Study guide
2.1 NFPA 70E Approach Boundaries & Arc-Flash
NETA ETT Level II Certified Assistant Technician Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 About the NETA Level 2 Exam 1.2 The NETA Certification Hierarchy & Eligibility 1.3 Exam Administration, Scoring & Scheduling 1.4 Study Plan & How to Use This Guide
2 Chapter 1: Electrical Safety
2.1 NFPA 70E Approach Boundaries & Arc-Flash 2.2 PPE, Rubber Glove Classes & Hearing Protection 2.3 LOTO & the Electrically Safe Work Condition 2.4 Energized Work Permits & Live-Dead-Live 2.5 Temporary Protective Grounds & Induced Voltage 2.6 Hipot Testing Safety & Post-Hipot Grounding 2.7 Confined Space & General Electrical Safety 2.8 Risk Assessment, Job Briefings & the Hierarchy of Risk Controls 2.9 Codes & Standards: NFPA 70 Key Provisions and the ANSI/NETA Specifications
3 Chapter 2: Power Systems Theory
3.1 Three-Phase Power & Wye/Delta Relationships 3.2 Power Factor, Voltage Unbalance & Negative Sequence 3.3 Symmetrical Components & Fault-Current Paths 3.4 Grounding Systems & Impedance Grounding 3.5 Insulation Degradation & Dielectric Theory 3.6 Electrical Calculations, Units & Conversions
4 Chapter 3: Protection & Device Fundamentals
4.1 ANSI Device Numbers (27, 50, 51, 59, 86, 87) 4.2 IDMT/TCC Curves & Coordination 4.3 CT Theory: Ratio, Polarity, Burden, Accuracy & Knee Point 4.4 PT/VT Fundamentals & Insulation Coordination 4.5 Motor Circuits: FLA, PF Correction & Current Imbalance 4.6 One-Lines, Three-Lines, Schematics & Electrical Symbols 4.7 Short-Circuit & Coordination Studies
5 Chapter 4: Insulation Resistance Testing
5.1 Insulation Resistance: Test Voltages & IEEE 43 Minimums 5.2 Polarization Index (PI) & Dielectric Absorption Ratio (DAR) 5.3 Overpotential vs IR & Cable Hipot Basics 5.4 Guard Terminal, Doble Test Set & Thermography
6 Chapter 5: Withstand & Power-Factor Testing
6.1 DC Hipot: Step Voltage, Leakage Current & Pass Criteria 6.2 VLF Cable Testing & the DC/AC Voltage Conversion 6.3 Bushing Power Factor & Transformer PF Configurations 6.4 Oil Dielectric (ASTM) & DGA Sampling 6.5 Cable Fault Locating
7 Chapter 6: Transformer Testing
7.1 Transformer Turns Ratio (TTR) & Acceptance 7.2 Winding Resistance & Transformer Polarity 7.3 Transformer IR Configurations & Neutral-Ground Bond 7.4 SFRA, Sudden-Pressure Relay & Dry-Transformer ATS Tests
8 Chapter 7: CT, Relay & Motor Testing
8.1 CT Ratio, Polarity & Saturation Testing 8.2 Primary vs Secondary Injection & Relay Pickup 8.3 Three-Phase Relay Test Set, Phase-Angle Meter & Induction Disc 8.4 Motor Surge Test & Current Imbalance 8.5 Adjustable-Speed Drives, Reclosers, Sectionalizers & Fiber-Optic Cables
9 Chapter 8: Switchgear & Breaker Testing
9.1 Contact Resistance (Ductor) & Torque Verification 9.2 Vacuum Bottle Integrity & VCB Maintenance Tests 9.3 Post-Fault Breaker Maintenance & LV Trip-Unit Settings 9.4 Switchgear Bus IR, MCC Inspection & Bonding Jumpers 9.5 Switches, Circuit Switchers & Network Protectors 9.6 Metal-Enclosed Busways & Outdoor Bus Structures
10 Chapter 9: Grounding, Batteries & Protective Devices
10.1 Ground-Electrode Testing: Fall-of-Potential & Clamp-On 10.2 Battery Load Test (IEEE 450), VRLA Ohmic & Intervals 10.3 Fuses, GFCI & Zero-Sequence CT Grounding 10.4 Surge Arrester Acceptance & SPD Verification 10.5 Metering Devices & Regulating Apparatus 10.6 Capacitor Banks & Reactors: Inspection, Testing & Acceptance
11 Chapter 10: Systems & Commissioning
11.1 Automatic Transfer Switch Functional Testing 11.2 NFPA 110 Emergency System Load Tests 11.3 Switchgear Functional Testing & Feeder Trip Troubleshooting 11.4 Generator Paralleling & Emergency System Commissioning 11.5 As-Found / As-Left Documentation 11.6 Restoration & Handover Workflow
2.1 NFPA 70E Approach Boundaries & Arc-Flash
Key Takeaways Explain This Topic AI
NFPA 70E defines three shock approach boundaries for AC exposed parts: Limited Approach and Restricted Approach (the legacy Prohibited Approach Boundary was deleted in NFPA 70E-2015)
The arc-flash boundary is the distance from the arc source where incident energy equals 1.2 cal/cm², the threshold for a second-degree burn on bare skin per the Stoll curve
For 15.1-36 kV exposed parts, the Limited Approach Boundary is 10 ft 0 in for movable conductors and 6 ft 0 in for fixed circuit parts per Table 130.4(E)
Two PPE selection methods exist: the Incident Energy Analysis Method (IEEE 1584-2018 calc) and the PPE Category Method (table lookup) — you may use either, but not both on the same equipment
PPE Category minimum arc ratings are Cat 1 = 4, Cat 2 = 8, Cat 3 = 25, Cat 4 = 40 cal/cm²; energized work above 40 cal/cm² is generally prohibited
Last updated: August 2026
The Three Shock Approach Boundaries
NFPA 70E Article 130.4 defines three concentric approach boundaries around exposed energized electrical conductors. From farthest to closest, they are the Limited Approach Boundary and the Restricted Approach Boundary ; the legacy Prohibited Approach Boundary was deleted in the 2015 edition of NFPA 70E. An unqualified person may not cross the Limited Approach Boundary unless escorted by a qualified person; crossing the Restricted Approach Boundary is considered the same as contact and requires energized-work controls (under current NFPA 70E, work inside the Restricted Approach Boundary is treated like touching the energized part; there is no separate Prohibited Boundary).
