Study guide
4.3 CT Theory: Ratio, Polarity, Burden, Accuracy & Knee Point
NETA ETT Level II Certified Assistant Technician Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 About the NETA Level 2 Exam 1.2 The NETA Certification Hierarchy & Eligibility 1.3 Exam Administration, Scoring & Scheduling 1.4 Study Plan & How to Use This Guide
2 Chapter 1: Electrical Safety
2.1 NFPA 70E Approach Boundaries & Arc-Flash 2.2 PPE, Rubber Glove Classes & Hearing Protection 2.3 LOTO & the Electrically Safe Work Condition 2.4 Energized Work Permits & Live-Dead-Live 2.5 Temporary Protective Grounds & Induced Voltage 2.6 Hipot Testing Safety & Post-Hipot Grounding 2.7 Confined Space & General Electrical Safety 2.8 Risk Assessment, Job Briefings & the Hierarchy of Risk Controls 2.9 Codes & Standards: NFPA 70 Key Provisions and the ANSI/NETA Specifications
3 Chapter 2: Power Systems Theory
3.1 Three-Phase Power & Wye/Delta Relationships 3.2 Power Factor, Voltage Unbalance & Negative Sequence 3.3 Symmetrical Components & Fault-Current Paths 3.4 Grounding Systems & Impedance Grounding 3.5 Insulation Degradation & Dielectric Theory 3.6 Electrical Calculations, Units & Conversions
4 Chapter 3: Protection & Device Fundamentals
4.1 ANSI Device Numbers (27, 50, 51, 59, 86, 87) 4.2 IDMT/TCC Curves & Coordination 4.3 CT Theory: Ratio, Polarity, Burden, Accuracy & Knee Point 4.4 PT/VT Fundamentals & Insulation Coordination 4.5 Motor Circuits: FLA, PF Correction & Current Imbalance 4.6 One-Lines, Three-Lines, Schematics & Electrical Symbols 4.7 Short-Circuit & Coordination Studies
5 Chapter 4: Insulation Resistance Testing
5.1 Insulation Resistance: Test Voltages & IEEE 43 Minimums 5.2 Polarization Index (PI) & Dielectric Absorption Ratio (DAR) 5.3 Overpotential vs IR & Cable Hipot Basics 5.4 Guard Terminal, Doble Test Set & Thermography
6 Chapter 5: Withstand & Power-Factor Testing
6.1 DC Hipot: Step Voltage, Leakage Current & Pass Criteria 6.2 VLF Cable Testing & the DC/AC Voltage Conversion 6.3 Bushing Power Factor & Transformer PF Configurations 6.4 Oil Dielectric (ASTM) & DGA Sampling 6.5 Cable Fault Locating
7 Chapter 6: Transformer Testing
7.1 Transformer Turns Ratio (TTR) & Acceptance 7.2 Winding Resistance & Transformer Polarity 7.3 Transformer IR Configurations & Neutral-Ground Bond 7.4 SFRA, Sudden-Pressure Relay & Dry-Transformer ATS Tests
8 Chapter 7: CT, Relay & Motor Testing
8.1 CT Ratio, Polarity & Saturation Testing 8.2 Primary vs Secondary Injection & Relay Pickup 8.3 Three-Phase Relay Test Set, Phase-Angle Meter & Induction Disc 8.4 Motor Surge Test & Current Imbalance 8.5 Adjustable-Speed Drives, Reclosers, Sectionalizers & Fiber-Optic Cables
9 Chapter 8: Switchgear & Breaker Testing
9.1 Contact Resistance (Ductor) & Torque Verification 9.2 Vacuum Bottle Integrity & VCB Maintenance Tests 9.3 Post-Fault Breaker Maintenance & LV Trip-Unit Settings 9.4 Switchgear Bus IR, MCC Inspection & Bonding Jumpers 9.5 Switches, Circuit Switchers & Network Protectors 9.6 Metal-Enclosed Busways & Outdoor Bus Structures
10 Chapter 9: Grounding, Batteries & Protective Devices
10.1 Ground-Electrode Testing: Fall-of-Potential & Clamp-On 10.2 Battery Load Test (IEEE 450), VRLA Ohmic & Intervals 10.3 Fuses, GFCI & Zero-Sequence CT Grounding 10.4 Surge Arrester Acceptance & SPD Verification 10.5 Metering Devices & Regulating Apparatus 10.6 Capacitor Banks & Reactors: Inspection, Testing & Acceptance
11 Chapter 10: Systems & Commissioning
