Study guide

5.2 Emergency Relief System Sizing & Two-Phase Flow (DIERS)

NEBOSH HSE Certificate in Process Safety Management Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Process Safety Leadership

1.1 Process Safety vs Personal Safety & Historical Disasters 1.2 Board-Level Leadership & PSLG Principles 1.3 Leading and Lagging Performance Indicators 1.4 Management of Change (MOC) 1.5 Worker Engagement & Competence Management Systems

2 Chapter 2: Risk Management Techniques

2.1 COMAH 2015 Regulations & Regulatory Duties 2.2 Hazard Identification (HAZID) & HAZOP Studies 2.3 Layer of Protection Analysis (LOPA) & Independent Protection Layers (IPLs) 2.4 Bow-Tie Analysis & Risk Assessment Frameworks 2.5 Inherent Safety Principles & CCPS RBPS Framework

3 Chapter 3: Asset Integrity & Safe Systems of Work

3.1 Life-Cycle Asset Integrity & Maintenance Strategies 3.2 Risk-Based Inspection (RBI) & Non-Destructive Testing (NDT) 3.3 Safety-Critical Elements (SCEs) & Performance Standards 3.4 Permit-to-Work (PTW) Systems & High-Risk Controls 3.5 Safe Isolation (HSG253), Shift Handover & Contractor Management

4 Chapter 4: Process Hazard Control

4.1 Safe Operating Envelopes & Transient Operations 4.2 Alarm Management & EEMUA 191 Guidelines 4.3 Safety Instrumented Systems (SIS) & Functional Safety (IEC 61511) 4.4 Utility Failures & Process Support Hazards 4.5 Static Electricity Controls & DSEAR/ATEX Area Classification

5 Chapter 5: Dangerous Substances: Reactions, Storage & Transport

5.1 Exothermic Runaway Reactions & Thermal Safety Screening 5.2 Emergency Relief System Sizing & Two-Phase Flow (DIERS) 5.3 Bulk Storage Tank Design, Overfill Protection & Bunding 5.4 LPG Storage, Refrigeration & BLEVE Prevention 5.5 Drum Storage, CLP Classification & Road Tanker Transfer

6 Chapter 6: Fire & Explosion Protection and Emergency Response

6.1 Fire Mechanics, Flammable Properties & Fire Types 6.2 Vapour Cloud Explosions (VCE) & Congestion/Confinement 6.3 Dust Explosions, Pentagons & Kst Classification 6.4 Explosion Prevention, Relief Venting & Inerting 6.5 Fire Protection Systems, Gas Detection & COMAH Emergency Planning

5.2 Emergency Relief System Sizing & Two-Phase Flow (DIERS)

Key Takeaways Explain This Topic AI

The Design Institute for Emergency Relief Systems (DIERS) established that runaway chemical reactions frequently discharge two-phase (liquid-vapour) mixtures rather than pure single-phase gas or vapour.

Two-phase relief flows require significantly larger vent areas—often 2 to 10 times larger than single-phase vapour vents—to achieve equivalent volumetric pressure relief.

Reaction systems are categorized by DIERS as Vapour (tempered by boiling), Gassy (non-tempered gas generation), or Hybrid (combined non-condensable gas and boiling liquid).

Rupture discs provide zero-leakage, fast-acting isolation for corrosive or toxic media and are commonly installed upstream of safety relief valves with a tell-tale pressure gauge.

Downstream effluent handling systems—such as knock-out drums, quench tanks, and scrubbers—must be designed to separate liquid-vapour mixtures and prevent hazardous atmospheric releases.

Last updated: July 2026

The DIERS Methodology & Historic Context

Prior to the mid-1970s, emergency relief vents on chemical reactors were sized assuming single-phase vapour or gas flow using standard aerodynamic equations (such as API RP 520). However, following major chemical disasters—most notably the Seveso disaster in 1976 in Italy, where a runaway reaction in a 2,4,5-trichlorophenol reactor released toxic dioxins into the atmosphere—the global chemical industry recognised that conventional relief sizing methods were dangerously non-conservative.

