2.4 Impedance, Power Triangles & Power Factor

NCCER Commercial Electrician COMELEC26_01

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Electrical Safety, OSHA & NFPA 70E

1.1 OSHA Regulations & Subpart S Compliance 1.2 NFPA 70E Standards & Arc-Flash Protection 1.3 Lockout/Tagout (LOTO) & Absence-of-Voltage Verification 1.4 Jobsite Hazard Recognition & Fall/Trench Safety

2 Chapter 2: Electrical Theory & AC/DC Fundamentals

2.1 DC Fundamentals, Ohm's Law & Power 2.2 Series, Parallel & Combination Circuits 2.3 AC Fundamentals, Reactance & Magnetism 2.4 Impedance, Power Triangles & Power Factor

3 Chapter 3: NEC Layout, General Requirements & Services

3.1 NEC Structure, Navigation & Article 100 Definitions 3.2 NEC Article 110: General Requirements for Electrical Installations 3.3 NEC Article 230: Services & Service Equipment

4 Chapter 4: Branch Circuits, Feeders & Overcurrent Protection

4.1 Branch Circuits & Feeders 4.2 Commercial Load Calculations 4.3 Overcurrent Protection & Coordination

5 Chapter 5: Conductors, Insulation & Sizing Calculations

5.1 Conductor Construction, Materials & Insulation 5.2 Ampacity Determination & Table 310.16 5.3 Ampacity Derating & Adjustment Calculations 5.4 Conductor Installation, Pulling Tension & Splices

6 Chapter 6: Raceways, Boxes & Conduit Bending

6.1 Raceway Systems & Support Rules 6.2 Conduit Bending Principles & Mathematics 6.3 Raceway Fill Calculations 6.4 Box Sizing & Cable Tray Systems

7 Chapter 7: Commercial Wiring Methods, Devices & Special Occupancies

7.1 Commercial Wiring Devices & Receptacles 7.2 Switching Circuits & Commercial Controls 7.3 Commercial Lighting & Emergency Power Systems 7.4 Hazardous (Classified) Locations

8 Chapter 8: Motors, Motor Circuits & Overload Protection

8.1 Motor Principles & Nameplate Interpretation 8.2 Motor Feeder & Branch-Circuit Conductor Sizing 8.3 Motor Overload & Branch-Circuit Short-Circuit Protection

9 Chapter 9: Motor Controls, Ladder Logic & Industrial Drives

9.1 Magnetic Contactors, Starters & Relays 9.2 Control Circuits & Ladder Logic Schematics 9.3 Variable Frequency Drives (VFDs) & PLC Applications

10 Chapter 10: Transformers & Separately Derived Systems

10.1 Transformer Theory, Ratios & Single-Phase Connections 10.2 Three-Phase Transformer Configurations & Calculations 10.3 Transformer Sizing, Protection & Grounding

11 Chapter 11: Grounding & Bonding Systems (NEC Article 250)

11.1 Fundamental Concepts: Grounding vs. Bonding 11.2 Grounding Electrode System & GEC Sizing 11.3 Equipment Grounding Conductors (EGC) 11.4 Main, System & Supply-Side Bonding Jumpers

12 Chapter 12: Electrical Testing, Troubleshooting & Print Reading

12.1 Electrical Test Instruments & CAT Ratings 12.2 Systematic Circuit Troubleshooting & Fault Analysis 12.3 Electrical Drawings, Specifications & One-Line Diagrams 12.4 Fire Alarm Systems & Specialized Low-Voltage Wiring

2.4 Impedance, Power Triangles & Power Factor

Key Takeaways Explain This Topic AI

Impedance ( Z Z Z ) represents the total opposition to alternating current, combining resistance and net reactance via right-angle vector addition: Z = R 2 + ( X L − X C ) 2 Z = \sqrt{R^2 + (X_L - X_C)^2} Z = R 2 + ( X L ​ − X C ​ ) 2 ​ .

In an AC circuit, True Power ( P P P in Watts) does physical work, Reactive Power ( Q Q Q in VARs) maintains magnetic and electric fields, and Apparent Power ( S S S in VA) represents total source capacity: S = P 2 + Q 2 S = \sqrt{P^2 + Q^2} S = P 2 + Q 2 ​ .

Power Factor is the ratio of True Power to Apparent Power ( PF = P S = cos ⁡ θ \text{PF} = \frac{P}{S} = \cos\theta PF = S P ​ = cos θ ), where inductive commercial loads cause current to lag behind applied voltage.

