Study guide
6.1 Valve Types and Service Selection
NCCER Industrial Maintenance Mechanic Exam
Track your progress as you read
Finished sections get a check mark.
1 The NCCER Industrial Maintenance Mechanic Assessment
1.1 The IMM Journey-Level Credential and Assessment Specification 1.2 The Nine Content Domains: Item Counts and a Study Plan
2 Industrial Maintenance Mechanic Fundamentals
2.1 Safety Programs, PPE, and Hazard Communication 2.2 Hazardous Energy Control: Lockout/Tagout and Confined Space Entry 2.3 Tools of the Trade: Hand and Power Tools 2.4 Oxyfuel Cutting: Equipment, Safe Setup, and Cutting Practice 2.5 Ferrous Metal Piping Practices: Cutting, Threading, and Joining
3 Rigging and Mobile Equipment
3.1 Slings, Rigging Hardware, and Inspection Criteria 3.2 Load Weight, Center of Gravity, Sling Angle, and Hand Signals 3.3 Mobile and Support Equipment: Forklifts, Aerial Lifts, and Mobile Cranes
4 Craft Mathematics, Layout, and Precision Measurement
4.1 Craft-Related Mathematics: Fractions, Units, Area, and Volume 4.2 Advanced Trade Math: Right Triangles, Trigonometry, and Pipe Offsets 4.3 Basic Layout: Squaring, Leveling, and Transferring Elevations 4.4 Precision Measuring Tools: Micrometers, Verniers, and Dial Indicators 4.5 Gauges, Tolerances and Fits, and Torque Measurement
5 Construction Drawings and Blueprint Reading
5.1 Reading Construction Drawings: Views, Lines, Scales, and the Title Block 5.2 Orthographic, Isometric, Arrangement, and Foundation Drawings 5.3 Advanced Blueprint Reading: P&IDs, Instrument Tags, and Welding Symbols
6 Valves, Packing, and Mechanical Seals
6.1 Valve Types and Service Selection 6.2 Valve Construction, Markings, Pressure Classes, and Actuators 6.3 Removing and Installing Valves: Flange Bolting and Torque Sequence 6.4 Valve Maintenance: Packing, Stuffing Boxes, Gaskets, and O-Rings 6.5 Hydrostatic and Pneumatic Testing of Piping and Equipment 6.6 Mechanical Seals: Components, Types, and Installation
7 Bearings, Lubrication, and Couplings
7.1 Bearing Types, Designations, and Selection 7.2 Bearing Lubrication, Handling, and Failure Analysis 7.3 Removing and Installing Bearings: Fits, Heating, and Mounting 7.4 Couplings: Types, Selection, and Installation
8 Pumps, Baseplates, and Mechanical Drives
8.1 Pumps and Drivers: Centrifugal and Positive Displacement 8.2 Setting Baseplates and Soleplates: Leveling, Anchoring, and Grouting 8.3 Prealignment: Soft Foot, Runout, Pipe Strain, and Shims 8.4 Installing Belt and Chain Drives
9 Shaft Alignment: Conventional, Reverse, and Laser
9.1 Conventional Rim-and-Face Dial Indicator Alignment 9.2 Reverse Dial Indicator Alignment 9.3 Laser Shaft Alignment Systems
10 Maintenance Troubleshooting: Method, Pumps, and Gearboxes
10.1 Systematic Troubleshooting and Root Cause Analysis 10.2 Troubleshooting and Repairing Pumps 10.3 Troubleshooting and Repairing Gearboxes
11 Steam Systems, Boilers, and Process Vessels
11.1 Low-Pressure Steam Systems, Traps, and Condensate Return 11.2 High-Pressure Steam Generation and Boiler Auxiliaries 11.3 Distillation Towers, Vessels, and Internals
12 Compressors and Pneumatic Systems
12.1 Air Compressor Types, Operation, and Maintenance 12.2 Compressed Air Treatment, Storage, and Distribution 12.3 FRL Units, Pneumatic Valves, Actuators, and Speed Control
6.1 Valve Types and Service Selection
Key Takeaways Explain This Topic AI
A gate valve is an on/off valve and must not be used for throttling, because a partly open disc chatters and erodes the seat.
A globe valve is the standard throttling valve; its tortuous flow path gives it a much higher pressure drop than a gate valve.
Ball, plug, and butterfly valves are quarter-turn valves, which makes them fast to operate and easy to see the position of.
A swing check valve must be installed in a horizontal line or in a vertical line with upward flow so gravity assists closure.
A safety valve serves compressible fluids and pops fully open, while a relief valve serves incompressible liquids and opens progressively.
Last updated: September 2026
The largest domain on the exam
Domain 5, Valves and Seals , contributes 16 of 115 items — tied for the largest single block. It references 32109 Valves , 32204 Ferrous Metal Piping Practices , 32205 Identify, Install, and Maintain Valves , 32206 Hydrostatic and Pneumatic Testing , and 32308 Installing Mechanical Seals . Chapters 2 and 6 of this guide together cover all five.