In 1976, the American Institute of Chemical Engineers (AIChE) formed the Design Institute for Emergency Relief Systems (DIERS) , a consortium of 29 companies. DIERS research established that when a reactor overpressurises during a thermal runaway, rapid boiling and gas evolution cause foam formation and liquid swell , forcing a two-phase (liquid-vapour/gas) mixture through the relief vent.

Characterisation of Reaction Systems (Vapour vs. Gassy vs. Hybrid)

DIERS classifies runaway reaction systems into three distinct categories based on their thermodynamic behavior during pressure relief: +-----------------------------------+

  • | DIERS System Types |
  • +-----------------------------------+
  • |
  • +--------------------------+--------------------------+
  • | | |
  • v v v
  • +--------------+ +--------------+ +--------------+
  • | Vapour | | Gassy | | Hybrid |
  • | (Tempered) | | (Non-Tempered| | (Combined) |
  • +--------------+ +--------------+ +--------------+
  • | Boiling moderates | Gas evolution | Both non- |
  • | temp; venting cools | drives pressure; | condensable |
  • | the vessel mass. | temp continues rising. | gas & boiling.|
  • +--------------+ +--------------+ +--------------+
  • 1. Vapour Systems (Tempered Systems)

In a vapour system , the reaction mass contains volatile solvents or reactants. As the temperature rises, the liquid reaches its boiling point at the relief set pressure.

Tempering Effect : The latent heat of vaporisation ( Δ H v a p \Delta H_{vap} Δ H v a p ​ ) removes thermal energy from the liquid bulk. Venting vapour extracts mass and heat, effectively arresting further temperature rise once the relief valve opens.

Sizing Basis : Sized based on the latent heat of vaporization required to balance the peak volumetric heat generation rate at maximum allowable overpressure.

2. Gassy Systems (Non-Tempered Systems)

In a gassy system , the runaway reaction decomposes to generate non-condensable gases (e.g., C O 2 CO_2 C O 2 ​ , N 2 N_2 N 2 ​ , O 2 O_2 O 2 ​ ) without significant liquid boiling or vaporisation (e.g., organic peroxide decomposition or acid-catalyzed nitration).

No Latent Cooling : Because non-condensable gas generation does not remove latent heat, venting gas does not cool the liquid mass. The reaction temperature continues to rise even while the vessel is actively venting!

Sizing Basis : Vent sizing must accommodate the maximum volumetric gas generation rate ( d V / d t dV/dt d V / d t ) at the peak reaction temperature.

3. Hybrid Systems (Combined Systems)

A hybrid system exhibits both non-condensable gas generation and boiling volatile liquid. Pressure generation is driven by both gas partial pressure and solvent vapour pressure. These systems require complex adiabatic calorimetry modeling (using ARC or Vent Sizing Package / VSP) to isolate gas evolution rates from vapour pressures.

Two-Phase Flow Hydraulics & Vent Sizing Mechanics

When relief occurs under two-phase flow conditions, liquid droplets or foam are entrained in the expanding vapour stream. Because liquid density ( ρ L \rho_L ρ L ​ ) is orders of magnitude higher than vapour density ( ρ V \rho_V ρ V ​ ), two-phase mixtures exhibit significantly lower volumetric discharge rates per unit area than pure gas.

Hydraulic Flow Model Flow Assumption Application & Characteristics

Homogeneous Equilibrium Model (HEM) Liquid and vapour phases are perfectly mixed, in thermodynamic equilibrium, and travel at identical velocity (no slip). Benchmark model for flashing two-phase flow in DIERS calculations. Highly conservative for non-foamy liquids.

Homogeneous Non-Equilibrium Model (HNEM) Assumes short nozzle length (< 100 mm) prevents phase change equilibrium from completing within the orifice. Used for high-speed liquid jets through thin orifice plates.

Drift-Flux / Slip Models (Coupled Vessel-Vent Sizing) Accounts for relative velocity (slip) between rising gas bubbles and surrounding liquid mass. Differentiates between foamy (homogeneous swell) and non-foamy (churn-turbulent/bubbly) phase separation.

Foamy vs. Non-Foamy Hydrodynamics

Foamy Systems : Minor concentrations of surfactants, polymers, or fine particulates stabilize bubbles, causing uniform volumetric expansion (homogeneous swell). The entire vessel content swells to fill the vapour space, forcing two-phase flow throughout the entire relief event.

