Study guide

3.4 Grounding Systems & Impedance Grounding

NETA ETT Level II Certified Assistant Technician Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 About the NETA Level 2 Exam 1.2 The NETA Certification Hierarchy & Eligibility 1.3 Exam Administration, Scoring & Scheduling 1.4 Study Plan & How to Use This Guide

2 Chapter 1: Electrical Safety

2.1 NFPA 70E Approach Boundaries & Arc-Flash 2.2 PPE, Rubber Glove Classes & Hearing Protection 2.3 LOTO & the Electrically Safe Work Condition 2.4 Energized Work Permits & Live-Dead-Live 2.5 Temporary Protective Grounds & Induced Voltage 2.6 Hipot Testing Safety & Post-Hipot Grounding 2.7 Confined Space & General Electrical Safety 2.8 Risk Assessment, Job Briefings & the Hierarchy of Risk Controls 2.9 Codes & Standards: NFPA 70 Key Provisions and the ANSI/NETA Specifications

3 Chapter 2: Power Systems Theory

3.1 Three-Phase Power & Wye/Delta Relationships 3.2 Power Factor, Voltage Unbalance & Negative Sequence 3.3 Symmetrical Components & Fault-Current Paths 3.4 Grounding Systems & Impedance Grounding 3.5 Insulation Degradation & Dielectric Theory 3.6 Electrical Calculations, Units & Conversions

4 Chapter 3: Protection & Device Fundamentals

4.1 ANSI Device Numbers (27, 50, 51, 59, 86, 87) 4.2 IDMT/TCC Curves & Coordination 4.3 CT Theory: Ratio, Polarity, Burden, Accuracy & Knee Point 4.4 PT/VT Fundamentals & Insulation Coordination 4.5 Motor Circuits: FLA, PF Correction & Current Imbalance 4.6 One-Lines, Three-Lines, Schematics & Electrical Symbols 4.7 Short-Circuit & Coordination Studies

5 Chapter 4: Insulation Resistance Testing

5.1 Insulation Resistance: Test Voltages & IEEE 43 Minimums 5.2 Polarization Index (PI) & Dielectric Absorption Ratio (DAR) 5.3 Overpotential vs IR & Cable Hipot Basics 5.4 Guard Terminal, Doble Test Set & Thermography

6 Chapter 5: Withstand & Power-Factor Testing

6.1 DC Hipot: Step Voltage, Leakage Current & Pass Criteria 6.2 VLF Cable Testing & the DC/AC Voltage Conversion 6.3 Bushing Power Factor & Transformer PF Configurations 6.4 Oil Dielectric (ASTM) & DGA Sampling 6.5 Cable Fault Locating

7 Chapter 6: Transformer Testing

7.1 Transformer Turns Ratio (TTR) & Acceptance 7.2 Winding Resistance & Transformer Polarity 7.3 Transformer IR Configurations & Neutral-Ground Bond 7.4 SFRA, Sudden-Pressure Relay & Dry-Transformer ATS Tests

8 Chapter 7: CT, Relay & Motor Testing

8.1 CT Ratio, Polarity & Saturation Testing 8.2 Primary vs Secondary Injection & Relay Pickup 8.3 Three-Phase Relay Test Set, Phase-Angle Meter & Induction Disc 8.4 Motor Surge Test & Current Imbalance 8.5 Adjustable-Speed Drives, Reclosers, Sectionalizers & Fiber-Optic Cables

9 Chapter 8: Switchgear & Breaker Testing

9.1 Contact Resistance (Ductor) & Torque Verification 9.2 Vacuum Bottle Integrity & VCB Maintenance Tests 9.3 Post-Fault Breaker Maintenance & LV Trip-Unit Settings 9.4 Switchgear Bus IR, MCC Inspection & Bonding Jumpers 9.5 Switches, Circuit Switchers & Network Protectors 9.6 Metal-Enclosed Busways & Outdoor Bus Structures

10 Chapter 9: Grounding, Batteries & Protective Devices

10.1 Ground-Electrode Testing: Fall-of-Potential & Clamp-On 10.2 Battery Load Test (IEEE 450), VRLA Ohmic & Intervals 10.3 Fuses, GFCI & Zero-Sequence CT Grounding 10.4 Surge Arrester Acceptance & SPD Verification 10.5 Metering Devices & Regulating Apparatus 10.6 Capacitor Banks & Reactors: Inspection, Testing & Acceptance

11 Chapter 10: Systems & Commissioning

11.1 Automatic Transfer Switch Functional Testing 11.2 NFPA 110 Emergency System Load Tests 11.3 Switchgear Functional Testing & Feeder Trip Troubleshooting 11.4 Generator Paralleling & Emergency System Commissioning 11.5 As-Found / As-Left Documentation 11.6 Restoration & Handover Workflow

3.4 Grounding Systems & Impedance Grounding

Key Takeaways Explain This Topic AI

Grounded vs. grounding: the 'grounded conductor' is the current-carrying neutral bonded to ground at the service; the 'grounding conductor' (EGC) bonds non-current-carrying metal parts and carries fault current only during a fault.

System grounding types: solid, low-resistance, high-resistance, reactance, and ungrounded — each trades fault-current magnitude against service continuity and equipment damage.

High-resistance grounding limits ground-fault current to about 5-10 A (alarm, do not trip); low-resistance grounding limits it to roughly 200-400 A (trip selectively).

The equipment grounding conductor (EGC) provides the low-impedance metallic return path that lets overcurrent devices clear a ground fault quickly.

