Study guide

2.1 DC Fundamentals, Ohm's Law & Power

NCCER Commercial Electrician COMELEC26_01

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Electrical Safety, OSHA & NFPA 70E

1.1 OSHA Regulations & Subpart S Compliance 1.2 NFPA 70E Standards & Arc-Flash Protection 1.3 Lockout/Tagout (LOTO) & Absence-of-Voltage Verification 1.4 Jobsite Hazard Recognition & Fall/Trench Safety

2 Chapter 2: Electrical Theory & AC/DC Fundamentals

2.1 DC Fundamentals, Ohm's Law & Power 2.2 Series, Parallel & Combination Circuits 2.3 AC Fundamentals, Reactance & Magnetism 2.4 Impedance, Power Triangles & Power Factor

3 Chapter 3: NEC Layout, General Requirements & Services

3.1 NEC Structure, Navigation & Article 100 Definitions 3.2 NEC Article 110: General Requirements for Electrical Installations 3.3 NEC Article 230: Services & Service Equipment

4 Chapter 4: Branch Circuits, Feeders & Overcurrent Protection

4.1 Branch Circuits & Feeders 4.2 Commercial Load Calculations 4.3 Overcurrent Protection & Coordination

5 Chapter 5: Conductors, Insulation & Sizing Calculations

5.1 Conductor Construction, Materials & Insulation 5.2 Ampacity Determination & Table 310.16 5.3 Ampacity Derating & Adjustment Calculations 5.4 Conductor Installation, Pulling Tension & Splices

6 Chapter 6: Raceways, Boxes & Conduit Bending

6.1 Raceway Systems & Support Rules 6.2 Conduit Bending Principles & Mathematics 6.3 Raceway Fill Calculations 6.4 Box Sizing & Cable Tray Systems

7 Chapter 7: Commercial Wiring Methods, Devices & Special Occupancies

7.1 Commercial Wiring Devices & Receptacles 7.2 Switching Circuits & Commercial Controls 7.3 Commercial Lighting & Emergency Power Systems 7.4 Hazardous (Classified) Locations

8 Chapter 8: Motors, Motor Circuits & Overload Protection

8.1 Motor Principles & Nameplate Interpretation 8.2 Motor Feeder & Branch-Circuit Conductor Sizing 8.3 Motor Overload & Branch-Circuit Short-Circuit Protection

9 Chapter 9: Motor Controls, Ladder Logic & Industrial Drives

9.1 Magnetic Contactors, Starters & Relays 9.2 Control Circuits & Ladder Logic Schematics 9.3 Variable Frequency Drives (VFDs) & PLC Applications

10 Chapter 10: Transformers & Separately Derived Systems

10.1 Transformer Theory, Ratios & Single-Phase Connections 10.2 Three-Phase Transformer Configurations & Calculations 10.3 Transformer Sizing, Protection & Grounding

11 Chapter 11: Grounding & Bonding Systems (NEC Article 250)

11.1 Fundamental Concepts: Grounding vs. Bonding 11.2 Grounding Electrode System & GEC Sizing 11.3 Equipment Grounding Conductors (EGC) 11.4 Main, System & Supply-Side Bonding Jumpers

12 Chapter 12: Electrical Testing, Troubleshooting & Print Reading

12.1 Electrical Test Instruments & CAT Ratings 12.2 Systematic Circuit Troubleshooting & Fault Analysis 12.3 Electrical Drawings, Specifications & One-Line Diagrams 12.4 Fire Alarm Systems & Specialized Low-Voltage Wiring

2.1 DC Fundamentals, Ohm's Law & Power

Key Takeaways Explain This Topic AI

An electrical current of 1 Ampere represents the directed transfer of 1 Coulomb of electrical charge (6.2415 × 10¹⁸ electrons) past a given point per second.

Ohm's Law defines the fundamental linear relationship across DC circuits where current is directly proportional to electromotive force and inversely proportional to resistance: I = V R I = \frac{V}{R} I = R V ​ .

Joule's Law of electric power defines dissipation as P = V × I = I 2 R = V 2 R P = V \times I = I^2 R = \frac{V^2}{R} P = V × I = I 2 R = R V 2 ​ ; doubling circuit current quadruples conductor thermal power loss ( I 2 R I^2R I 2 R ).

