Study guide

8.3 Motor Overload & Branch-Circuit Short-Circuit Protection

NCCER Commercial Electrician COMELEC26_01

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Electrical Safety, OSHA & NFPA 70E

1.1 OSHA Regulations & Subpart S Compliance 1.2 NFPA 70E Standards & Arc-Flash Protection 1.3 Lockout/Tagout (LOTO) & Absence-of-Voltage Verification 1.4 Jobsite Hazard Recognition & Fall/Trench Safety

2 Chapter 2: Electrical Theory & AC/DC Fundamentals

2.1 DC Fundamentals, Ohm's Law & Power 2.2 Series, Parallel & Combination Circuits 2.3 AC Fundamentals, Reactance & Magnetism 2.4 Impedance, Power Triangles & Power Factor

3 Chapter 3: NEC Layout, General Requirements & Services

3.1 NEC Structure, Navigation & Article 100 Definitions 3.2 NEC Article 110: General Requirements for Electrical Installations 3.3 NEC Article 230: Services & Service Equipment

4 Chapter 4: Branch Circuits, Feeders & Overcurrent Protection

4.1 Branch Circuits & Feeders 4.2 Commercial Load Calculations 4.3 Overcurrent Protection & Coordination

5 Chapter 5: Conductors, Insulation & Sizing Calculations

5.1 Conductor Construction, Materials & Insulation 5.2 Ampacity Determination & Table 310.16 5.3 Ampacity Derating & Adjustment Calculations 5.4 Conductor Installation, Pulling Tension & Splices

6 Chapter 6: Raceways, Boxes & Conduit Bending

6.1 Raceway Systems & Support Rules 6.2 Conduit Bending Principles & Mathematics 6.3 Raceway Fill Calculations 6.4 Box Sizing & Cable Tray Systems

7 Chapter 7: Commercial Wiring Methods, Devices & Special Occupancies

7.1 Commercial Wiring Devices & Receptacles 7.2 Switching Circuits & Commercial Controls 7.3 Commercial Lighting & Emergency Power Systems 7.4 Hazardous (Classified) Locations

8 Chapter 8: Motors, Motor Circuits & Overload Protection

8.1 Motor Principles & Nameplate Interpretation 8.2 Motor Feeder & Branch-Circuit Conductor Sizing 8.3 Motor Overload & Branch-Circuit Short-Circuit Protection

9 Chapter 9: Motor Controls, Ladder Logic & Industrial Drives

9.1 Magnetic Contactors, Starters & Relays 9.2 Control Circuits & Ladder Logic Schematics 9.3 Variable Frequency Drives (VFDs) & PLC Applications

10 Chapter 10: Transformers & Separately Derived Systems

10.1 Transformer Theory, Ratios & Single-Phase Connections 10.2 Three-Phase Transformer Configurations & Calculations 10.3 Transformer Sizing, Protection & Grounding

11 Chapter 11: Grounding & Bonding Systems (NEC Article 250)

11.1 Fundamental Concepts: Grounding vs. Bonding 11.2 Grounding Electrode System & GEC Sizing 11.3 Equipment Grounding Conductors (EGC) 11.4 Main, System & Supply-Side Bonding Jumpers

12 Chapter 12: Electrical Testing, Troubleshooting & Print Reading

12.1 Electrical Test Instruments & CAT Ratings 12.2 Systematic Circuit Troubleshooting & Fault Analysis 12.3 Electrical Drawings, Specifications & One-Line Diagrams 12.4 Fire Alarm Systems & Specialized Low-Voltage Wiring

8.3 Motor Overload & Branch-Circuit Short-Circuit Protection

Key Takeaways Explain This Topic AI

Motor circuits separate overcurrent protection into two discrete functions: Overload Protection (NEC Part III) protecting against sustained operational overcurrents, and Branch-Circuit Short-Circuit and Ground-Fault Protection (BCSCGFP - NEC Part IV) protecting against catastrophic fault currents.

Separate motor overload protection under NEC 430.32(A)(1) is sized strictly using nameplate FLA: maximum 125% of FLA for motors with Service Factor ≥ 1.15 \ge 1.15 ≥ 1.15 or temperature rise ≤ 40 ∘ C \le 40^\circ\text{C} ≤ 4 0 ∘ C , and maximum 115% of FLA for all other motors.