Series resonance occurs when inductive reactance equals capacitive reactance ( X L = X C X_L = X_C X L ​ = X C ​ ), collapsing net reactance to zero, reducing circuit impedance to pure resistance ( Z = R Z = R Z = R ), and driving circuit current to its maximum.

Installing shunt power factor correction capacitors in parallel with inductive loads supplies magnetizing kVAR locally, reducing total line current, mitigating feeder I 2 R I^2R I 2 R thermal losses, and eliminating utility low-power-factor penalties.

Last updated: October 2026

2.4 Impedance, Power Triangles & Power Factor

Practical commercial and industrial AC systems rarely contain pure resistance, pure inductance, or pure capacitance in isolation. Electric discharge luminaires, commercial refrigeration compressors, three-phase induction motors, and electronic switch-mode power supplies present complex combinations of resistive and reactive elements. To properly size service conductors, transformers, and switchboards, an electrician must master vector impedance calculations and power factor correction principles.

AC Impedance ( Z Z Z ) and Phasor Analysis

Impedance ( Z Z Z , measured in Ohms , Ω \Omega Ω ) is the total opposition an AC circuit presents to the flow of alternating current. Impedance combines pure resistance ( R R R ) and net reactance ( X X X ) into a single vector quantity.

Because resistance causes current and voltage to be in phase ( 0 ∘ 0^\circ 0 ∘ ), inductive reactance causes voltage to lead current by + 90 ∘ +90^\circ + 9 0 ∘ ( + j +j + j ), and capacitive reactance causes voltage to lag current by − 90 ∘ -90^\circ − 9 0 ∘ ( − j -j − j ), these quantities cannot be summed with basic arithmetic. They must be added as vectors (phasors) in a complex plane: +j (Inductive Reactance, +XL)

  • |
  • | * Phasor Z = R + j(XL - XC)
  • | * |
  • | * | Net Reactance
  • |* θ | X = (XL - XC)
  • -----------+------+------------ Real Axis (Resistance, R)
  • |
  • |
  • |
  • j (Capacitive Reactance, -XC)
  • Series RLC Circuit Relationships

In a series RLC circuit:

Net Reactance ( X X X ): Because inductive and capacitive reactances are 180 ∘ 180^\circ 18 0 ∘ out of phase, they cancel each other out directly: X = X L − X C X = X_L - X_C X = X L ​ − X C ​

If X L > X C X_L > X_C X L ​ > X C ​ , the circuit is net inductive (current lags voltage).

If X C > X L X_C > X_L X C ​ > X L ​ , the circuit is net capacitive (current leads voltage).

If X L = X C X_L = X_C X L ​ = X C ​ , the circuit is in resonance .

Total Impedance ( Z Z Z ): Derived from the Pythagorean theorem on the impedance triangle: Z = R 2 + X 2 = R 2 + ( X L − X C ) 2 Z = \sqrt{R^2 + X^2} = \sqrt{R^2 + (X_L - X_C)^2} Z = R 2 + X 2 ​ = R 2 + ( X L ​ − X C ​ ) 2 ​

Phase Angle ( θ \theta θ ): The angular displacement between total applied voltage and circuit current: θ = arctan ⁡ ( X L − X C R ) \theta = \arctan\left(\frac{X_L - X_C}{R}\right) θ = arctan ( R X L ​ − X C ​ ​ )

Ohm's Law for AC Circuits: I = V Z V = I × Z Z = V I I = \frac{V}{Z} \qquad V = I \times Z \qquad Z = \frac{V}{I} I = Z V ​ V = I × Z Z = I V ​

Worked Example: Series RLC Circuit Calculation

Problem: A 240 V , 60 Hz 240\text{V}, 60\text{ Hz} 240 V , 60 Hz commercial branch circuit powers a series network consisting of a resistance R = 30 Ω R = 30\ \Omega R = 30 Ω , an inductive reactance X L = 70 Ω X_L = 70\ \Omega X L ​ = 70 Ω , and a capacitive reactance X C = 30 Ω X_C = 30\ \Omega X C ​ = 30 Ω . Determine net reactance, total impedance, circuit current, phase angle, and the voltage drop across each component.