Conductor resistance is proportional to length and material resistivity, and inversely proportional to cross-sectional area: R = ρ L A R = \rho \frac{L}{A} R = ρ A L ​ , where copper resistivity is 10.4 Ω ⋅ cmil/ft 10.4\ \Omega\cdot\text{cmil/ft} 10.4 Ω ⋅ cmil/ft at 20°C.

Standard 4-band resistor color codes use bands 1 and 2 for significant digits, band 3 for the decimal multiplier, and band 4 for tolerance (Gold = ±5%, Silver = ±10%, None = ±20%).

Last updated: October 2026

2.1 DC Fundamentals, Ohm's Law & Power

Understanding direct current (DC) electrical circuits begins at the atomic scale. Every electrical phenomenon encountered on a commercial or industrial jobsite—from the operation of solid-state programmable logic controller (PLC) power supplies to large battery energy storage systems (BESS)—is governed by the behavior of subatomic electrical charges responding to electromotive force.

Atomic Structure & Conduction Mechanics

All matter is composed of atoms containing three primary subatomic particles: protons (carrying a positive electrical charge of + 1.602 × 10 − 19 +1.602 \times 10^{-19} + 1.602 × 1 0 − 19 Coulombs), neutrons (electrically neutral), and electrons (carrying an equal negative electrical charge of − 1.602 × 10 − 19 -1.602 \times 10^{-19} − 1.602 × 1 0 − 19 Coulombs). The dense central nucleus contains the protons and neutrons, while electrons orbit within discrete quantum energy shells designated by letters K , L , M , N K, L, M, N K , L , M , N or principal quantum numbers n = 1 , 2 , 3 , 4 n = 1, 2, 3, 4 n = 1 , 2 , 3 , 4 .

The outermost partially filled shell of an atom is termed the valence shell , and the electrons residing within it are valence electrons . The number of valence electrons dictates the chemical and electrical behavior of an element:

Electrical Conductors (1 to 3 valence electrons): Elements such as copper (1 valence electron in its fourth shell), silver (1 valence electron), gold (1 valence electron), and aluminum (3 valence electrons) hold their valence charges with weak electrostatic binding forces. In solid crystalline lattices, the valence band overlaps directly with the conduction band . Consequently, thermal energy at ambient temperatures ( 20 ∘ C 20^\circ\text{C} 2 0 ∘ C to 25 ∘ C 25^\circ\text{C} 2 5 ∘ C ) provides sufficient energy to liberate billions of electrons, forming a sea of free electrons capable of coordinated drift under an electric field.

Semiconductors (exactly 4 valence electrons): Elements like silicon and germanium form rigid covalent crystalline bonds where electrons are shared equally. At absolute zero, semiconductors behave as pure insulators; at room temperature, minor thermal agitation produces limited charge carriers. Controlled introduction of impurities ( doping ) produces N N N -type (electron donor) or P P P -type (hole donor) materials fundamental to diodes, transistors, and rectifiers.

Electrical Insulators (5 to 8 valence electrons): Materials such as polyvinyl chloride (PVC), cross-linked polyethylene (XLPE), rubber, glass, and porcelain possess completely or nearly filled valence shells. A wide forbidden energy gap (band gap exceeding 5 eV 5\text{ eV} 5 eV ) separates the valence band from the conduction band. Extremely high external potentials (dielectric breakdown voltage) are required to strip these electrons from their parent nuclei.

  • Material Class Valence Electrons Band Gap Energy Common Trade Materials
  • Conductor 1 to 3 None (Bands overlap) Copper, Aluminum, Silver, Gold
  • Semiconductor Exactly 4 Moderate (~1.1 eV for Si) Silicon, Germanium, Gallium Arsenide
  • Insulator 5 to 8 Wide (> 5.0 eV) PVC, Rubber, Porcelain, Mica, Teflon
  • Electrical Units: Charge, Current, and Potential
  • 1. The Coulomb ( Q Q Q )

The Coulomb is the SI derived unit of quantity of electric charge (equivalent to one ampere-second). One Coulomb is defined as the absolute charge possessed by approximately 6.2415 × 10 18 6.2415 \times 10^{18} 6.2415 × 1 0 18 electrons (or protons):

1 Coulomb = 6.2415 × 10 18 elementary charges 1\text{ Coulomb} = 6.2415 \times 10^{18}\text{ elementary charges} 1 Coulomb = 6.2415 × 1 0 18 elementary charges