NEC Table 430.52 standard maximum ratings for BCSCGFP are: Dual-Element Time-Delay Fuses (175%), Inverse-Time Breakers (250%), Non-Time Delay Fuses (300%), and Instantaneous Trip Breakers (800%).

Exception 1 to NEC 430.52(C)(1) permits rounding UP to the next standard ampere rating in 240.6(A) if the calculated branch protective rating does not match a standard size.

Feeder overcurrent protection per NEC 430.62(A) equals the largest branch-circuit protective device rating plus the sum of other motor Table FLCs; unlike branch circuits, feeder protective devices must NEVER round up—they must round DOWN to the next standard rating.

Last updated: October 2026

8.3 Motor Overload & Branch-Circuit Short-Circuit Protection

In standard commercial branch circuits (such as lighting and general receptacle circuits), a single overcurrent protective device—typically a standard 15A or 20A inverse-time circuit breaker—performs both overload protection and short-circuit/ground-fault protection simultaneously. In motor circuits, however, this unified approach is physically impossible. Because an electric motor draws five to eight times its normal operating current during locked-rotor starting, an overcurrent device sized closely enough to protect the motor windings from mild overloads ( 115 % to 125 % of FLA 115\%\text{ to }125\%\text{ of FLA} 115% to 125% of FLA ) would trip instantly every time the motor attempted to start.

To solve this dilemma, NEC Article 430 splits motor overcurrent protection into two discrete, coordinated systems :

Motor Overload Protection (NEC Article 430, Part III) : Protects the motor windings, controller contactors, and branch conductors against excessive, damaging thermal heating resulting from mechanical motor overloads, low supply voltage, or phase loss (single-phasing).

Motor Branch-Circuit Short-Circuit and Ground-Fault Protection (NEC Article 430, Part IV) : Protects the motor branch-circuit conductors, motor controller, and disconnect switch against violent short circuits (phase-to-phase faults) and ground faults (phase-to-ground faults). Overcurrent Spectrum in Motor Circuits

  • ┌───────────────────────────────────────────────┬───────────────────────────────────────────┐
  • │ OVERLOAD REGION │ SHORT-CIRCUIT & GROUND-FAULT REGION │
  • │ (105% to 600% of Motor Full-Load Current) │ (600% to 50,000%+ Fault Current) │
  • ├───────────────────────────────────────────────┼───────────────────────────────────────────┤
  • │ • Mechanical binding or bearing failure │ • Phase-to-phase short circuit │
  • │ • Low terminal voltage / high current draw │ • Phase-to-ground dielectric breakdown │
  • │ • Loss of one phase (single-phasing) │ • Direct metallic bolted faults │
  • │ • Continuous shaft overloading │ │
  • │ • Cleared by: OVERLOAD RELAYS (NEC Part III) │ • Cleared by: FUSES / BREAKERS (Part IV) │
  • │ • Tripping response: Seconds to minutes │ • Tripping response: Milliseconds / cycles│
  • └───────────────────────────────────────────────┴───────────────────────────────────────────┘
  • Motor Overload Protection Mechanics (NEC Part III)

An overload is an operating overcurrent condition that, if permitted to persist for a sufficient time, will cause dangerous overheating of motor winding insulation. Overload relays are installed inside the magnetic motor starter housing, directly downstream from the electromagnetic contactor poles.

Commercial facilities utilize three primary overload relay mechanisms:

1. Bimetallic Thermal Overload Relays

Operating Principle : Current flowing to the motor passes through small internal resistive heater elements located adjacent to a bimetallic strip (composed of two dissimilar metals with different coefficients of thermal expansion welded together). As current heats the strip, one metal expands faster than the other, causing the strip to bend.

Tripping Mechanism : Under persistent overload, the physical deflection of the bimetallic strip pushes against an internal mechanical trip bar, snapping open a set of normally closed (NC) auxiliary control contacts (terminals 95-96) . Opening these contacts instantly de-energizes the magnetic starter contactor coil, dropping out the main power contacts and disconnecting the motor from the line.

Ambient Temperature Compensation : Bimetallic relays often feature a compensating bimetal strip that flexes with ambient room temperature swings, preventing false tripping when starters are mounted in hot mechanical rooms or outdoor control panels.