Calculate net reactance ( X X X ): X = X L − X C = 70 Ω − 30 Ω = 40 Ω (Inductive) X = X_L - X_C = 70\ \Omega - 30\ \Omega = 40\ \Omega\text{ (Inductive)} X = X L ​ − X C ​ = 70 Ω − 30 Ω = 40 Ω (Inductive)

Calculate total impedance ( Z Z Z ): Z = R 2 + X 2 = 30 2 + 40 2 = 900 + 1 , 600 = 2 , 500 = 50 Ω Z = \sqrt{R^2 + X^2} = \sqrt{30^2 + 40^2} = \sqrt{900 + 1,600} = \sqrt{2,500} = 50\ \Omega Z = R 2 + X 2 ​ = 3 0 2 + 4 0 2 ​ = 900 + 1 , 600 ​ = 2 , 500 ​ = 50 Ω

Calculate circuit current ( I I I ): I = V Z = 240 V 50 Ω = 4.8 Amps I = \frac{V}{Z} = \frac{240\text{ V}}{50\ \Omega} = 4.8\text{ Amps} I = Z V ​ = 50 Ω 240 V ​ = 4.8 Amps

Calculate phase angle ( θ \theta θ ): θ = arctan ⁡ ( 40 30 ) = arctan ⁡ ( 1.3333 ) ≈ 53.13 ∘ (lagging) \theta = \arctan\left(\frac{40}{30}\right) = \arctan(1.3333) \approx 53.13^\circ\text{ (lagging)} θ = arctan ( 30 40 ​ ) = arctan ( 1.3333 ) ≈ 53.1 3 ∘ (lagging)

Calculate individual component voltage drops:

Across resistance: V R = I × R = 4.8 A × 30 Ω = 144 V V_R = I \times R = 4.8\text{ A} \times 30\ \Omega = 144\text{ V} V R ​ = I × R = 4.8 A × 30 Ω = 144 V

Across inductor: V L = I × X L = 4.8 A × 70 Ω = 336 V V_L = I \times X_L = 4.8\text{ A} \times 70\ \Omega = 336\text{ V} V L ​ = I × X L ​ = 4.8 A × 70 Ω = 336 V

Across capacitor: V C = I × X C = 4.8 A × 30 Ω = 144 V V_C = I \times X_C = 4.8\text{ A} \times 30\ \Omega = 144\text{ V} V C ​ = I × X C ​ = 4.8 A × 30 Ω = 144 V

Verify total source voltage using vector addition: V S = V R 2 + ( V L − V C ) 2 = 144 2 + ( 336 − 144 ) 2 = 144 2 + 192 2 = 20 , 736 + 36 , 864 = 57 , 600 = 240 V V_S = \sqrt{V_R^2 + (V_L - V_C)^2} = \sqrt{144^2 + (336 - 144)^2} = \sqrt{144^2 + 192^2} = \sqrt{20,736 + 36,864} = \sqrt{57,600} = 240\text{ V} V S ​ = V R 2 ​ + ( V L ​ − V C ​ ) 2 ​ = 14 4 2 + ( 336 − 144 ) 2 ​ = 14 4 2 + 19 2 2 ​ = 20 , 736 + 36 , 864 ​ = 57 , 600 ​ = 240 V

Note

Notice that the voltage drop across the inductor ( V L = 336 V V_L = 336\text{ V} V L ​ = 336 V ) is significantly greater than the total applied supply voltage ( 240 V 240\text{ V} 240 V ). In reactive AC circuits, reactive voltage drops can exceed source potential because reactive components exchange energy without dissipating it.

Series Resonance

Series resonance occurs at the specific operating frequency where inductive reactance exactly equals capacitive reactance ( X L = X C X_L = X_C X L ​ = X C ​ ). Under this condition:

2 π f r L = 1 2 π f r C ⟹ f r = 1 2 π L C 2\pi f_r L = \frac{1}{2\pi f_r C} \implies f_r = \frac{1}{2\pi \sqrt{LC}} 2 π f r ​ L = 2 π f r ​ C 1 ​ ⟹ f r ​ = 2 π L C ​ 1 ​

Key Electrical Conditions at Series Resonance

Zero Net Reactance: X n e t = X L − X C = 0 Ω X_{net} = X_L - X_C = 0\ \Omega X n e t ​ = X L ​ − X C ​ = 0 Ω .

Minimum Impedance: Total circuit impedance collapses to pure resistance: Z = R Z = R Z = R .

Maximum Current: Circuit current reaches its absolute upper limit: I m a x = V S R I_{max} = \frac{V_S}{R} I ma x ​ = R V S ​ ​ .

