4.7 Fuses, Medium-Voltage Switches, and Disconnecting Devices

NICET Electrical Power Testing Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Electrical Safety, Standards, and Work Practices (NFPA 70E & OSHA)

1.1 NFPA 70E Framework, Electrically Safe Work Conditions, and Approach Boundaries 1.2 Arc Flash Hazard Analysis, Incident Energy, and PPE Category Selection 1.3 Hazardous Energy Control: OSHA 1910.147 Lockout/Tagout & Grounding Procedures 1.4 Confined Spaces, Hazard Communication, and Job Site Safety Management 1.5 Voltage Classes, Approach Boundaries in Practice, and Equipment Isolation 1.6 Temporary Protective Grounding: ASTM F855, OSHA 1910.269(n), and the Equipotential Zone 1.7 Fall Protection, Ladders, Scaffolds, and Elevated Work 1.8 Fire Hazards, Extinguisher Classes, Emergency Response, First Aid, and CPR

2 Chapter 2: Electrical Power Theory, Test Instrumentation, and Basic Measurements

2.1 AC/DC Power Fundamentals, Three-Phase Systems, and Power Factor Concepts 2.2 Insulation Resistance Testing Fundamentals, Megohmmeters, DAR, and PI (IEEE 43) 2.3 Low-Resistance Measurement: Contact Resistance, DLROs, and Micro-ohmmeters 2.4 High-Voltage Test Equipment: AC/DC Hipots, VLF Sets, and Dielectric Withstand Principles 2.5 DC Circuit Analysis: Ohm's Law, Series and Parallel Networks, and Power 2.6 Test Equipment Identification, Selection, Ranges, and Calibration Control 2.7 Insulation Power Factor and Dissipation Factor Instrumentation: GST, GSTg, and UST Modes

3 Chapter 3: Power Transformers, Regulators, and Insulating Fluids

3.1 Transformer Visual Inspection, Nameplate Interpretation, and Vector Groups 3.2 Transformer Turns Ratio (TTR) and Winding Resistance Testing 3.3 Insulation Power Factor & Dissipation Factor Testing (Doble Test & Bushings) 3.4 Insulating Liquid Testing: Dielectric Breakdown (ASTM D877/D1816) and Physical Properties 3.5 Dissolved Gas Analysis (DGA, ASTM D3612), Duval Triangle, and Fault Interpretation 3.6 Excitation Current, Core Insulation, and Applied and Induced Potential Tests 3.7 Load Tap Changers, Voltage Regulators, and Insulating Liquid Processing

4 Chapter 4: Circuit Breakers, Switchgear, and Motor Control Centers

4.1 Low-Voltage Circuit Breakers (MCCB/LVPCB) and Electronic Trip Unit Testing (LSIG) 4.2 Medium- and High-Voltage Circuit Breakers: Vacuum, SF6, and Air Magnetic Breakers 4.3 Circuit Breaker Timing, Motion/Travel Analysis, and Contact Velocity 4.4 Switchgear, Switchboards, MCC Buswork, and Interlock Systems 4.5 Overcurrent Device Testing: Primary Injection, Secondary Injection, and Time-Current Curves 4.6 Vacuum Interrupter Integrity Testing and SF₆ Gas Quality Management 4.7 Fuses, Medium-Voltage Switches, and Disconnecting Devices

5 Chapter 5: Power Cables, Busways, and Terminations

5.1 Medium-Voltage Cable Construction, Shielding, and Termination Inspection 5.2 Cable Insulation Resistance, DC Withstand, and VLF Field Testing (IEEE 400.2) 5.3 Advanced Cable Diagnostics: Tan-Delta / Dissipation Factor and Partial Discharge (IEEE 400.3) 5.4 Busways, Duct Banks, and Cable Shield Continuity Testing 5.5 Cable Fault Location: TDR, Thumping, Arc Reflection, and Sectionalizing

6 Chapter 6: Protective Relaying and Instrument Transformers

6.1 Current Transformers (CTs): Ratio, Polarity, Excitation/Saturation, and Burden Testing 6.2 Voltage Transformers (VTs/PTs) and Control Power Transformers (CPTs) 6.3 Protective Relaying Fundamentals, Device ANSI Numbers (50/51, 87, 21, 27/59, 81), and Coordination 6.4 Electromechanical, Solid-State, and Digital/Microprocessor Relay Testing Methods 6.5 Differential Protection (87T, 87B, 87G) and Impedance/Distance Protection (21) 6.6 Overcurrent Relay Testing (50/51): Pickup, Timing, Reset, and Curve Selection 6.7 Protective Device Coordination, Short-Circuit, and Arc Flash Studies 6.8 Watt-Hour Meters, Transducers, and Power Quality Analysis 6.9 SCADA, Substation Automation, Functional Test Plans, and P&C Troubleshooting