Non-Foamy Systems : Bubbles coalesce rapidly and rise through the liquid phase (churn-turbulent regime). If the freeboard vapour space above the liquid level is sufficiently large, disengagement occurs and venting transitions to single-phase vapour after an initial liquid prompt purge. Foamy Swell vs Non-Foamy Disengagement

  • [ Foamy Regime ] [ Non-Foamy Regime ]
  • +----------------+ +----------------+
  • | ~~~~~~~~~~~~~~ | -> Vent | | -> Vapour Vent
  • | O o O o O o O | (Two- | - - - - - - - -| (Disengaged)
  • | o O o O o O o | Phase) | O o O o |
  • | O o O o O o O | |~~~~~~~~~~~~~~~~| Liquid level
  • +----------------+ +----------------+
  • Vent Area Comparison

Because the mass flux ( G G G , k g / m 2 ⋅ s kg/m^2\cdot s k g / m 2 ⋅ s ) of a two-phase mixture is dramatically lower than that of pure vapour, a vent sized for two-phase flow requires an orifice surface area 200% to 1000% (2x to 10x) larger than a single-phase vent for the same reactor volume!

Relief Device Technology: Bursting Discs vs. Safety Relief Valves

Primary emergency pressure relief is achieved using reclosing devices (Safety Relief Valves / SRVs) and non-reclosing devices (Bursting / Rupture Discs). Rupture Disc + Safety Valve Combination

  • |
  • v To Effluent Header / Flare
  • +---------+
  • | SRV | Safety Relief Valve (Reclosing)
  • +---------+
  • |
  • | <-- Tell-Tale Pressure Gauge & Bleed Valve
  • +---------+
  • | DISC | Bursting Disc (Non-Reclosing, Zero Leakage)
  • +---------+
  • |
  • v From Corrosive Reactor Vapour Space

Parameter / Feature Rupture (Bursting) Disc Safety Relief Valve (SRV) Combined Disc + Valve Assembly

Operating Action Non-reclosing (bursts permanently) Reclosing (reseals when pressure drops below blowdown) Dual action: Disc isolates valve; valve reseals after relief event

Leak Tightness Absolute zero leak rate; ideal for toxic/corrosive media Subject to seat leakage, weeping, or particulate damage Zero process emissions under normal operating conditions

Response Speed Extremely fast (< 2 ms); suitable for rapid deflagrations Mechanical inertia (spring/spindle); milliseconds response Fast burst followed by controlled mechanical venting

Maintenance & Testing Destructive device; must be replaced after burst or fatigue limit Can be bench-tested and recalibrated periodically Protects expensive valve internals from process corrosion

Requirements for Combined Assemblies

When a rupture disc is installed upstream of a safety relief valve (to protect the valve from corrosive process fluids):

Tell-Tale Gauge / Excess Pressure Indicator : A pressure gauge, try-cock valve, or pressure transmitter MUST be installed in the interspace between the disc and valve seat.

Interspace Backpressure : Any leakage through the rupture disc creates backpressure in the interspace, increasing the effective burst pressure of the disc dollar-for-dollar and preventing the disc from opening at its design pressure!

Downstream Containment & Effluent Handling Systems

Direct atmospheric discharge of hazardous two-phase relief streams is unacceptable under modern environmental and safety legislation (such as COMAH and DSEAR). Relief headers must route effluent to dedicated treatment systems:

Knock-Out Drums & Liquid-Vapour Separators : Gravity settling vessels designed to reduce vapour velocity below the terminal settling velocity of liquid droplets ( u t u_t u t ​ ), separating liquid bulk from the gas stream.

Quench Tanks & Dump Vessels : Submerged dip-pipe vessel filled with cold water or neutralizing fluid to condense steam/vapour and chemically neutralize acid gases.

Scrubbers & Absorption Towers : Packed towers utilizing counter-current chemical reagents (e.g., sodium hydroxide solution for chlorine or acid gas absorption).

Flare Stacks & Thermal Oxidisers : High-elevation elevated flares with continuous pilot burners to combust flammable hydrocarbon gases safely.