2. The Ampere ( I I I )

The Ampere (Amp) measures the rate of electrical charge flow past a specific reference cross-section in an electrical circuit. One Ampere is equivalent to one Coulomb transferring past a cross-section per second:

I = Q t I = \frac{Q}{t} I = t Q ​

Where:

  • I = current in Amperes (A) I = \text{current in Amperes (A)} I = current in Amperes (A)
  • Q = charge in Coulombs (C) Q = \text{charge in Coulombs (C)} Q = charge in Coulombs (C)
  • t = time in seconds (s) t = \text{time in seconds (s)} t = time in seconds (s)
  • 3. Voltage and Electromotive Force ( V V V or E E E )

Voltage , or potential difference , represents the work or energy required to move a unit charge between two distinct points in an electrical field. Electromotive Force (EMF) refers specifically to the potential generated by an active source converting chemical, mechanical, thermal, or optical energy into electrical energy. One Volt equals one Joule of work expended per Coulomb of transferred charge:

1 Volt = 1 Joule per Coulomb = 1 J/C 1\text{ Volt} = 1\text{ Joule per Coulomb} = 1\text{ J/C} 1 Volt = 1 Joule per Coulomb = 1 J/C

Primary sources of EMF in electrical craft applications include:

Chemical Action: Lead-acid and lithium-iron-phosphate ( L i F e P O 4 LiFePO_4 L i F e P O 4 ​ ) batteries utilizing electrochemical redox reactions.

Electromagnetic Induction: Mechanical generators spinning conductors through magnetic fields.

Photovoltaic Effect: Solar cells converting solar photon energy into DC potential across P - N P\text{-}N P - N junctions.

Thermoelectric Effect: Thermocouples generating millivolt potentials proportional to temperature gradients (Seebeck effect).

Piezoelectric Effect: Mechanical strain applied to quartz or ceramic crystals generating high-voltage, low-current charges.

Note

Conventional Current vs. Electron Flow: In early electrical science, Benjamin Franklin posited that electricity flowed from an area of positive excess to negative deficiency ( conventional current ). Subatomic physics later proved that physical charge carriers in metallic conductors are negatively charged electrons moving from the negative terminal to the positive terminal ( electron flow ). Commercial circuit schematics, vector diagrams, semiconductor symbols (diode arrows), and standard formulas adhere strictly to conventional current conventions.

Conductor Resistance and Resistivity

Resistance ( R R R , measured in Ohms , Ω \Omega Ω ) represents the intrinsic opposition a material presents to the drift of free electrons. Resistance converts electrical energy directly into thermal energy via atomic collisions. Four physical properties govern the resistance of a metallic conductor:

Material Type (Resistivity, ρ \rho ρ or K K K ): The atomic structure and free-electron density.

Conductor Length ( L L L ): Resistance is directly proportional to length.

Cross-Sectional Area ( A A A ): Resistance is inversely proportional to cross-sectional area.

Operating Temperature ( T T T ): Metal conductors exhibit a positive temperature coefficient of resistance.

In North American commercial calculations, cross-sectional area is expressed in circular mils (cmil) . A mil is one one-thousandth of an inch ( 0.001 inch 0.001\text{ inch} 0.001 inch ). The circular mil area of a solid round wire equals its diameter ( d d d ) in mils squared:

A (cmil) = [ d (mils) ] 2 A\text{ (cmil)} = [d\text{ (mils)}]^2 A (cmil) = [ d (mils) ] 2

The DC resistance formula for a conductor is expressed as:

R = ρ × L A = K × L A R = \frac{\rho \times L}{A} = \frac{K \times L}{A} R = A ρ × L ​ = A K × L ​

Where:

R = conductor resistance in Ohms ( Ω ) R = \text{conductor resistance in Ohms (}\Omega\text{)} R = conductor resistance in Ohms ( Ω )

K = resistivity constant in Ohms-circular mil per foot ( Ω ⋅ cmil/ft) K = \text{resistivity constant in Ohms-circular mil per foot (}\Omega\cdot\text{cmil/ft}\text{)} K = resistivity constant in Ohms-circular mil per foot ( Ω ⋅ cmil/ft )