Unity Power Factor: Current and voltage are perfectly in phase ( θ = 0 ∘ , cos ⁡ θ = 1.0 \theta = 0^\circ, \cos\theta = 1.0 θ = 0 ∘ , cos θ = 1.0 ).

Voltage Magnification ( Q Q Q -factor): The Quality Factor ( Q = X L R Q = \frac{X_L}{R} Q = R X L ​ ​ ) can produce massive resonant overvoltages across L L L and C C C ( V L = V C = Q × V S V_L = V_C = Q \times V_S V L ​ = V C ​ = Q × V S ​ ), capable of rupturing capacitor dielectric layers or flashing over insulation in commercial variable frequency drive (VFD) filter networks.

The AC Power Triangle

In direct current circuits, power is simply P = V × I P = V \times I P = V × I . In alternating current circuits containing reactance, voltage and current are displaced by phase angle θ \theta θ , producing three distinct forms of electrical power that form the AC Power Triangle : /|

  • / |
  • Apparent Power/ | Reactive Power
  • (S, VA)/ | (Q, VAR)
  • / |
  • /θ |
  • +------+
  • True Power (P, Watts)
  • 1. True Power ( P P P / Real Power / Active Power)

The actual rate at which electrical energy is transformed into mechanical work, heat, or light.

Measured in Watts (W) or Kilowatts (kW) .

  • Formula: P = V × I × cos ⁡ θ = I 2 R P = V \times I \times \cos\theta = I^2 R P = V × I × cos θ = I 2 R
  • 2. Reactive Power ( Q Q Q / Quadrature Power)

Power oscillating bidirectionally between the source and reactive storage fields (magnetic fields in inductors, electric fields in capacitors). Reactive power performs no useful mechanical work, but is required to sustain the alternating magnetic flux in motors, transformers, ballasts, and solenoids.

Measured in Volt-Amperes Reactive (VAR) or kilovar (kVAR) .

  • Formula: Q = V × I × sin ⁡ θ = I 2 X Q = V \times I \times \sin\theta = I^2 X Q = V × I × sin θ = I 2 X
  • 3. Apparent Power ( S S S / Total Power)

The total vector power supplied to the circuit by the source. All utility service equipment, transformers, switchgear, and generators are sized and rated in terms of Apparent Power.

Measured in Volt-Amperes (VA) or kilovolt-amperes (kVA) .

Formula: S = V × I = I 2 Z = P 2 + Q 2 S = V \times I = I^2 Z = \sqrt{P^2 + Q^2} S = V × I = I 2 Z = P 2 + Q 2 ​

Power Component Symbol Unit Physical Manifestation Formula

True Power P P P Watts (W) / kW Heat, light, shaft torque (Real work) P = V I cos ⁡ θ = I 2 R P = V I \cos\theta = I^2 R P = V I cos θ = I 2 R

Reactive Power Q Q Q VAR / kVAR Alternating magnetic/electric fields Q = V I sin ⁡ θ = I 2 X Q = V I \sin\theta = I^2 X Q = V I sin θ = I 2 X

Apparent Power S S S VA / kVA Total delivery capacity required S = V I = P 2 + Q 2 S = V I = \sqrt{P^2 + Q^2} S = V I = P 2 + Q 2 ​

Power Factor (PF) & Commercial Impacts

Power Factor represents the efficiency with which electrical power is delivered and utilized. It is defined as the mathematical ratio of True Power to Apparent Power:

PF = True Power Apparent Power = P S = cos ⁡ θ \text{PF} = \frac{\text{True Power}}{\text{Apparent Power}} = \frac{P}{S} = \cos\theta PF = Apparent Power True Power ​ = S P ​ = cos θ

Power factor ranges between 0.0 0.0 0.0 and 1.0 1.0 1.0 (or 0 % 0\% 0% to 100 % 100\% 100% ):

Unity Power Factor ( PF = 1.0 \text{PF} = 1.0 PF = 1.0 ): True power equals apparent power ( P = S P = S P = S ). All current performs useful work; phase angle θ = 0 ∘ \theta = 0^\circ θ = 0 ∘ .

Lagging Power Factor: Current lags voltage (inductive loads such as induction motors, welders, and magnetic ballasts). This is the dominant state of commercial and industrial facilities.

Leading Power Factor: Current leads voltage (capacitive loads, unloaded long underground cables, or over-excited synchronous motors).

