6.5 Cable Fault Locating

NETA ETT Level II Certified Assistant Technician Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 About the NETA Level 2 Exam 1.2 The NETA Certification Hierarchy & Eligibility 1.3 Exam Administration, Scoring & Scheduling 1.4 Study Plan & How to Use This Guide

2 Chapter 1: Electrical Safety

2.1 NFPA 70E Approach Boundaries & Arc-Flash 2.2 PPE, Rubber Glove Classes & Hearing Protection 2.3 LOTO & the Electrically Safe Work Condition 2.4 Energized Work Permits & Live-Dead-Live 2.5 Temporary Protective Grounds & Induced Voltage 2.6 Hipot Testing Safety & Post-Hipot Grounding 2.7 Confined Space & General Electrical Safety 2.8 Risk Assessment, Job Briefings & the Hierarchy of Risk Controls 2.9 Codes & Standards: NFPA 70 Key Provisions and the ANSI/NETA Specifications

3 Chapter 2: Power Systems Theory

3.1 Three-Phase Power & Wye/Delta Relationships 3.2 Power Factor, Voltage Unbalance & Negative Sequence 3.3 Symmetrical Components & Fault-Current Paths 3.4 Grounding Systems & Impedance Grounding 3.5 Insulation Degradation & Dielectric Theory 3.6 Electrical Calculations, Units & Conversions

4 Chapter 3: Protection & Device Fundamentals

4.1 ANSI Device Numbers (27, 50, 51, 59, 86, 87) 4.2 IDMT/TCC Curves & Coordination 4.3 CT Theory: Ratio, Polarity, Burden, Accuracy & Knee Point 4.4 PT/VT Fundamentals & Insulation Coordination 4.5 Motor Circuits: FLA, PF Correction & Current Imbalance 4.6 One-Lines, Three-Lines, Schematics & Electrical Symbols 4.7 Short-Circuit & Coordination Studies

5 Chapter 4: Insulation Resistance Testing

5.1 Insulation Resistance: Test Voltages & IEEE 43 Minimums 5.2 Polarization Index (PI) & Dielectric Absorption Ratio (DAR) 5.3 Overpotential vs IR & Cable Hipot Basics 5.4 Guard Terminal, Doble Test Set & Thermography

6 Chapter 5: Withstand & Power-Factor Testing

6.1 DC Hipot: Step Voltage, Leakage Current & Pass Criteria 6.2 VLF Cable Testing & the DC/AC Voltage Conversion 6.3 Bushing Power Factor & Transformer PF Configurations 6.4 Oil Dielectric (ASTM) & DGA Sampling 6.5 Cable Fault Locating

7 Chapter 6: Transformer Testing

7.1 Transformer Turns Ratio (TTR) & Acceptance 7.2 Winding Resistance & Transformer Polarity 7.3 Transformer IR Configurations & Neutral-Ground Bond 7.4 SFRA, Sudden-Pressure Relay & Dry-Transformer ATS Tests

8 Chapter 7: CT, Relay & Motor Testing

8.1 CT Ratio, Polarity & Saturation Testing 8.2 Primary vs Secondary Injection & Relay Pickup 8.3 Three-Phase Relay Test Set, Phase-Angle Meter & Induction Disc 8.4 Motor Surge Test & Current Imbalance 8.5 Adjustable-Speed Drives, Reclosers, Sectionalizers & Fiber-Optic Cables

9 Chapter 8: Switchgear & Breaker Testing

9.1 Contact Resistance (Ductor) & Torque Verification 9.2 Vacuum Bottle Integrity & VCB Maintenance Tests 9.3 Post-Fault Breaker Maintenance & LV Trip-Unit Settings 9.4 Switchgear Bus IR, MCC Inspection & Bonding Jumpers 9.5 Switches, Circuit Switchers & Network Protectors 9.6 Metal-Enclosed Busways & Outdoor Bus Structures