11.1 Automatic Transfer Switch Functional Testing 11.2 NFPA 110 Emergency System Load Tests 11.3 Switchgear Functional Testing & Feeder Trip Troubleshooting 11.4 Generator Paralleling & Emergency System Commissioning 11.5 As-Found / As-Left Documentation 11.6 Restoration & Handover Workflow
4.3 CT Theory: Ratio, Polarity, Burden, Accuracy & Knee Point
Key Takeaways Explain This Topic AI
A CT steps primary current down to a standardized secondary (1 A or 5 A); IEEE C57.13 standard burdens are based on a 5 A secondary, while 1 A secondaries (IEC practice) can drive 25x the burden impedance for the same C-rating.
CT polarity (H1/X1) tells you which way secondary current flows for a given primary direction; wrong polarity makes a differential (87) relay trip on through-faults and a directional (67) relay operate the wrong way.
CT burden is the total secondary impedance (relay/meter + lead resistance + CT winding resistance); exceeding rated burden drives the CT into saturation and produces ratio error.
IEEE C57.13 relaying class C200/C400 means the CT delivers 200 V / 400 V to its standard burden at 20x rated secondary current with under 10% ratio error; IEC 10P20 means composite error stays under 10% up to 20x rated current.
Never open the secondary of an energized CT — the open circuit forces the core to drive all magnetizing current through the open point, producing dangerously high voltage and risking insulation failure and arc flash.
Last updated: August 2026
CT Ratio and the 1 A vs. 5 A Secondary
Quick Answer: A current transformer (CT) has a nameplate ratio such as 600:5 — at 600 A primary, 5 A flows in the secondary. The standardized secondary ratings are 5 A (most common in North American IEEE practice) and 1 A (common in IEC practice).
A 600:5 CT has a turns ratio of 120:1. At any primary current Ip, the ideal secondary current Is = Ip / 120. Real CTs have ratio error (the measured secondary is slightly less than ideal) and phase angle error, both of which increase as the CT approaches saturation.
The choice of 1 A or 5 A secondary is a burden decision. The CT must develop terminal voltage V = Is x Z_burden. For the same C-rating, a 1 A secondary drives 25x the impedance of a 5 A secondary at the same terminal voltage, because the current is 5x lower and voltage = I x Z. That is why long cable runs from outdoor switchyard CTs to the relay room often use 1 A secondaries — the lead resistance is a smaller fraction of total burden.
CT Polarity (X1/H1) and Why It Matters for 87
Every CT has polarity marks, typically H1 on the primary and X1 on the secondary. When primary current enters H1, secondary current leaves X1 (and returns through X2). In schematics, the polarity mark is the dot.
Polarity matters because protective relays compare current direction . The two places it is most critical:
Differential (87) schemes. Currents entering and leaving a protected zone are summed. If both zone-boundary CTs have correct polarity, a through-fault produces near-zero differential current. If one CT is reversed, the secondary currents add instead of subtract, and the 87 trips on a perfectly healthy through-fault — a commissioning failure that an injection test catches before energization.
Directional (67) relays. A polarizing quantity (usually voltage or a polarizing CT) is compared with the operate current. Reversed polarity makes the relay declare forward faults as reverse (and vice versa), so it never trips for the fault it is supposed to clear.