L = length of the conductor in feet (ft) L = \text{length of the conductor in feet (ft)} L = length of the conductor in feet (ft)

A = cross-sectional area in circular mils (cmil) A = \text{cross-sectional area in circular mils (cmil)} A = cross-sectional area in circular mils (cmil)

At 20 ∘ C 20^\circ\text{C} 2 0 ∘ C ( 68 ∘ F 68^\circ\text{F} 6 8 ∘ F ), standard commercial values for K K K are:

  • Annealed Copper: K ≈ 10.4 Ω ⋅ cmil/ft K \approx 10.4\ \Omega\cdot\text{cmil/ft} K ≈ 10.4 Ω ⋅ cmil/ft
  • Hard-Drawn Aluminum: K ≈ 17.0 Ω ⋅ cmil/ft K \approx 17.0\ \Omega\cdot\text{cmil/ft} K ≈ 17.0 Ω ⋅ cmil/ft

Tip

Under elevated conductor operating temperatures (such as 75 ∘ C 75^\circ\text{C} 7 5 ∘ C under normal full-load operating conditions), conductor resistance rises. Commercial calculations frequently adopt adjusted values ( K = 12.9 Ω ⋅ cmil/ft K = 12.9\ \Omega\cdot\text{cmil/ft} K = 12.9 Ω ⋅ cmil/ft for copper and K = 21.2 Ω ⋅ cmil/ft K = 21.2\ \Omega\cdot\text{cmil/ft} K = 21.2 Ω ⋅ cmil/ft for aluminum) to ensure conservative voltage drop evaluations.

Worked Example: Conductor Resistance Calculation

Problem: Calculate the DC resistance of a single 400-foot run of 3 AWG solid copper conductor having an exact diameter of 0.2294 inches at 20 ∘ C 20^\circ\text{C} 2 0 ∘ C .

Convert diameter to mils: d = 0.2294 in × 1 , 000 mils/in = 229.4 mils d = 0.2294\text{ in} \times 1,000\text{ mils/in} = 229.4\text{ mils} d = 0.2294 in × 1 , 000 mils/in = 229.4 mils

Calculate cross-sectional area in circular mils: A = d 2 = ( 229.4 ) 2 ≈ 52 , 624.36 cmil A = d^2 = (229.4)^2 \approx 52,624.36\text{ cmil} A = d 2 = ( 229.4 ) 2 ≈ 52 , 624.36 cmil

Apply the conductor resistance formula using copper K = 10.4 Ω ⋅ cmil/ft K = 10.4\ \Omega\cdot\text{cmil/ft} K = 10.4 Ω ⋅ cmil/ft : R = 10.4 Ω ⋅ cmil/ft × 400 ft 52 , 624.36 cmil = 4 , 160 52 , 624.36 ≈ 0.0791 Ω R = \frac{10.4\ \Omega\cdot\text{cmil/ft} \times 400\text{ ft}}{52,624.36\text{ cmil}} = \frac{4,160}{52,624.36} \approx 0.0791\ \Omega R = 52 , 624.36 cmil 10.4 Ω ⋅ cmil/ft × 400 ft ​ = 52 , 624.36 4 , 160 ​ ≈ 0.0791 Ω

Ohm's Law & Joule's Law of Electric Power

Formulated by Georg Simon Ohm in 1827, Ohm's Law states that the current flowing through a linear conductor is directly proportional to the potential difference across it and inversely proportional to its resistance:

V = I × R I = V R R = V I V = I \times R \qquad I = \frac{V}{R} \qquad R = \frac{V}{I} V = I × R I = R V ​ R = I V ​

Joule's Law defines electrical power ( P P P , measured in Watts , W) as the rate at which electrical energy is transformed into heat or work. Combining Joule's relationship ( P = V × I P = V \times I P = V × I ) with Ohm's Law yields the three fundamental expressions for electrical power:

P = V × I = I 2 R = V 2 R P = V \times I = I^2 R = \frac{V^2}{R} P = V × I = I 2 R = R V 2 ​

From these basic identities, the Ohm's Law Circle (12-formula wheel) provides direct solutions for any unknown parameter given two known values:

Target Variable Given V V V & I I I Given I I I & R R R Given V V V & R R R Given P P P & I I I Given P P P & V V V Given P P P & R R R