7 Chapter 7: Grounding Systems and Ground-Fault Protection

7.1 Ground Resistance Testing: Fall-of-Potential (IEEE 81), 62% Rule, and Clamp-On Methods 7.2 Soil Resistivity Measurement (Wenner 4-Pin Method) and Ground Grid Integrity 7.3 Equipment Grounding, System Grounding, and Bonding Verification 7.4 Ground-Fault Protection Systems (GFPE): Sensor, Relay, and Injection Testing (NEC 230.95) 7.5 Step and Touch Potential and Ground Grid Design Criteria (IEEE 80)

8 Chapter 8: Rotating Machinery, Specialty Equipment, and Commissioning Management

8.1 AC/DC Motors and Generators: Stator, Rotor, Surge Comparison, and High-Potential Testing 8.2 Stationary Battery Systems, UPS, and DC Distribution Testing (IEEE 450 / 1188) 8.3 Automatic Transfer Switches and Emergency Power Transfer 8.4 NETA Acceptance vs. Maintenance Standards, Test Data Trending, and Temperature Correction 8.5 Electrical Commissioning: The Phased Sequence from Receipt to Full Load 8.6 Surge Arresters: Types, MCOV, Application, and Field Evaluation 8.7 Capacitors, Reactors, and Harmonic Filter Banks

9 Chapter 9: Infrared Thermography and Condition-Based Assessment

9.1 Infrared Thermography Fundamentals: Emissivity, Reflectivity, and Camera Setup 9.2 Conducting and Evaluating Thermographic Surveys (NETA Section 9, Table 100.18) 9.3 Ultrasonic, Corona, and Vibration Survey Techniques

10 Chapter 10: Test Data Evaluation, Troubleshooting, and Failure Analysis

10.1 Reading Electrical Drawings: One-Lines, Three-Lines, Schematics, and Site Plans 10.2 Evaluating Test Results Against NETA, Manufacturer, and Baseline Data 10.3 Serviceability Determination and Energization Readiness 10.4 Failure Modes, Root-Cause Analysis, and Corrective Recommendations

11 Chapter 11: Documentation, Reporting, and Standards Literacy

11.1 IEEE C37.2 Device Function Numbers, IEEE 315 Symbols, and NEMA Ratings 11.2 Test Data Recording, Field Forms, and Data Integrity 11.3 Technical Report Writing, Data Trending, and Communicating Deficiencies 11.4 Standards and Regulatory Literacy: NETA, IEEE, NFPA, ASTM, ANSI, and OSHA

12 Chapter 12: Job Planning, Switching, Supervision, and Professional Practice

12.1 Site-Specific Safety Plans, Job Hazard Analysis, and Safety Audits 12.2 Project Testing (Job) Plans, Scheduling, and Resource Management 12.3 Switching Procedures: Development, Review, Confirmation, and Execution 12.4 Supervising Test Crews, Training, and Assigning Personnel 12.5 NICET Code of Ethics, Client Relations, and Certification Maintenance

4.7 Fuses, Medium-Voltage Switches, and Disconnecting Devices

Key Takeaways Explain This Topic AI

Level III task 3.1d.4 requires comparing nameplate fuse data against design drawings, the short-circuit study, and specifications, and performing a fuse resistance test.

E-rated fuses are defined by their melting characteristic for transformer and feeder protection; R-rated fuses are current-limiting fuses for motor starter service used with a contactor and overload relay.

A current-limiting fuse clears within the first half cycle before the fault current reaches its prospective peak, so the let-through energy is far below the available fault energy.

The 2026 Level II outline adds medium-voltage switch testing as its own named task.

A load-interrupter switch can make and break load current but has no fault interrupting rating, which is why it is fused rather than relied on for fault clearing.

Last updated: August 2026

Fuses, Medium-Voltage Switches, and Disconnecting Devices

Quick Answer: Level III task 3.1d.4, "Check fuse types, ratings, and applications," requires the technician to "compare nameplate fuse data with design drawings, short circuit study, and/or specifications," "compare control fuse types and ratings to schematics," and "perform and evaluate a fuse resistance test." The 2026 Level II outline adds 2.2.1, "Demonstrate testing knowledge for medium voltage (MV) switches." Both are separately graded and neither is covered by the circuit breaker material.

1. The three numbers on every fuse

Voltage rating. A fuse must be applied at or below its voltage rating. Crucially, a fuse may not be applied on a system above its rating , but a higher-rated fuse on a lower-voltage system is generally acceptable — the rating relates to the fuse's ability to interrupt and then withstand the recovery voltage across the open gap.

Continuous current rating. What it will carry indefinitely without opening, subject to ambient and enclosure derating.

Interrupting rating. The maximum fault current the fuse can safely interrupt. This must equal or exceed the available fault current at its location. A fuse applied below the available fault current can rupture violently rather than interrupting.

