1 Chapter 1: Electrical Safety, Standards, and Work Practices (NFPA 70E & OSHA)

1.1 NFPA 70E Framework, Electrically Safe Work Conditions, and Approach Boundaries 1.2 Arc Flash Hazard Analysis, Incident Energy, and PPE Category Selection 1.3 Hazardous Energy Control: OSHA 1910.147 Lockout/Tagout & Grounding Procedures 1.4 Confined Spaces, Hazard Communication, and Job Site Safety Management 1.5 Voltage Classes, Approach Boundaries in Practice, and Equipment Isolation 1.6 Temporary Protective Grounding: ASTM F855, OSHA 1910.269(n), and the Equipotential Zone 1.7 Fall Protection, Ladders, Scaffolds, and Elevated Work 1.8 Fire Hazards, Extinguisher Classes, Emergency Response, First Aid, and CPR

2 Chapter 2: Electrical Power Theory, Test Instrumentation, and Basic Measurements

2.1 AC/DC Power Fundamentals, Three-Phase Systems, and Power Factor Concepts 2.2 Insulation Resistance Testing Fundamentals, Megohmmeters, DAR, and PI (IEEE 43) 2.3 Low-Resistance Measurement: Contact Resistance, DLROs, and Micro-ohmmeters 2.4 High-Voltage Test Equipment: AC/DC Hipots, VLF Sets, and Dielectric Withstand Principles 2.5 DC Circuit Analysis: Ohm's Law, Series and Parallel Networks, and Power 2.6 Test Equipment Identification, Selection, Ranges, and Calibration Control 2.7 Insulation Power Factor and Dissipation Factor Instrumentation: GST, GSTg, and UST Modes

3 Chapter 3: Power Transformers, Regulators, and Insulating Fluids

3.1 Transformer Visual Inspection, Nameplate Interpretation, and Vector Groups 3.2 Transformer Turns Ratio (TTR) and Winding Resistance Testing 3.3 Insulation Power Factor & Dissipation Factor Testing (Doble Test & Bushings) 3.4 Insulating Liquid Testing: Dielectric Breakdown (ASTM D877/D1816) and Physical Properties 3.5 Dissolved Gas Analysis (DGA, ASTM D3612), Duval Triangle, and Fault Interpretation 3.6 Excitation Current, Core Insulation, and Applied and Induced Potential Tests 3.7 Load Tap Changers, Voltage Regulators, and Insulating Liquid Processing

4 Chapter 4: Circuit Breakers, Switchgear, and Motor Control Centers

4.1 Low-Voltage Circuit Breakers (MCCB/LVPCB) and Electronic Trip Unit Testing (LSIG) 4.2 Medium- and High-Voltage Circuit Breakers: Vacuum, SF6, and Air Magnetic Breakers 4.3 Circuit Breaker Timing, Motion/Travel Analysis, and Contact Velocity 4.4 Switchgear, Switchboards, MCC Buswork, and Interlock Systems 4.5 Overcurrent Device Testing: Primary Injection, Secondary Injection, and Time-Current Curves 4.6 Vacuum Interrupter Integrity Testing and SF₆ Gas Quality Management 4.7 Fuses, Medium-Voltage Switches, and Disconnecting Devices

5 Chapter 5: Power Cables, Busways, and Terminations

5.1 Medium-Voltage Cable Construction, Shielding, and Termination Inspection 5.2 Cable Insulation Resistance, DC Withstand, and VLF Field Testing (IEEE 400.2) 5.3 Advanced Cable Diagnostics: Tan-Delta / Dissipation Factor and Partial Discharge (IEEE 400.3) 5.4 Busways, Duct Banks, and Cable Shield Continuity Testing 5.5 Cable Fault Location: TDR, Thumping, Arc Reflection, and Sectionalizing