2. Melting Alloy (Eutectic Alloy) Overload Relays

Operating Principle : Commonly known as "solder pot" relays. Motor current flows through an interchangeable resistive heater coil surrounding a small brass tube filled with a special eutectic alloy solder . A ratchet wheel is held rigidly stationary within the solidified solder pot, restraining a spring-loaded mechanical trip arm.

Tripping Mechanism : When persistent overload current heats the alloy to its exact melting point (eutectic transition), the solder liquefies instantly. The ratchet wheel spins freely, releasing the spring-loaded trip arm to snap open the NC control contacts (95-96). Once tripped, the alloy must cool and resolidify (taking 1 to 3 minutes) before the reset pushbutton can re-engage the ratchet wheel.

Interchangeable Heaters : The electrical trip rating is changed physically by unscrewing and swapping out the modular heater elements according to manufacturer thermal selection tables based on motor nameplate FLA.

3. Solid-State (Electronic) Overload Relays

Operating Principle : Utilizes internal current transformers (CTs) or Hall-effect sensors to continuously monitor the actual current flowing in all three phases electronically.

Phase Loss & Unbalance Protection : Electronic overloads detect a phase loss (single-phasing) or current unbalance exceeding 30 % 30\% 30% within 2 to 3 seconds , tripping the starter before the rotor experiences catastrophic thermal destruction. (Mechanical thermal heaters may take minutes to trip under single-phasing, often failing to save the motor).

Selectable Trip Classes : Electronic overloads allow electricians to toggle between standardized trip classes per NEMA ICS 2 :

Class 10 : Must trip within 10 seconds at 600 % 600\% 600% of full-load current (used for hermetic refrigeration compressors, submersible pumps, and high-efficiency motors).

Class 20 : Must trip within 20 seconds at 600 % 600\% 600% of full-load current (standard industrial baseline for general-purpose Design B motors).

Class 30 : Must trip within 30 seconds at 600 % 600\% 600% of full-load current (used for hard-to-start, high-inertia loads like crushers and large industrial fans).

Sizing Motor Overload Protection (NEC 430.32)

Under NEC 430.32(A)(1) , each continuous-duty motor rated more than 1 HP 1\text{ HP} 1 HP must be protected against overload by an independent overload device sized as a percentage of the motor nameplate Full-Load Amperes (FLA) , NOT the NEC Table FLC!

Overload Sizing Rules (NEC 430.32(A)(1)):

Motors with a Marked Service Factor of 1.15 or Greater : Overload protection must be sized at not more than 125 % 125\% 125% of the motor nameplate FLA : Overload Maximum Setting = 1.25 × I Nameplate FLA \text{Overload Maximum Setting} = 1.25 \times I_{\text{Nameplate FLA}} Overload Maximum Setting = 1.25 × I Nameplate FLA ​

Motors with a Marked Temperature Rise of 40°C or Less : Overload protection must be sized at not more than 125 % 125\% 125% of the motor nameplate FLA : Overload Maximum Setting = 1.25 × I Nameplate FLA \text{Overload Maximum Setting} = 1.25 \times I_{\text{Nameplate FLA}} Overload Maximum Setting = 1.25 × I Nameplate FLA ​

All Other Motors : Motors marked with a Service Factor of 1.0, or marked with a temperature rise greater than 40 ∘ C 40^\circ\text{C} 4 0 ∘ C (e.g., 50 ∘ C 50^\circ\text{C} 5 0 ∘ C ), must be protected at not more than 115 % 115\% 115% of the motor nameplate FLA : Overload Maximum Setting = 1.15 × I Nameplate FLA \text{Overload Maximum Setting} = 1.15 \times I_{\text{Nameplate FLA}} Overload Maximum Setting = 1.15 × I Nameplate FLA ​

Overload Modification Rules (NEC 430.32(C))

If the standard overload relay heater selected under the 125 % 125\% 125% or 115 % 115\% 115% rule is insufficient to allow the motor to start or carry its load (for example, high inertia causes the thermal heater to trip during acceleration), the electrician is permitted to install the next larger size heater, subject to the absolute maximum ceilings established by NEC 430.32(C) :

Service Factor ≥ 1.15 \ge 1.15 ≥ 1.15 or Temp Rise ≤ 40 ∘ C \le 40^\circ\text{C} ≤ 4 0 ∘ C : Absolute maximum 140 % 140\% 140% of nameplate FLA .