10 Chapter 9: Grounding, Batteries & Protective Devices

10.1 Ground-Electrode Testing: Fall-of-Potential & Clamp-On 10.2 Battery Load Test (IEEE 450), VRLA Ohmic & Intervals 10.3 Fuses, GFCI & Zero-Sequence CT Grounding 10.4 Surge Arrester Acceptance & SPD Verification 10.5 Metering Devices & Regulating Apparatus 10.6 Capacitor Banks & Reactors: Inspection, Testing & Acceptance

11 Chapter 10: Systems & Commissioning

11.1 Automatic Transfer Switch Functional Testing 11.2 NFPA 110 Emergency System Load Tests 11.3 Switchgear Functional Testing & Feeder Trip Troubleshooting 11.4 Generator Paralleling & Emergency System Commissioning 11.5 As-Found / As-Left Documentation 11.6 Restoration & Handover Workflow

6.5 Cable Fault Locating

Key Takeaways Explain This Topic AI

Cable fault locating is a two-stage process: prelocation narrows the fault to a distance along the cable, then pinpointing finds it within a few feet at the surface.

A low-voltage TDR finds opens, splices, and low-resistance faults, but a high-resistance fault is invisible to it until a surge creates a temporary arc.

Arc reflection combines a surge generator with a TDR so the momentary arc appears as a low-impedance reflection on the trace, which is the standard method for high-resistance faults.

Distance from a TDR trace depends on the cable's velocity of propagation, so using the wrong VOP scales every measured distance by the same error.

Sheath and jacket faults are located with a DC voltage applied to the sheath and an A-frame earth-gradient receiver, not with a TDR.

Last updated: August 2026

Why Fault Locating Is Its Own Skill

A megger tells you a cable is bad. It does not tell you where . On a 2,400 ft medium-voltage feeder in duct bank, the difference between knowing the fault is at 340 ft and not knowing is the difference between one excavation and twelve. The Level 2 DCO lists cable fault locating as an explicit knowledge item under Cables, and the exam tests method selection rather than instrument operation.

The workflow is always the same four steps:

Isolate, verify dead, and ground both ends. Discharge the cable and keep it grounded until you are ready to test.

Characterize the fault — is it open, low resistance, high resistance, or a sheath fault? An insulation resistance test and a continuity check answer this in two minutes.

Prelocate — find the distance to the fault from one end.

Pinpoint — walk the route and find the fault at the surface within a few feet.

Step 2: Characterizing the Fault

  • Test result Fault type Prelocation method that works
  • Conductor continuity open Open circuit / broken conductor TDR (low voltage)

Very low IR, low resistance to ground or between phases Low-resistance (bolted) fault TDR, or resistance bridge

IR low but not zero, or IR normal until voltage is applied High-resistance / flashover fault Arc reflection, surge pulse reflection, or decay

Conductor good, jacket/sheath resistance to earth low Sheath or jacket fault DC voltage plus A-frame earth gradient

The distinction the exam cares about: a high-resistance fault is invisible to a low-voltage TDR. The fault only conducts when enough voltage is applied to break down the gap, so a 20 V TDR pulse passes straight by it and reflects off the far end. Technicians who do not understand this conclude the cable is healthy.

  • Prelocation Methods
  • Time Domain Reflectometry (TDR)

A TDR launches a low-voltage pulse down the cable and displays the reflections. Impedance changes send energy back:

An open reflects a positive (upward) pulse.

A short or low-resistance fault reflects a negative (downward) pulse.

Splices, joints, and taps produce small reflections that are useful landmarks — comparing an as-found trace against a commissioning baseline trace is the fastest way to spot what changed.

Distance comes from the round-trip time and the cable's velocity of propagation (VOP) , usually expressed as a fraction of the speed of light or as a velocity factor. Because the pulse travels out and back: distance = (velocity x round-trip time) / 2

VOP is a property of the insulation. Typical XLPE and EPR power cable runs near 0.5 to 0.56 of the speed of light; paper-insulated lead-covered cable is lower. If you enter the wrong VOP, every distance the instrument reports is wrong by the same percentage. Setting VOP for XLPE and testing a PILC cable can put you 15% off — 60 feet on a 400 ft run. Where a cable of known length is available, calibrate by shooting the open far end and adjusting VOP until the trace reads the true length.