6 Chapter 6: Protective Relaying and Instrument Transformers

6.1 Current Transformers (CTs): Ratio, Polarity, Excitation/Saturation, and Burden Testing 6.2 Voltage Transformers (VTs/PTs) and Control Power Transformers (CPTs) 6.3 Protective Relaying Fundamentals, Device ANSI Numbers (50/51, 87, 21, 27/59, 81), and Coordination 6.4 Electromechanical, Solid-State, and Digital/Microprocessor Relay Testing Methods 6.5 Differential Protection (87T, 87B, 87G) and Impedance/Distance Protection (21) 6.6 Overcurrent Relay Testing (50/51): Pickup, Timing, Reset, and Curve Selection 6.7 Protective Device Coordination, Short-Circuit, and Arc Flash Studies 6.8 Watt-Hour Meters, Transducers, and Power Quality Analysis 6.9 SCADA, Substation Automation, Functional Test Plans, and P&C Troubleshooting

7 Chapter 7: Grounding Systems and Ground-Fault Protection

7.1 Ground Resistance Testing: Fall-of-Potential (IEEE 81), 62% Rule, and Clamp-On Methods 7.2 Soil Resistivity Measurement (Wenner 4-Pin Method) and Ground Grid Integrity 7.3 Equipment Grounding, System Grounding, and Bonding Verification 7.4 Ground-Fault Protection Systems (GFPE): Sensor, Relay, and Injection Testing (NEC 230.95) 7.5 Step and Touch Potential and Ground Grid Design Criteria (IEEE 80)

8 Chapter 8: Rotating Machinery, Specialty Equipment, and Commissioning Management

8.1 AC/DC Motors and Generators: Stator, Rotor, Surge Comparison, and High-Potential Testing 8.2 Stationary Battery Systems, UPS, and DC Distribution Testing (IEEE 450 / 1188) 8.3 Automatic Transfer Switches and Emergency Power Transfer 8.4 NETA Acceptance vs. Maintenance Standards, Test Data Trending, and Temperature Correction 8.5 Electrical Commissioning: The Phased Sequence from Receipt to Full Load 8.6 Surge Arresters: Types, MCOV, Application, and Field Evaluation 8.7 Capacitors, Reactors, and Harmonic Filter Banks

9 Chapter 9: Infrared Thermography and Condition-Based Assessment

9.1 Infrared Thermography Fundamentals: Emissivity, Reflectivity, and Camera Setup 9.2 Conducting and Evaluating Thermographic Surveys (NETA Section 9, Table 100.18) 9.3 Ultrasonic, Corona, and Vibration Survey Techniques

10 Chapter 10: Test Data Evaluation, Troubleshooting, and Failure Analysis

10.1 Reading Electrical Drawings: One-Lines, Three-Lines, Schematics, and Site Plans 10.2 Evaluating Test Results Against NETA, Manufacturer, and Baseline Data 10.3 Serviceability Determination and Energization Readiness 10.4 Failure Modes, Root-Cause Analysis, and Corrective Recommendations

11 Chapter 11: Documentation, Reporting, and Standards Literacy

11.1 IEEE C37.2 Device Function Numbers, IEEE 315 Symbols, and NEMA Ratings 11.2 Test Data Recording, Field Forms, and Data Integrity 11.3 Technical Report Writing, Data Trending, and Communicating Deficiencies 11.4 Standards and Regulatory Literacy: NETA, IEEE, NFPA, ASTM, ANSI, and OSHA

12 Chapter 12: Job Planning, Switching, Supervision, and Professional Practice

12.1 Site-Specific Safety Plans, Job Hazard Analysis, and Safety Audits 12.2 Project Testing (Job) Plans, Scheduling, and Resource Management 12.3 Switching Procedures: Development, Review, Confirmation, and Execution 12.4 Supervising Test Crews, Training, and Assigning Personnel 12.5 NICET Code of Ethics, Client Relations, and Certification Maintenance

11.4 Standards and Regulatory Literacy: NETA, IEEE, NFPA, ASTM, ANSI, and OSHA

Key Takeaways Explain This Topic AI

The 2026 Level II outline adds recognizing the scope of standards and regulatory organizations as a named task.

OSHA regulations are law and are enforceable; NFPA, IEEE, NETA, and ASTM documents are consensus standards that become enforceable when adopted, referenced, or contracted.

NETA ATS covers acceptance testing for initial energization and NETA MTS covers maintenance testing for continued service.

NFPA 70 is the installation code, NFPA 70B is the maintenance recommended practice that became a standard in its 2023 edition, and NFPA 70E is the electrical safety in the workplace standard.