Adverse Consequences of Poor Power Factor

Operating a commercial facility at poor power factor (e.g., PF < 0.85 \text{PF} < 0.85 PF < 0.85 ) imposes severe operational and economic burdens:

Excessive Line Current: To deliver a fixed amount of real work ( P P P ), lower power factor forces total line current to rise: I = P V × PF I = \frac{P}{V \times \text{PF}} I = V × PF P ​

Elevated Conductor Thermal Losses ( I 2 R I^2R I 2 R ): Higher line current causes heat dissipation in facility feeders and distribution transformers to surge with the square of current.

Premature Transformer & Switchgear Capacity Saturation: Distribution equipment is rated in kVA. Non-working reactive current consumes transformer ampacity, preventing the addition of new revenue-producing loads.

Increased System Voltage Drop: High line currents increase I × Z I \times Z I × Z impedance drops across feeder conductors, causing brownouts and motor under-voltage.

Utility Demand Penalties: Commercial electric utility tariffs impose direct financial surcharges or bill based on peak kVA demand if average facility power factor falls below a contractual threshold (typically 0.90 0.90 0.90 or 0.95 0.95 0.95 ).

Power Factor Correction Engineering

Because induction motors and transformers require inductive magnetizing current (lagging by 90 ∘ 90^\circ 9 0 ∘ ), connecting shunt capacitor banks in parallel across facility distribution buses supplies this reactive current locally. The capacitor draws leading current that cancels out the lagging current of the inductive loads, freeing upstream utility lines and transformers to carry only true active power.

Sizing Power Factor Correction Capacitors

To correct facility power factor from an initial lagging value ( PF 1 = cos ⁡ θ 1 \text{PF}_1 = \cos\theta_1 PF 1 ​ = cos θ 1 ​ ) to an improved target value ( PF 2 = cos ⁡ θ 2 \text{PF}_2 = \cos\theta_2 PF 2 ​ = cos θ 2 ​ ):

Q C = P × ( tan ⁡ θ 1 − tan ⁡ θ 2 ) Q_C = P \times (\tan\theta_1 - \tan\theta_2) Q C ​ = P × ( tan θ 1 ​ − tan θ 2 ​ )

Where:

Q C = required capacitive rating in kVAR Q_C = \text{required capacitive rating in kVAR} Q C ​ = required capacitive rating in kVAR

P = facility true power in kW P = \text{facility true power in kW} P = facility true power in kW

θ 1 = arccos ⁡ ( PF 1 ) = initial phase angle \theta_1 = \arccos(\text{PF}_1) = \text{initial phase angle} θ 1 ​ = arccos ( PF 1 ​ ) = initial phase angle

θ 2 = arccos ⁡ ( PF 2 ) = target phase angle \theta_2 = \arccos(\text{PF}_2) = \text{target phase angle} θ 2 ​ = arccos ( PF 2 ​ ) = target phase angle

Worked Example: Commercial Facility Power Factor Correction

Problem: A commercial fabrication facility operates on a 480 V 480\text{V} 480 V , 3-phase service with a steady active load P = 300 kW P = 300\text{ kW} P = 300 kW at an uncorrected power factor of 0.72 lagging 0.72\text{ lagging} 0.72 lagging ( PF 1 = 0.72 \text{PF}_1 = 0.72 PF 1 ​ = 0.72 ). Management wishes to install a shunt capacitor bank to raise the facility power factor to 0.95 lagging 0.95\text{ lagging} 0.95 lagging ( PF 2 = 0.95 \text{PF}_2 = 0.95 PF 2 ​ = 0.95 ) to eliminate utility low-power-factor penalties.

Calculate initial apparent power ( S 1 S_1 S 1 ​ ) and line current ( I 1 I_1 I 1 ​ ): S 1 = P PF 1 = 300 kW 0.72 ≈ 416.67 kVA S_1 = \frac{P}{\text{PF}_1} = \frac{300\text{ kW}}{0.72} \approx 416.67\text{ kVA} S 1 ​ = PF 1 ​ P ​ = 0.72 300 kW ​ ≈ 416.67 kVA I 1 = S 1 3 × V = 416 , 667 VA 1.732 × 480 V = 416 , 667 831.38 ≈ 501.2 Amps I_1 = \frac{S_1}{\sqrt{3} \times V} = \frac{416,667\text{ VA}}{1.732 \times 480\text{ V}} = \frac{416,667}{831.38} \approx 501.2\text{ Amps} I 1 ​ = 3 ​ × V S 1 ​ ​ = 1.732 × 480 V 416 , 667 VA ​ = 831.38 416 , 667 ​ ≈ 501.2 Amps