Field polarity is verified with a DC kick test (battery, momentary contact, and a DC analog ammeter deflecting in the expected direction) or a commercial polarity tester. Always record the polarity result on the acceptance test sheet.
CT Burden and How Over-Burden Drives Saturation
Burden is the total impedance connected to the CT secondary, expressed in ohms (or VA at rated current). It is the sum of:
- Relay/meter input impedance (often 0.1 to 1.0 ohm per device)
- Lead resistance (round-trip cable from CT to relay and back — a common culprit on long runs)
- CT secondary winding resistance (Rct, internal)
The CT must develop terminal voltage V = Is x Z_burden. If the burden is too high, the CT cannot develop that voltage without saturating its core, the secondary waveform distorts, and both ratio error and phase error grow. A saturated CT is the most common cause of relay misoperation during heavy through-faults.
Rule of thumb: keep actual burden under the rated burden for the accuracy class. For an IEEE C400 CT (rated at B-4.0, which is 4.0 ohm), the secondary circuit should measure well under 4.0 ohm, leaving margin for lead aging and added devices.
CT Accuracy Class: C200, C400, and 10P20
IEEE C57.13 relaying accuracy classes use a letter plus a voltage number:
- Class letter Meaning
- C Ratio can be calculated (low leakage flux; bushing/window/bar CTs)
- T Ratio must be determined by test (leakage flux appreciable; wound CTs)
- X User-defined: specifies knee voltage Ek, exciting current Ik, and Rct
The number after the letter is the secondary terminal voltage the CT can deliver to a standard burden at 20x rated secondary current with ratio error under 10%.
- Class Terminal voltage Standard burden VA at 5 A
- C100 100 V B-1.0 (1.0 ohm) 25 VA
- C200 200 V B-2.0 (2.0 ohm) 50 VA
- C400 400 V B-4.0 (4.0 ohm) 100 VA
- C800 800 V B-8.0 (8.0 ohm) 200 VA
So a C400 CT can deliver 400 V to a 4.0 ohm burden at 100 A secondary (20 x 5 A) while keeping ratio error under 10%. All C-class CTs are defined at 20x rated current — that 20 is the IEEE standard accuracy limit factor.
The IEC equivalent is the 10P20 class: 10 = maximum composite error (10%), P = protection class, 20 = accuracy limit factor (the CT holds 10% error up to 20x rated primary current at rated burden). A 5P20 is the same but with 5% composite error. IEC and IEEE ratings are not directly interchangeable, but both describe how the CT behaves under heavy fault current.
CT Knee Point
The knee point is the bend in the CT excitation (saturation) curve where the core begins to saturate. Definitions:
IEC 60044 / IEC 61869: the point where a 10% increase in excitation voltage produces a 50% increase in excitation current .
IEEE C57.13: the point where a 10% increase in voltage produces a 50% increase in current — historically the same definition; IEEE also uses a 45-degree tangent line on the log-log excitation curve.
The saturation curve is developed by applying variable AC voltage to the secondary with the primary open-circuited , plotting excitation current versus excitation voltage. The knee voltage must meet or exceed the manufacturer's data, and for a protective CT it must be at least high enough that the CT does not saturate at the maximum fault current and burden.
The Open-CT Hazard (Critical Safety Rule)
Never open the secondary of an energized CT. With the secondary shorted or connected to its low-impedance burden, the CT operates happily — primary ampere-turns are balanced by secondary ampere-turns, and the core flux stays low. If the secondary is opened, the secondary current cannot flow, so there is nothing to oppose the primary ampere-turns. The core is driven hard into saturation every half-cycle, and the open secondary voltage spikes to thousands of volts — enough to break down CT insulation, arc across terminal boards, and cause severe injury.
The field rule is absolute: before disconnecting any CT secondary lead, either de-energize the primary or short the CT secondary at a terminal block with a CT shorting block. Modern CT test switches are designed so the CT is automatically shorted before the test plug removes the relay from the circuit.