Arc Reflection (ARM)

The workhorse for high-resistance faults. A surge generator (thumper) and a TDR are connected through a filter. The surge breaks down the fault into a temporary arc; the arc is a near short circuit; the TDR — triggered during the arc — sees a clear negative reflection at the fault. The filter protects the TDR from the surge energy. Its advantage over plain thumping is that you get a distance before you start walking, and you can compare the pre-arc and during-arc traces overlaid, which makes the fault unmistakable.

Surge Pulse Reflection (ICE / Impulse Current)

Used when the fault will not hold an arc long enough for arc reflection, or where the fault is at very high resistance. A high-energy surge is applied and the current transient is captured; the fault distance is read from the period of the traveling-wave oscillation. It is more interpretive than arc reflection but works on faults that ARM cannot capture.

Decay (Voltage Decay) Method

For flashover faults that only break down above a voltage the surge generator cannot sustain — typical of faults in joints on long cables with high capacitance. The cable is charged with a DC source until the fault flashes over; the resulting traveling wave is captured and the distance derived from its period. Used with a hipot rather than a thumper.

Bridge Methods (Murray and Wheatstone Loop)

The oldest prelocation technique. The faulted conductor is looped at the far end to a healthy conductor of the same size, and a resistance bridge measures the ratio of the two legs. Fault distance is proportional to that ratio times the total loop length. Requirements and limits worth knowing:

Needs a healthy return conductor of the same size and length — which is why it suits multi-conductor cable and fails on a single-conductor run.

Works on low-resistance faults; a high-resistance fault must first be burned down.

Extremely accurate when its conditions are met, and it needs no expensive instrument.

Pinpointing Methods

Prelocation gets you to a stretch of route. Pinpointing puts you on the spot.

Acoustic (thumping). The surge generator repeatedly discharges into the fault, producing an audible thump. An acoustic-magnetic receiver listens for the sound and simultaneously senses the magnetic pulse; because the magnetic field arrives essentially instantly and the sound travels at roughly 1,100 ft/s, the time difference between the magnetic and acoustic signals shrinks to zero as you stand over the fault . This is the standard pinpointing method on direct-buried and duct cable.

Earth gradient / A-frame. For sheath and jacket faults , a DC voltage is applied between the sheath and earth, and an A-frame with two ground probes measures the voltage gradient in the soil. The needle deflects toward the fault and reverses when you pass over it. A TDR cannot find a jacket fault — the conductor insulation is intact.

Route tracing. Before pinpointing, trace and mark the cable route with a transmitter and receiver so your measured distance follows the actual path. Distance along a cable is not distance across a parking lot; slack in vaults and route bends routinely add 5-10%.

Safety Rules for Thumping

Surge generators store lethal energy and put high voltage on a cable that people may assume is dead.

Ground and short both ends before and after every test, and discharge through a resistive stick before touching a conductor. A long cable stores enough capacitive charge to kill after the source is removed.

Guard the far end. The remote termination must be secured and attended or physically isolated; the surge appears there too.

Limit energy and duration. Every thump degrades cable insulation and can extend a fault or damage sound insulation elsewhere. Use the lowest energy setting that produces a usable signal, prelocate before you thump so you thump for minutes rather than hours, and stop when you have the location.

Never thump a cable with an unknown or attached load. Disconnect terminations, potheads, and any connected apparatus — transformers, arresters, and PTs will not survive surge energy and will also mask the fault.

Method Selection Summary

  • Fault Prelocate with Pinpoint with
  • Open conductor TDR Route trace and TDR distance
  • Low-resistance fault TDR or bridge Acoustic thump
  • High-resistance fault Arc reflection Acoustic thump
  • Flashover only at high voltage Decay method Acoustic thump
  • Sheath / jacket fault Sheath integrity test A-frame earth gradient