ASTM standards specify test methods for insulating liquids, and citing the correct method number is part of reporting an oil result correctly.

Last updated: August 2026

Standards and Regulatory Literacy: NETA, IEEE, NFPA, ASTM, ANSI, and OSHA

Quick Answer: The 2026 Level II outline adds task 2.3.4, "Recognize the scope of standards and regulatory organizations." The distinction that organizes everything: OSHA regulations are law. NFPA, IEEE, NETA, ASTM, and ANSI documents are consensus standards — they become enforceable when adopted into law by a jurisdiction, referenced by an enforceable regulation, or written into a contract.

1. Law versus consensus standard

OSHA — the Occupational Safety and Health Administration — issues regulations in the Code of Federal Regulations. They are federal law, enforced by inspection and citation.

  • Regulation Scope
  • 29 CFR 1910 General industry — the standard for operating facilities
  • 1910.132 Personal protective equipment, general requirements
  • 1910.146 Permit-required confined spaces
  • 1910.147 The control of hazardous energy ( lockout/tagout )
  • 1910.269 Electric power generation, transmission, and distribution
  • 1910.331-335 Electrical safety-related work practices
  • 1910.1200 Hazard Communication
  • 29 CFR 1926 Construction
  • 1926 Subpart K Electrical
  • 1926 Subpart M Fall protection
  • 1926 Subpart V Electric power transmission and distribution

Consensus standards are developed by industry through balanced committees. They carry authority in three ways: adoption into law (most US jurisdictions adopt some edition of NFPA 70 as the electrical code), incorporation by reference (OSHA's general duty clause and specific rules reference recognized industry practice), and contract (a project specification requiring "testing per ANSI/NETA ATS" makes that standard binding on that job).

A recurring exam framing: "Is NFPA 70E law?" Not by itself. It is a consensus standard. But OSHA cites it as the recognized industry method for compliance with electrical safety requirements, and many employers and jurisdictions adopt it directly — so in practice a violation of 70E is very often also an OSHA citation.

2. The standards that define EPT work

NETA — InterNational Electrical Testing Association. The standards at the centre of this credential:

  • Standard Scope
  • ANSI/NETA ATS Acceptance Testing Specifications — suitability for initial energization
  • ANSI/NETA MTS Maintenance Testing Specifications — fitness for continued service
  • ANSI/NETA ETT Standard for Certification of Electrical Testing Technicians
  • ANSI/NETA ECS Standard for Electrical Commissioning Specifications

Both ATS and MTS are organized as: Section 7 by equipment type (7.1 switchgear, 7.2 transformers, 7.3 cables, 7.5 breakers, 7.6 protective relays, and so on), each with visual and mechanical inspection, electrical tests, and test values; Section 8 for system function tests; Section 9 for thermographic surveys ; and the Table 100 series of numerical criteria.

IEEE — Institute of Electrical and Electronics Engineers. The numbers that recur throughout EPT:

  • Standard Subject
  • IEEE 43 Insulation resistance testing of rotating machinery — the source of PI
  • IEEE 80 Safety in AC substation grounding — step and touch potential
  • IEEE 81 Measuring earth resistivity, ground impedance, and earth surface potentials
  • IEEE 315 Graphic symbols for electrical diagrams
  • IEEE 400 / 400.1 / 400.2 / 400.3 Field testing of shielded power cable: general, DC, VLF , partial discharge
  • IEEE 450 / 1188 / 1106 Maintenance and testing of vented lead-acid, VRLA , and nickel-cadmium batteries
  • IEEE 519 Harmonic control — voltage and current distortion limits
  • IEEE 1100 Powering and grounding electronic equipment (the Emerald Book)
  • IEEE C37.2 Device function numbers

IEEE C37.13 / C37.20 / C37.09 Low-voltage power circuit breakers, switchgear assemblies, HV breaker test procedure

  • IEEE C57.12.90 / .91 Test code for liquid-immersed and dry-type transformers
  • IEEE C57.104 Interpretation of gases generated in oil-immersed transformers ( DGA )
  • IEEE C57.106 Acceptance and maintenance of insulating mineral oil
  • IEEE C57.13 Instrument transformers