Never open the secondary of an energized current transformer — the developing high voltage can break down insulation and injure personnel; short the secondary first if a burden must be removed.

Last updated: August 2026

Grounded vs. Grounding: The NEC Distinction

Quick Answer: The grounded conductor is the current-carrying conductor bonded to ground at the service (usually the neutral). The grounding conductor (equipment grounding conductor, EGC) bonds non-current-carrying metal parts together and to ground; it carries current only during a fault.

NEC Article 100 and 250 make this distinction because the two conductors serve different purposes:

Grounded conductor: carries normal load current (unbalanced neutral current in a 3φ 4-wire system) and is bonded to the grounding electrode system at the service disconnect (main bonding jumper). It is a current-carrying conductor that happens to be grounded.

Equipment grounding conductor (EGC): bonds equipment enclosures, raceways, and cable trays together and to the system grounding point. It carries fault current only when a phase-to-ground fault occurs, and its low impedance is what allows the overcurrent device to trip quickly.

On a 480Y/277 V service, the neutral is the grounded conductor; the green/bare bond wire in the conduit is the EGC. Mixing these up on the exam is a guaranteed wrong answer.

System Grounding Types

  • Type Ground-Fault Current Typical Use Action on First Ground Fault
  • Solid High (full available fault) Commercial/industrial services, 480Y/277, 208Y/120 Trip immediately
  • Low-resistance ~200-400 A Medium-voltage industrial (4.16 kV, 13.8 kV) Trip selectively
  • High-resistance ~5-10 A Critical continuous-process plants, generators Alarm, do not trip
  • Reactance Limited (reactor in neutral) Large generators, utilities Trip or alarm

Ungrounded ~0 (capacitive charging only) Old installations, high continuity needs Alarm; locate before second fault

Why Limit Ground-Fault Current?

A solidly grounded 13.8 kV system can deliver 20,000+ A into a ground fault. That current does three damaging things:

Arc burn at the fault point: melts cable, switches, and bus at the arc location.

Mechanical stress on the equipment: the magnetic forces from high fault current can deform bus bars and damage transformer windings.

Thermal damage to the neutral resistor/reactor and winding: sustained ground-fault current overheats the iron and copper.

Impedance grounding inserts a resistor or reactor between the transformer neutral and ground so the ground-fault current is predictable and limited. Industrial 4.16 kV and 13.8 kV systems often use low-resistance grounding (~400 A) to allow selective relaying while reducing damage. High-resistance grounding (~5-10 A) is used where continuity of service is critical (refineries, hospitals, data centers) — the system alarms, the operator locates the fault, and the process keeps running until a planned shutdown.

The Ground-Fault Current Path and the EGC

On a solidly grounded system, a ground fault on a piece of equipment sends current from the source, through the phase conductor, through the fault to the equipment enclosure, through the EGC back to the service neutral-ground bond, and through the grounded neutral to the source. The EGC's impedance determines how much current flows and how fast the breaker trips. A high-impedance EGC (loose connection, undersized wire, corroded bond) means low fault current and a slow (or no) trip — exactly the condition that starts fires and shocks workers. This is why NETA testing includes the ground-fault circuit impedance test and visual inspection of bonding and grounding connections.

Ground-Fault Detection

Three common detection schemes:

Residual (wye-connected CTs): the three phase CT secondaries are summed. In a balanced system the sum is zero; a ground fault produces residual current. Simple and common on 51N/50G relays.

Zero-sequence (core-balance) CT: all three phase conductors (and the neutral if present) pass through one CT. Any imbalance indicates ground-fault current. Sensitive — used for GFPE and high-resistance grounded system alarms.

Neutral CT or shunt: a CT on the neutral-to-ground bond directly measures ground-fault current. Used on resistance-grounded systems where the fault current returns through the resistor.

On a high-resistance grounded system the neutral resistor is sized so the available ground-fault current equals or slightly exceeds the system's total charging current (so the zero-sequence capacitive current is canceled and the alarm is meaningful). A 13.8 kV system with 15 A charging current might use a 15-20 A neutral resistor.

The Open-CT Hazard Rule (Critical Safety)

A current transformer is a constant-current source (within its accuracy range) on the secondary side. The secondary current is fixed by the primary current and the turns ratio: Isec = Iprim / N. The voltage developed across the secondary is Vsec = Isec × Zburden. If you remove the burden (open the secondary), Zburden approaches infinity and Vsec rises until the core saturates — but saturation still leaves a high, dangerous peak voltage that can:

Break down the CT's secondary insulation.

Produce a lethal shock hazard at the open terminals.

Drive the CT into saturation that ruins its accuracy until demagnetized.

Rule: never open the secondary of an energized CT. If you must remove a relay or meter, short the CT secondary first with a CT shorting block or jumper, then disconnect the burden. Many test sets and switchgear CT terminal blocks include built-in shorting bars that engage before the burden lifts. NETA field work routinely involves isolating CTs for injection testing — the shorting sequence is non-negotiable and a frequent exam question.

The same rule does not apply to potential transformers (PTs) — a PT secondary can be opened (like any voltage source) but must never be shorted, and PT secondaries should be fused and grounded.

Exam Trap

A common trap confuses 'solidly grounded' with 'low-impedance grounded.' Solid grounding means the neutral is bonded to ground with no intentional impedance — the fault current is limited only by the source and transformer impedances. Low-resistance and high-resistance grounding add a deliberate resistor in the neutral. If a question says 'resistance-grounded,' do not treat it as solidly grounded for fault calculations — the resistor dominates Z0.