Voltage ( V V V ) — V = I × R V = I \times R V = I × R — V = P I V = \frac{P}{I} V = I P ​ — V = P × R V = \sqrt{P \times R} V = P × R ​

Current ( I I I ) — — I = V R I = \frac{V}{R} I = R V ​ — I = P V I = \frac{P}{V} I = V P ​ I = P R I = \sqrt{\frac{P}{R}} I = R P ​ ​

Resistance ( R R R ) R = V I R = \frac{V}{I} R = I V ​ — — R = P I 2 R = \frac{P}{I^2} R = I 2 P ​ R = V 2 P R = \frac{V^2}{P} R = P V 2 ​ —

Power ( P P P ) P = V × I P = V \times I P = V × I P = I 2 R P = I^2 R P = I 2 R P = V 2 R P = \frac{V^2}{R} P = R V 2 ​ — — —

Conductor I 2 R I^2R I 2 R Heat Losses

The relationship P = I 2 R P = I^2 R P = I 2 R demonstrates why electric utilities transmit power at high voltages and low currents. If current through a feeder conductor doubles, the rate of thermal dissipation in that conductor quadruples ( 2 2 = 4 2^2 = 4 2 2 = 4 ). Conversely, halving the current reduces thermal conductor losses to one-fourth ( 25 % 25\% 25% ) of the original value.

Work, Energy & Kilowatt-Hours

While power represents the instantaneous rate of energy consumption ( 1 Watt = 1 Joule per second 1\text{ Watt} = 1\text{ Joule per second} 1 Watt = 1 Joule per second ), work and energy represent total power sustained across an elapsed time period ( E = P × t E = P \times t E = P × t ).

Because the Joule is a tiny unit ( 1 J = 1 Watt-second 1\text{ J} = 1\text{ Watt-second} 1 J = 1 Watt-second ), commercial power distribution utilizes the Kilowatt-hour (kWh) for metering and billing:

1 kWh = 1 , 000 Watts × 3 , 600 seconds = 3 , 600 , 000 Joules = 3.6 MJ 1\text{ kWh} = 1,000\text{ Watts} \times 3,600\text{ seconds} = 3,600,000\text{ Joules} = 3.6\text{ MJ} 1 kWh = 1 , 000 Watts × 3 , 600 seconds = 3 , 600 , 000 Joules = 3.6 MJ

Worked Example: Commercial Energy Consumption and Cost

Problem: A commercial rooftop ventilation unit draws 15 Amps 15\text{ Amps} 15 Amps on a 240 V 240\text{V} 240 V DC bus. The unit runs continuously for 12 hours per day 12\text{ hours per day} 12 hours per day over a 30 day 30\text{ day} 30 day operating cycle. If electrical energy is billed at $0.12 per kWh, determine total energy consumed and the monthly operating cost.

Calculate power consumption in Watts and Kilowatts: P = V × I = 240 V × 15 A = 3 , 600 Watts = 3.6 kW P = V \times I = 240\text{ V} \times 15\text{ A} = 3,600\text{ Watts} = 3.6\text{ kW} P = V × I = 240 V × 15 A = 3 , 600 Watts = 3.6 kW

Calculate total operating hours: Hours = 12 hours/day × 30 days = 360 hours \text{Hours} = 12\text{ hours/day} \times 30\text{ days} = 360\text{ hours} Hours = 12 hours/day × 30 days = 360 hours

Calculate total energy in kilowatt-hours: E = 3.6 kW × 360 hours = 1 , 296 kWh E = 3.6\text{ kW} \times 360\text{ hours} = 1,296\text{ kWh} E = 3.6 kW × 360 hours = 1 , 296 kWh

Calculate monthly operating cost: Cost = 1 , 296 kWh × $ 0.12 / kWh = $ 155.52 \text{Cost} = 1,296\text{ kWh} \times \$0.12/\text{kWh} = \$155.52 Cost = 1 , 296 kWh × $0.12/ kWh = $155.52

Resistor Color Code System

Fixed composition and film resistors utilize standardized color bands to indicate nominal resistance value, multiplier, and manufacturing tolerance per standard EIA-RS-279. Band 1: 1st Significant Digit