All Other Motors (SF = 1.0) : Absolute maximum 130 % 130\% 130% of nameplate FLA .

Motor Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC Part IV)

Branch-circuit short-circuit and ground-fault protective devices (BCSCGFP) protect the branch-circuit conductors, disconnect switches, and controllers against catastrophic magnetic forces and arc-flash energies resulting from short circuits.

Table 430.52 Sizing Multipliers

Under NEC 430.52 , the maximum rating or setting of the branch-circuit protective device is determined by multiplying the motor full-load current from NEC Tables 430.248 or 430.250 (Table FLC) by the percentage specified in NEC Table 430.52 :

Protective Device Type Maximum % of NEC Table FLC (Single-Phase & SCIM) Operational Characteristics

Non-Time Delay Fuses 300% Fast-acting; requires 300% sizing to clear locked-rotor inrush without blowing.

Dual-Element (Time-Delay) Fuses 175% Contains thermal overload spring + fast short-circuit element; rides through starting inrush.

Inverse-Time Circuit Breakers 250% Thermal-magnetic breaker; thermal element rides through inrush, magnetic trip clears faults.

Instantaneous Trip Breakers (MCP) 800% Magnetic-only breaker; permitted ONLY as part of a listed combination starter assembly.

The "Next Higher Standard Rating" Rule: Exception 1 to NEC 430.52(C)(1)

Standard ampere ratings for fuses and fixed inverse-time circuit breakers are established by NEC 240.6(A) :

Standard Sizes (Amperes) : 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600...

Under NEC 430.52(C)(1) Exception 1 , where the calculated maximum percentage does not correspond to a standard ampere rating, the electrician is permitted to round UP to the next higher standard ampere rating listed in NEC 240.6(A).

Exception 2: Maximum Escalation Ceilings for Hard Starting

If the protective device selected under the standard Table 430.52 percentages and Exception 1 still trips during motor starting, NEC 430.52(C)(1) Exception 2 permits increasing the protective device rating up to the following absolute statutory maximums:

Dual-Element (Time-Delay) Fuses : Permitted to be increased up to 225 % 225\% 225% of Table FLC .

Inverse-Time Circuit Breakers :

For motors with Table FLC of 100 Amperes 100\text{ Amperes} 100 Amperes or less : Permitted to be increased up to 400 % 400\% 400% of Table FLC .

For motors with Table FLC greater than 100 Amperes 100\text{ Amperes} 100 Amperes : Permitted to be increased up to 300 % 300\% 300% of Table FLC .

Non-Time Delay Fuses : Permitted to be increased up to 400 % 400\% 400% of Table FLC (for fuses rated 600A or less).

Instantaneous Trip Breakers : May be adjusted up to 1 , 100 % 1,100\% 1 , 100% of Table FLC for standard motors, or up to 1 , 700 % 1,700\% 1 , 700% of Table FLC for NEMA Design B energy-efficient motors where necessary to clear high transient inrush.

Feeder Short-Circuit & Ground-Fault Protection (NEC 430.62)

When a single feeder supplies two or more motor branch circuits, the feeder overcurrent protective device must be sized to allow the largest motor to start while all other motors are operating at full load, without creating an overcurrent hazard on the feeder conductors.

Sizing Formula (NEC 430.62(A))

Under NEC 430.62(A) , the rating or setting of the feeder overcurrent protective device shall NOT exceed the rating of the largest branch-circuit short-circuit and ground-fault protective device of any motor in the group, plus the sum of the full-load currents of all other motors served by the feeder:

Feeder OCPD Max = Largest Branch Protective Device Rating + ∑ I FLC (other motors) \text{Feeder OCPD Max} = \text{Largest Branch Protective Device Rating} + \sum I_{\text{FLC (other motors)}} Feeder OCPD Max = Largest Branch Protective Device Rating + ∑ I FLC (other motors) ​

[!CRITICAL] The Strict Feeder Rounding Trap : Unlike branch circuits where Exception 1 to 430.52 permits rounding UP to the next standard rating, NEC 430.62(A) contains NO exception allowing rounding up ! The code establishes an absolute maximum ceiling. If the calculated feeder protective rating does not equal a standard size in NEC 240.6(A), you MUST round DOWN to the next lower standard rating ! Rounding up on a feeder calculation is a major code violation on licensing exams and job inspections.