Determine initial and target phase angles: θ 1 = arccos ⁡ ( 0.72 ) ≈ 43.95 ∘ ⟹ tan ⁡ ( 43.95 ∘ ) ≈ 0.9639 \theta_1 = \arccos(0.72) \approx 43.95^\circ \implies \tan(43.95^\circ) \approx 0.9639 θ 1 ​ = arccos ( 0.72 ) ≈ 43.9 5 ∘ ⟹ tan ( 43.9 5 ∘ ) ≈ 0.9639 θ 2 = arccos ⁡ ( 0.95 ) ≈ 18.19 ∘ ⟹ tan ⁡ ( 18.19 ∘ ) ≈ 0.3287 \theta_2 = \arccos(0.95) \approx 18.19^\circ \implies \tan(18.19^\circ) \approx 0.3287 θ 2 ​ = arccos ( 0.95 ) ≈ 18.1 9 ∘ ⟹ tan ( 18.1 9 ∘ ) ≈ 0.3287

Calculate initial and target reactive power: Q 1 = P × tan ⁡ θ 1 = 300 kW × 0.9639 ≈ 289.17 kVAR Q_1 = P \times \tan\theta_1 = 300\text{ kW} \times 0.9639 \approx 289.17\text{ kVAR} Q 1 ​ = P × tan θ 1 ​ = 300 kW × 0.9639 ≈ 289.17 kVAR Q 2 = P × tan ⁡ θ 2 = 300 kW × 0.3287 ≈ 98.61 kVAR Q_2 = P \times \tan\theta_2 = 300\text{ kW} \times 0.3287 \approx 98.61\text{ kVAR} Q 2 ​ = P × tan θ 2 ​ = 300 kW × 0.3287 ≈ 98.61 kVAR

Calculate required capacitor bank rating ( Q C Q_C Q C ​ ): Q C = Q 1 − Q 2 = 289.17 kVAR − 98.61 kVAR = 190.56 kVAR Q_C = Q_1 - Q_2 = 289.17\text{ kVAR} - 98.61\text{ kVAR} = 190.56\text{ kVAR} Q C ​ = Q 1 ​ − Q 2 ​ = 289.17 kVAR − 98.61 kVAR = 190.56 kVAR (Specify a standard commercial 200 kVAR 200\text{ kVAR} 200 kVAR switched capacitor bank).

Calculate post-correction apparent power ( S 2 S_2 S 2 ​ ) and line current ( I 2 I_2 I 2 ​ ): S 2 = P PF 2 = 300 kW 0.95 ≈ 315.79 kVA S_2 = \frac{P}{\text{PF}_2} = \frac{300\text{ kW}}{0.95} \approx 315.79\text{ kVA} S 2 ​ = PF 2 ​ P ​ = 0.95 300 kW ​ ≈ 315.79 kVA I 2 = S 2 3 × V = 315 , 789 VA 831.38 ≈ 379.8 Amps I_2 = \frac{S_2}{\sqrt{3} \times V} = \frac{315,789\text{ VA}}{831.38} \approx 379.8\text{ Amps} I 2 ​ = 3 ​ × V S 2 ​ ​ = 831.38 315 , 789 VA ​ ≈ 379.8 Amps

Evaluation of Results: Correcting the power factor drops feeder line current from 501.2 A 501.2\text{ A} 501.2 A to 379.8 A 379.8\text{ A} 379.8 A —an immediate reduction of 121.4 Amps 121.4\text{ Amps} 121.4 Amps ( 24.2 % 24.2\% 24.2% current reduction). Conductor I 2 R I^2R I 2 R thermal losses throughout the facility main service decrease by: Loss Reduction = 1 − ( 379.8 501.2 ) 2 = 1 − ( 0.7578 ) 2 = 1 − 0.5743 = 42.57 % \text{Loss Reduction} = 1 - \left(\frac{379.8}{501.2}\right)^2 = 1 - (0.7578)^2 = 1 - 0.5743 = 42.57\% Loss Reduction = 1 − ( 501.2 379.8 ​ ) 2 = 1 − ( 0.7578 ) 2 = 1 − 0.5743 = 42.57%

Tip

Always avoid over-correcting past unity into a leading power factor . Over-correction can trigger resonance with supply transformer leakage reactance, generating high harmonic overvoltages that damage sensitive commercial building automation and computer hardware.

Loading diagram... The AC Power Triangle & Vector Relationships