Distances are tabulated in NFPA 70E Table 130.4(E)(a) for AC and 130.4(E)(b) for DC. The boundary distances increase with system voltage and differ depending on whether the exposed part is a movable conductor (a cable end or jumper that can be repositioned) or a fixed circuit part (a busbar or terminal). For example, in the 15.1-36 kV AC range the Limited Approach Boundary is 10 ft 0 in for exposed movable conductors and 6 ft 0 in for exposed fixed circuit parts, while the Restricted Approach Boundary is much closer (about 2 ft 2 in / 1 ft 8 in respectively). NETA ETT Level 2 candidates must be able to read these tables and recognize that the movable-conductor distance is always the larger of the two because a movable conductor can swing toward the worker.
Trap: The old Prohibited Approach Boundary was removed from the body of NFPA 70E in the 2015 edition and replaced with a note that work within the Restricted Approach Boundary is equivalent to contact. Many older study guides and exam-prep materials still list the three boundaries including Prohibited. For NETA purposes, know both the current terminology and the legacy term, because exam items may reference either.
How Boundaries Are Determined
The shock approach boundaries are fixed by voltage and are looked up in tables — they are not calculated per job. The arc-flash boundary, by contrast, is calculated as the distance from the prospective arc source at which incident energy equals 1.2 cal/cm² (5 J/cm²), the onset threshold for a second-degree burn on bare skin per the Stoll skin burn injury model. The calculation uses the available fault current, the arc clearing time, the system voltage, the equipment geometry, and the working distance. IEEE 1584-2018 is the industry calculation model.
The Arc-Flash Boundary and PPE Selection
Inside the arc-flash boundary, arc-rated PPE is required. NFPA 70E 130.5(F) gives two methods for selecting that PPE — and you may use either, but not both on the same piece of equipment:
Incident Energy Analysis Method — An engineering calculation (typically IEEE 1584-2018) yields the incident energy in cal/cm² at the working distance. The worker then selects arc-rated clothing with a rating at least equal to the calculated incident energy.
PPE Category Method — A table lookup (Tables 130.7(C)(15)(a) and (b)) based on equipment class, maximum available fault current, and maximum clearing time. The table returns a PPE category (1-4) and an arc-flash boundary.
PPE Category Levels (Table 130.7(C)(15)(c))
- PPE Category Minimum Arc Rating (cal/cm²) Typical PPE
- 1 4 Arc-rated shirt/pants or coverall, arc-rated face shield, leather gloves, hearing protection
- 2 8 Arc-rated shirt/pants or coverall, arc-rated face shield and balaclava (or hood), leather gloves
3 25 Multi-layer arc flash suit (jacket + pants), arc flash suit hood, arc-rated or rubber insulating gloves with protectors
4 40 Full multi-layer arc flash suit, arc flash suit hood, rubber insulating gloves with protectors
Work above 40 cal/cm² is generally prohibited — no PPE is considered adequate, and the task must be done de-energized.
Terminology note: Current NFPA 70E uses "PPE category" (sometimes abbreviated "Cat"). Older editions called this the "hazard/risk category" or "HRC." The numeric ratings (4/8/25/40) have not changed, but the label has. Expect exam items that use either label.
Why This Matters for NETA Technicians
NETA testing frequently involves energized equipment above 480 V — switchgear, medium-voltage cable, transformers — where approach boundaries and arc-flash exposure drive the entire work plan. The technician must know which boundary governs the task, which method (category or incident energy) the company's engineering study used, and which category of PPE to don. A common field error is to use the Limited Approach distance as the arc-flash boundary — they are independent quantities determined by different methods.
Reading the Tables in the Field
In practice, the NETA technician carries a copy of the NFPA 70E tables (or a company-issued summary) and reads them at the job site. The lookup sequence is: (1) identify the system voltage, (2) identify whether the exposed part is movable or fixed, (3) read the Limited and Restricted Approach Boundaries from Table 130.4(E), (4) determine the arc-flash boundary from the engineering study or from Table 130.7(C)(15)(a) if using the PPE Category Method, and (5) select PPE with an arc rating at least equal to the category minimum or the calculated incident energy. When the available fault current or clearing time exceeds the table limits, the PPE Category Method cannot be used and an incident energy analysis is required. NETA exam items commonly test the threshold voltage (750 V) above which the Prohibited approach concept applies and the 1.2 cal/cm² arc-flash boundary definition.