Comprehensive Worked Engineering Calculation: Multi-Motor Commercial Installation

Let us synthesize the entire scope of Article 430 by engineering the complete branch-circuit conductor, overload, branch short-circuit, feeder conductor, and feeder overcurrent protection for a commercial subpanel supplying three 460-volt, 3-phase, 60 Hz squirrel-cage induction motors.

System Data:

Motor 1 : 40 HP, 460V, 3-phase, NEMA Design B, Nameplate FLA = 50 A, Service Factor = 1.15. Protected by an Inverse-Time Circuit Breaker .

Motor 2 : 20 HP, 460V, 3-phase, NEMA Design B, Nameplate FLA = 26 A, Service Factor = 1.0. Protected by Dual-Element Time-Delay Fuses .

Motor 3 : 10 HP, 460V, 3-phase, NEMA Design B, Nameplate FLA = 13.5 A, Service Factor = 1.15. Protected by an Inverse-Time Circuit Breaker .

Raceway & Conductors : Copper conductors with 75 ∘ C 75^\circ\text{C} 7 5 ∘ C terminal ratings.

Step 1: Look Up Table FLCs (NEC Table 430.250)

Per NEC 430.6(A)(1), we look up the full-load currents from Table 430.250:

  • Motor 1 (40 HP) : Table FLC = 52 Amperes \text{Table FLC} = 52\text{ Amperes} Table FLC = 52 Amperes
  • Motor 2 (20 HP) : Table FLC = 27 Amperes \text{Table FLC} = 27\text{ Amperes} Table FLC = 27 Amperes
  • Motor 3 (10 HP) : Table FLC = 14 Amperes \text{Table FLC} = 14\text{ Amperes} Table FLC = 14 Amperes
  • Step 2: Sizing Individual Branch-Circuit Conductors (NEC 430.22)

Conductors must have an allowable ampacity ≥ 125 % × Table FLC \ge 125\% \times \text{Table FLC} ≥ 125% × Table FLC (Table 310.16, 75 ∘ C 75^\circ\text{C} 7 5 ∘ C Cu):

Motor 1 : I cond ≥ 1.25 × 52 A = 65.0 A → I_{\text{cond}} \ge 1.25 \times 52\text{ A} = 65.0\text{ A} \rightarrow I cond ​ ≥ 1.25 × 52 A = 65.0 A → 6 AWG Copper (rated 65A at 75°C).

Motor 2 : I cond ≥ 1.25 × 27 A = 33.75 A → I_{\text{cond}} \ge 1.25 \times 27\text{ A} = 33.75\text{ A} \rightarrow I cond ​ ≥ 1.25 × 27 A = 33.75 A → 10 AWG Copper (rated 35A at 75°C).

Motor 3 : I cond ≥ 1.25 × 14 A = 17.5 A → I_{\text{cond}} \ge 1.25 \times 14\text{ A} = 17.5\text{ A} \rightarrow I cond ​ ≥ 1.25 × 14 A = 17.5 A → 14 AWG Copper (rated 20A at 75°C).

Step 3: Sizing Separate Motor Overload Protection (NEC 430.32(A)(1))

Overload protection is sized strictly from Nameplate FLA :

Motor 1 (Service Factor 1.15 1.15 1.15 , Nameplate FLA = 50 A): Multiplier is 125 % 125\% 125% : Overload Max = 1.25 × 50 A = 62.5 Amperes \text{Overload Max} = 1.25 \times 50\text{ A} = 62.5\text{ Amperes} Overload Max = 1.25 × 50 A = 62.5 Amperes

Motor 2 (Service Factor 1.0 1.0 1.0 , Nameplate FLA = 26 A): Multiplier is 115 % 115\% 115% : Overload Max = 1.15 × 26 A = 29.9 Amperes \text{Overload Max} = 1.15 \times 26\text{ A} = 29.9\text{ Amperes} Overload Max = 1.15 × 26 A = 29.9 Amperes

Motor 3 (Service Factor 1.15 1.15 1.15 , Nameplate FLA = 13.5 A): Multiplier is 125 % 125\% 125% : Overload Max = 1.25 × 13.5 A = 16.88 Amperes \text{Overload Max} = 1.25 \times 13.5\text{ A} = 16.88\text{ Amperes} Overload Max = 1.25 × 13.5 A = 16.88 Amperes

Step 4: Sizing Branch-Circuit Short-Circuit & Ground-Fault Protection (NEC 430.52)

Sized from Table FLC using Table 430.52 and rounding UP per Exception 1 to 430.52(C)(1):

Motor 1 (Inverse-Time Breaker, max 250%) : Rating = 52 A (Table FLC) × 2.50 = 130 Amperes \text{Rating} = 52\text{ A (Table FLC)} \times 2.50 = 130\text{ Amperes} Rating = 52 A (Table FLC) × 2.50 = 130 Amperes

130A is not a standard size in Table 240.6(A). Applying Exception 1, we round UP to the next standard rating: 150 Ampere Circuit Breaker .