The four jobs a valve can do
Every valve exists to do one of four things: start and stop flow , throttle (regulate) flow , prevent reverse flow , or relieve pressure . Matching the valve to the job is the single most tested idea in this module.
- Valve Primary job Motion Pressure drop Notes
- Gate Start/stop Multi-turn, linear Very low when full open Never throttle; wedge or parallel slide disc
- Globe Throttle Multi-turn, linear High Seat perpendicular to flow; the throttling standard
- Ball Start/stop Quarter turn Very low (full port) Tight shutoff; full port vs reduced port
- Plug Start/stop, diverting Quarter turn Low Lubricated or sleeved; multiport versions divert
Butterfly Start/stop and moderate throttle Quarter turn Low to moderate Compact and light; wafer, lug, or double-flanged
- Diaphragm Start/stop, throttle Multi-turn Moderate Slurries and corrosives; no packing to leak
- Check Prevent backflow Automatic Varies by type No operator; flow itself opens and closes it
- Relief / safety Protect from overpressure Automatic N/A Set pressure; discharge to a safe location
- Needle Fine throttle, small flow Multi-turn Very high Instrument and sample lines
- Gate valves in detail
A gate valve lifts a flat or wedge-shaped disc straight out of the flow path. Fully open, the bore is nearly unobstructed, so the pressure drop is minimal. Fully closed, the disc seats against both faces.
The failure mode that defines the valve: throttling destroys it . A partly withdrawn disc sits in a high-velocity stream, vibrates against its guides, and the throttled jet erodes the seating surfaces. The valve then will not shut off tight, which is the one thing it was installed to do.
Two stem arrangements:
Rising stem (OS&Y — outside screw and yoke) : the stem rises as the valve opens, so the position is visible at a glance and the stem threads are outside the process fluid. Standard for steam and refinery service.
Non-rising stem (NRS) : the stem turns in place and the disc travels on it. Used where headroom is limited or the stem must be protected, such as buried water service. Position is not visible, and the threads are in the fluid.
Globe valves in detail
A globe valve forces the flow to make an S-turn through a seat that lies perpendicular to the flow path . The disc moves a short distance to and from that seat, which gives fine, stable control of flow and lets the valve seat tightly even after years of throttling.
The cost is pressure drop . A globe valve of a given size passes far less flow at the same differential than a gate valve, which is why globe valves are sized carefully and why they are not used as block valves on long runs.
Most globe valves are installed so flow enters under the disc . That arrangement keeps pressure off the packing when the valve is closed, so the packing can be serviced with the upstream side still isolated, and it makes the valve easier to open against pressure. Always confirm against the flow arrow cast into the body — installing a globe valve backwards causes the disc to slam and the stem to buckle.
Quarter-turn valves
Ball valves rotate a bored sphere. A full-port ball has a bore equal to the pipe, giving essentially no restriction; a reduced-port ball is one size smaller and cheaper. They give bubble-tight shutoff with soft seats, but the seats limit temperature.
Plug valves rotate a tapered or cylindrical plug. Lubricated plug valves need periodic sealant injection; sleeved plug valves use a PTFE sleeve instead. Multiport plug valves divert flow between two outlets from one body.
Butterfly valves rotate a disc on a shaft through the flow. They are light, short face-to-face, and inexpensive in large sizes. Wafer bodies are sandwiched between flanges; lug bodies have tapped lugs so one side can be removed with the line still in service.
Check valves
Check valves have no operator. Flow opens them; reverse flow and gravity close them.
- Type Closure element Installation constraint
- Swing check Hinged disc Horizontal line, or vertical with upward flow
Lift check Guided disc, like a globe plug Horizontal for horizontal-pattern bodies; vertical for vertical patterns
- Piston check Dashpot-damped disc Reduces slamming in pulsating service
- Dual-plate (wafer) Two spring-loaded half-discs Any orientation; short and light
- Ball check Free ball Viscous and slurry service
Installing a swing check in a downward-flow vertical line is a classic error: gravity holds the disc open and the valve cannot check.
Water hammer on pump shutdown is usually a check valve problem. A slow-closing swing check permits reverse flow to build before it slams; a spring-assisted dual-plate or piston check closes before the column reverses.
Relief and safety valves
The distinction is about the fluid:
A safety valve protects compressible fluid systems — steam, air, gas. It pops to the fully open position at set pressure, because a compressible fluid expands into the huss and needs immediate full capacity.
A relief valve protects incompressible liquid systems. It opens progressively in proportion to the overpressure, because a small liquid discharge relieves the excess.
A safety relief valve is designed to function as either, depending on the application.
Never block, gag, or adjust a set relief device in the field. Set pressure is stamped on the nameplate, and adjustment is a shop function with a documented pop test.