  • Band 2: 2nd Significant Digit
  • Band 3: Multiplier (10^n)
  • Band 4: Tolerance (±%)
  • [=== (1) (2) (3) (4) ===]
  • Color Digit (Bands 1, 2, 3) Multiplier (Band 3 or 4) Tolerance (Band 4 or 5)
  • Black 0 10 0 = 1 10^0 = 1 1 0 0 = 1 —
  • Brown 1 10 1 = 10 10^1 = 10 1 0 1 = 10 ± 1 % \pm 1\% ± 1% (F)
  • Red 2 10 2 = 100 10^2 = 100 1 0 2 = 100 ± 2 % \pm 2\% ± 2% (G)
  • Orange 3 10 3 = 1 , 000 10^3 = 1,000 1 0 3 = 1 , 000 —
  • Yellow 4 10 4 = 10 , 000 10^4 = 10,000 1 0 4 = 10 , 000 —
  • Green 5 10 5 = 100 , 000 10^5 = 100,000 1 0 5 = 100 , 000 ± 0.5 % \pm 0.5\% ± 0.5% (D)
  • Blue 6 10 6 = 1 , 000 , 000 10^6 = 1,000,000 1 0 6 = 1 , 000 , 000 ± 0.25 % \pm 0.25\% ± 0.25% (C)
  • Violet 7 10 7 = 10 , 000 , 000 10^7 = 10,000,000 1 0 7 = 10 , 000 , 000 ± 0.1 % \pm 0.1\% ± 0.1% (B)
  • Gray 8 10 8 = 100 , 000 , 000 10^8 = 100,000,000 1 0 8 = 100 , 000 , 000 ± 0.05 % \pm 0.05\% ± 0.05% (A)
  • White 9 10 9 = 1 , 000 , 000 , 000 10^9 = 1,000,000,000 1 0 9 = 1 , 000 , 000 , 000 —
  • Gold — 10 − 1 = 0.1 10^{-1} = 0.1 1 0 − 1 = 0.1 ± 5 % \pm 5\% ± 5% (J)
  • Silver — 10 − 2 = 0.01 10^{-2} = 0.01 1 0 − 2 = 0.01 ± 10 % \pm 10\% ± 10% (K)
  • None — — ± 20 % \pm 20\% ± 20% (M)
  • 4-Band Resistor Decoding

Band 1: First significant digit.

Band 2: Second significant digit.

Band 3: Decimal multiplier ( 10 n 10^n 1 0 n ).

Band 4: Manufacturing tolerance.

Example: A resistor with bands Red - Violet - Yellow - Gold :

  • Band 1 (Red) = 2
  • Band 2 (Violet) = 7
  • Band 3 (Yellow) = Multiplier 10 4 = 10 , 000 10^4 = 10,000 1 0 4 = 10 , 000
  • Band 4 (Gold) = Tolerance ± 5 % \pm 5\% ± 5%

Nominal Resistance: 27 × 10 , 000 Ω = 270 , 000 Ω = 270 k Ω ± 5 % 27 \times 10,000\ \Omega = 270,000\ \Omega = 270\text{ k}\Omega \pm 5\% 27 × 10 , 000 Ω = 270 , 000 Ω = 270 k Ω ± 5%

Acceptable resistance range: 270 k Ω ± 13.5 k Ω 270\text{ k}\Omega \pm 13.5\text{ k}\Omega 270 k Ω ± 13.5 k Ω ( 256.5 k Ω 256.5\text{ k}\Omega 256.5 k Ω to 283.5 k Ω 283.5\text{ k}\Omega 283.5 k Ω ).

5-Band Precision Resistors

Precision resistors add a third significant digit to achieve tight tolerances ( 1 % 1\% 1% or tighter):

Band 1: 1st digit | Band 2: 2nd digit | Band 3: 3rd digit | Band 4: Multiplier | Band 5: Tolerance.

Example: Orange - White - Black - Brown - Brown :

  • Orange (3), White (9), Black (0) → \to → 390
  • Multiplier (Brown) = × 10 \times 10 × 10
  • Tolerance (Brown) = ± 1 % \pm 1\% ± 1%

Nominal Resistance: 390 × 10 = 3 , 900 Ω = 3.9 k Ω ± 1 % 390 \times 10 = 3,900\ \Omega = 3.9\text{ k}\Omega \pm 1\% 390 × 10 = 3 , 900 Ω = 3.9 k Ω ± 1% .

Loading diagram... Ohm's Law & Power Equation Interrelationships