Motor 2 (Dual-Element Time-Delay Fuse, max 175%) : Rating = 27 A (Table FLC) × 1.75 = 47.25 Amperes \text{Rating} = 27\text{ A (Table FLC)} \times 1.75 = 47.25\text{ Amperes} Rating = 27 A (Table FLC) × 1.75 = 47.25 Amperes

47.25A is not a standard size in Table 240.6(A). Applying Exception 1, we round UP to the next standard rating: 50 Ampere Dual-Element Fuse .

Motor 3 (Inverse-Time Breaker, max 250%) : Rating = 14 A (Table FLC) × 2.50 = 35.0 Amperes \text{Rating} = 14\text{ A (Table FLC)} \times 2.50 = 35.0\text{ Amperes} Rating = 14 A (Table FLC) × 2.50 = 35.0 Amperes

35A is an exact standard rating in Table 240.6(A): 35 Ampere Circuit Breaker .

Step 5: Sizing Feeder Conductors (NEC 430.24)

I feeder ≥ ( 1.25 × I largest FLC ) + ∑ I other FLCs I_{\text{feeder}} \ge (1.25 \times I_{\text{largest FLC}}) + \sum I_{\text{other FLCs}} I feeder ​ ≥ ( 1.25 × I largest FLC ​ ) + ∑ I other FLCs ​ I feeder ≥ ( 1.25 × 52 A ) + 27 A + 14 A = 65 A + 41 A = 106.0 Amperes I_{\text{feeder}} \ge (1.25 \times 52\text{ A}) + 27\text{ A} + 14\text{ A} = 65\text{ A} + 41\text{ A} = 106.0\text{ Amperes} I feeder ​ ≥ ( 1.25 × 52 A ) + 27 A + 14 A = 65 A + 41 A = 106.0 Amperes

Table 310.16 ( 75 ∘ C 75^\circ\text{C} 7 5 ∘ C Cu): 3 AWG is rated 100A ( 100 A < 106 A 100\text{ A} < 106\text{ A} 100 A < 106 A — too small).

2 AWG Copper is rated 115 Amperes ( 115 A ≥ 106 A 115\text{ A} \ge 106\text{ A} 115 A ≥ 106 A ).

Select: 2 AWG Copper THHN/THWN-2 conductors for the feeder .

Step 6: Sizing Feeder Overcurrent Protective Device (NEC 430.62(A))

Apply the feeder protection formula: Feeder OCPD Max = Largest Branch Protective Device + ∑ I other Table FLCs \text{Feeder OCPD Max} = \text{Largest Branch Protective Device} + \sum I_{\text{other Table FLCs}} Feeder OCPD Max = Largest Branch Protective Device + ∑ I other Table FLCs ​

Largest branch protective device in the system: Motor 1 has a 150 A circuit breaker .

Sum of other motor Table FLCs: Motor 2 (27 A) + Motor 3 (14 A) = 41 A = 41\text{ A} = 41 A .

Feeder OCPD Max = 150 A + 41 A = 191.0 Amperes \text{Feeder OCPD Max} = 150\text{ A} + 41\text{ A} = 191.0\text{ Amperes} Feeder OCPD Max = 150 A + 41 A = 191.0 Amperes

Check Rounding Rule : 191A is not a standard ampere rating in NEC 240.6(A) (standard ratings are 175A, 200A, 225A). Because NEC 430.62(A) states the device "shall not exceed" this value, we CANNOT round up to 200A !

We must round DOWN to the next lower standard rating in 240.6(A):

Select: 175 Ampere Inverse-Time Circuit Breaker for the feeder overcurrent protection.

Loading diagram... Motor Protection Coordination: Overload vs Fault Tripping Curves