications utilize microfarads ( μ F = 10 − 6 F \mu\text{F} = 10^{-6}\text{ F} μ F = 1 0 − 6 F ) or picofarads ( pF = 10 − 12 F \text{pF} = 10^{-12}\text{ F} pF = 1 0 − 12 F ).

Capacitive Phase Relationship: ICE

When alternating voltage is applied across a capacitor, charging current flows into the plates at its highest rate when the voltage is passing through zero (maximum rate of voltage change Δ v / Δ t \Delta v / \Delta t Δ v /Δ t ). As the capacitor charges to peak voltage, current drops to zero. In a purely capacitive circuit, current leads voltage by 90 ∘ 90^\circ 9 0 ∘ :

Note

ICE: In a Capacitive circuit ( C C C ), Current ( I I I ) leads Electromotive force ( E E E ) by 90 ∘ 90^\circ 9 0 ∘ .

Combining both relationships yields the trade mnemonic: ELI the ICE man .

Capacitive Reactance Formula

The opposition to alternating current presented by a capacitor is termed Capacitive Reactance ( X C X_C X C ​ , measured in Ohms , Ω \Omega Ω ):

X C = 1 2 π f C X_C = \frac{1}{2\pi f C} X C ​ = 2 π f C 1 ​

Where:

X C = capacitive reactance in Ohms ( Ω ) X_C = \text{capacitive reactance in Ohms (}\Omega\text{)} X C ​ = capacitive reactance in Ohms ( Ω )

  • f = frequency in Hertz (Hz) f = \text{frequency in Hertz (Hz)} f = frequency in Hertz (Hz)
  • C = capacitance in Farads (F) C = \text{capacitance in Farads (F)} C = capacitance in Farads (F)

Worked Example: Calculate the capacitive reactance and current for a 35 μ F 35\ \mu\text{F} 35 μ F motor-run capacitor connected across a 240 V , 60 Hz 240\text{V}, 60\text{ Hz} 240 V , 60 Hz single-phase motor circuit.

Convert microfarads to Farads: C = 35 μ F = 35 × 10 − 6 F = 0.000035 F C = 35\ \mu\text{F} = 35 \times 10^{-6}\text{ F} = 0.000035\text{ F} C = 35 μ F = 35 × 1 0 − 6 F = 0.000035 F

Calculate X C X_C X C ​ : X C = 1 2 × π × 60 Hz × ( 35 × 10 − 6 F ) = 1 376.99 × 0.000035 = 1 0.013195 ≈ 75.79 Ω X_C = \frac{1}{2 \times \pi \times 60\text{ Hz} \times (35 \times 10^{-6}\text{ F})} = \frac{1}{376.99 \times 0.000035} = \frac{1}{0.013195} \approx 75.79\ \Omega X C ​ = 2 × π × 60 Hz × ( 35 × 1 0 − 6 F ) 1 ​ = 376.99 × 0.000035 1 ​ = 0.013195 1 ​ ≈ 75.79 Ω

Calculate current: I C = V X C = 240 V 75.79 Ω ≈ 3.17 Amps (leading voltage by 90 ∘ ) I_C = \frac{V}{X_C} = \frac{240\text{ V}}{75.79\ \Omega} \approx 3.17\text{ Amps (leading voltage by } 90^\circ) I C ​ = X C ​ V ​ = 75.79 Ω 240 V ​ ≈ 3.17 Amps (leading voltage by 9 0 ∘ )

Frequency Response of Reactances

The mathematical structures of X L X_L X L ​ and X C X_C X C ​ show opposing behaviors across the frequency spectrum:

Inductive Reactance ( X L = 2 π f L X_L = 2\pi f L X L ​ = 2 π f L ): Directly proportional to frequency ( X L ∝ f X_L \propto f X L ​ ∝ f ). At direct current ( f = 0 Hz f = 0\text{ Hz} f = 0 Hz ), an ideal inductor exhibits zero reactance ( X L = 0 Ω X_L = 0\ \Omega X L ​ = 0 Ω ), acting as a direct short circuit. As frequency rises, X L X_L X L ​ increases linearly, opposing high frequencies (choke behavior).

Capacitive Reactance ( X C = 1 2 π f C X_C = \frac{1}{2\pi f C} X C ​ = 2 π f C 1 ​ ): Inversely proportional to frequency ( X C ∝ 1 f X_C \propto \frac{1}{f} X C ​ ∝ f 1 ​ ). At direct current ( f = 0 Hz f = 0\text{ Hz} f = 0 Hz ), capacitive reactance is infinite ( X C = ∞ Ω X_C = \infty\ \Omega X C ​ = ∞ Ω ), completely blocking steady DC current. As frequency increases, X C X_C X C ​ drops toward zero, allowing high-frequency AC signals to pass freely. Reactance (Ω)

  • ^ / Inductive (XL = 2πfL)
  • | /
  • | /
  • | /
  • | /
  • | /
  • | /_______ Capacitive (XC = 1 / 2πfC)
  • | / ` - . _
  • +--+----------------> Frequency (f)
  • 0
  • Property Pure Resistance ( R R R ) Pure Inductance ( L L L ) Pure Capacitance ( C C C )
  • Opposition Unit Ohms ( Ω \Omega Ω ) Ohms ( Ω \Omega Ω , X L X_L X L ​ ) Ohms ( Ω \Omega Ω , X C X_C X C ​ )

Phase Relationship In phase ( θ = 0 ∘ \theta = 0^\circ θ = 0 ∘ ) Voltage leads Current by 90 ∘ 90^\circ 9 0 ∘ (ELI) Current leads Voltage by 90 ∘ 90^\circ 9 0 ∘ (ICE)

Formula R = ρ L / A R = \rho L / A R = ρ L / A X L = 2 π f L X_L = 2\pi f L X L ​ = 2 π f L X C = 1 / ( 2 π f C ) X_C = 1 / (2\pi f C) X C ​ = 1/ ( 2 π f C )

Response to Frequency ( f ↑ f \uparrow f ↑ ) Constant (Independent of f f f ) Increases linearly ( X L ↑ X_L \uparrow X L ​ ↑ ) Decreases inversely ( X C ↓ X_C \downarrow X C ​ ↓ )

Direct Current ( f = 0 Hz f = 0\text{ Hz} f = 0 Hz ) Normal opposition ( R R R ) Zero reactance ( X L = 0 Ω X_L = 0\ \Omega X L ​ = 0 Ω , Short) Infinite reactance ( X C = ∞ Ω X_C = \infty\ \Omega X C ​ = ∞ Ω , Open)

Loading diagram... Phase Relationships in AC Circuit Elements (ELI the ICE man)