2. Medium-voltage fuse classes

Class Application Key characteristic

E-rated Transformer primaries, feeders, general purpose Defined by a melting time characteristic : fuses 100 E and below melt at 200-240 % of the E rating in 300 seconds; above 100 E, at 220-264 % in 600 seconds

R-rated Medium-voltage motor starters only Current-limiting back-up fuse; the R number is not a continuous current rating

Current-limiting general purpose Feeders, transformers Interrupts within the first half cycle, limiting peak let-through

Expulsion / boric acid Outdoor distribution cutouts Vents arc products to atmosphere; not current-limiting

The R-rated fuse trap. An R-rated fuse used in a medium-voltage motor controller is a back-up current-limiting fuse . It is not sized to carry and protect against overload — the contactor and overload relay do that. The fuse exists only to interrupt high-magnitude faults that exceed the contactor's interrupting capability. Candidates who treat the R number as an ampere rating misapply the device. The classic exam framing is "what protects the motor against a sustained overload in an R-rated starter?" — the overload relay, not the fuse.

The E-rating trap is similar in shape: the E number is a melting characteristic classification, not a straightforward continuous ampere rating, though it correlates with one.

3. Current limitation and let-through energy

A current-limiting fuse melts, arcs, and clears within the first half cycle , before the prospective fault current has risen to its peak. Two consequences that matter for equipment protection:

Peak let-through current (I_p) is far below the prospective peak the circuit would have produced. This limits the magnetic forces on downstream equipment.

Let-through energy (I²t) is drastically reduced, which limits the thermal damage.

This is what allows a series-rated combination: downstream equipment with an interrupting rating below the available fault current can be applied when protected by a specific tested upstream current-limiting device. The critical restriction — and it is a code and safety matter, not a preference — is that series ratings are valid only for the exact tested combinations published by the manufacturer , and the assembly must be marked accordingly. Substituting a different fuse of the same rating voids the series rating.

Peak let-through charts are read by entering the available fault current on the horizontal axis, reading up to the fuse curve, and across to the let-through peak. Where the fuse curve meets the line representing the un-limited peak, the fuse ceases to be current-limiting — below that threshold current the fuse does not clear within the first half cycle.

4. The fuse resistance test

The check specified at Level III is straightforward and diagnostically useful:

Remove the fuse from the circuit — an in-circuit reading measures parallel paths, not the fuse.

Measure resistance with a DLRO or a low-resistance ohmmeter , not a general-purpose multimeter, because a healthy fuse element is a few milliohms or less.

Compare across the set. The three phases of a matched set should read closely to one another, and to the manufacturer's published cold resistance.

Investigate any fuse reading substantially higher than its mates — that fuse has partially melted, has a damaged element, or has a degraded end-cap connection, and it will not coordinate as designed.

Additional inspection points: verify the fuse type, class, voltage, current, and interrupting rating against the drawings and the short-circuit study ; check that the fuse clips exert proper pressure and are not discoloured or corroded; and confirm all three fuses in a set are the same manufacturer, type, and rating . A mixed set does not coordinate, and single-phasing from one blown fuse is a recognized motor-damage mechanism.

5. Medium-voltage switches — what interrupts what

The distinction the exam tests is what a device is rated to interrupt.

  • Device Can carry load Can break load current Can interrupt fault current
  • Isolating (disconnect) switch Yes No No
  • Load-interrupter switch Yes Yes No
  • Circuit breaker Yes Yes Yes
  • Fused load-interrupter switch Yes Yes Yes, via the fuse

An isolating switch is a no-load device . It provides a visible break for isolation and is operated only after the load has been interrupted by something else. Operating a plain disconnect under load draws an arc it cannot quench.

A load-interrupter switch adds an arc-quenching mechanism — commonly a quick-make quick-break spring mechanism with arcing horns or an SF₆ or vacuum interrupting element — sized for load current only. It has no fault interrupting rating , which is precisely why the standard medium-voltage unit substation front end is a fused load-interrupter switch : the switch handles routine load switching and isolation, and the fuse handles faults.

Testing a medium-voltage switch:

Visual and mechanical: blade alignment and full seating, contact pressure and wipe, arcing horn condition, insulator cleanliness and cracks, operating mechanism lubrication, and interlock verification — key interlocks and mechanical interlocks that prevent operating the switch with the door open, or racking with the switch closed, are safety devices and are functionally tested, not just inspected.

Contact resistance across each pole with a DLRO, compared phase to phase.

Insulation resistance phase-to-ground, phase-to-phase, and across the open gap.

Quick-make quick-break verification: the mechanism must be independent of operator speed. A slow-motion manual operation that produces a slow contact part indicates a failed spring mechanism and is a serious defect, because the arc duration then depends on how fast the operator moves the handle.

Exam trap: A question asks what protects a medium-voltage motor against a sustained mechanical overload in a controller using R-rated fuses. The answer is the overload relay . The R-rated fuse is a back-up current-limiting device for high-magnitude faults only and carries no continuous ampere rating in its designation.