NFPA — National Fire Protection Association:

  • Standard Role
  • NFPA 70 (NEC) Installation code — how it must be built

NFPA 70B Maintenance — historically a Recommended Practice, elevated to a Standard in its 2023 edition, which changed its language from "should" to "shall"

  • NFPA 70E Electrical Safety in the Workplace — how to work on or near it safely
  • NFPA 30 Flammable and combustible liquids code

Know which of the three "70s" answers which question. How should this be installed? NFPA 70. How do I maintain it? NFPA 70B. How do I work on it without getting hurt? NFPA 70E. That triage decides a surprising number of exam items.

ASTM International — test methods for insulating liquids, cited constantly in the EPT outlines:

  • Method Measures
  • D877 Dielectric breakdown, flat disc electrodes, 0.1 in (2.54 mm) gap

D1816 Dielectric breakdown, VDE spherical electrodes, 1 mm or 2 mm gap — more sensitive to moisture and particles

  • D923 Sampling of insulating liquids
  • D924 Dissipation factor / power factor of insulating liquid
  • D971 Interfacial tension
  • D974 / D664 Neutralization (acid) number
  • D1298 Specific gravity / density
  • D1500 Colour
  • D1524 Visual examination
  • D1533 Water content
  • D2285 / D4059 PCB content
  • D3612 Dissolved gas analysis
  • D92 Flash and fire point
  • D445 Viscosity

D877 versus D1816 is the pair most often tested. D877 uses flat disc electrodes with a wide gap and is relatively insensitive to small amounts of moisture and particulate. D1816 uses spherical VDE electrodes with a small gap and stirring, and is far more sensitive to exactly those contaminants. As a result, D1816 gives a lower breakdown voltage than D877 on the same oil, and their acceptance limits are numerically different — comparing a D1816 result against a D877 limit is a classic error.

ANSI — American National Standards Institute accredits the development process; it does not generally write standards itself. That is why documents appear as ANSI/NETA ATS or ANSI/IEEE C57 — the ANSI prefix indicates the standard was developed under an accredited consensus process. ANSI C84.1 (nominal system voltages) and ANSI Z535.4 (product safety signs and labels) are direct ANSI documents cited in the EPT outlines.

Other bodies in the outlines: NEMA (equipment ratings, enclosure types, ICS 19 diagram conventions), ASNT (nondestructive testing personnel qualification, relevant to thermography certification levels), and IEC (international standards, notably 61850 for substation automation and 60947 for control equipment).

3. Editions and effective dates

Standards are revised, and the applicable edition is a real question.

A project specification usually names an edition. That is the one that governs, even if a newer one exists.

A jurisdiction adopts a specific edition of the NEC, and adoption lags publication — sometimes by years. The edition your jurisdiction has adopted is the code, not the newest one published.

NETA revises ATS and MTS on a multi-year cycle, and Table values do change between editions. Cite the edition with the table.

When sources conflict, compare effective dates, scope, and applicability , and prefer the newest applicable document from the body that owns the subject over a stale secondary summary or a not-yet-effective future rule.

Citing a standard without its edition is an incomplete citation in a formal report, for exactly this reason.

4. Which body owns which question

  • Question Standard
  • What test do I perform on this new switchgear? ANSI/NETA ATS
  • What test do I perform at the maintenance interval? ANSI/NETA MTS
  • How is this installed? NFPA 70
  • How do I work on it safely? NFPA 70E + OSHA 1910/1926
  • How do I maintain the electrical system? NFPA 70B
  • What is the PI acceptance value for a motor? IEEE 43
  • How do I measure ground resistance? IEEE 81
  • How do I VLF-test a cable? IEEE 400.2
  • How do I interpret transformer gas data? IEEE C57.104
  • How do I sample transformer oil? ASTM D923
  • What does device 87 mean? IEEE C37.2
  • What harmonic distortion is acceptable? IEEE 519
  • Is this enclosure suitable outdoors? NEMA 250
  • What is the nominal voltage tolerance? ANSI C84.1

Exam trap: A question gives an insulating oil dielectric breakdown result and an acceptance limit, and the two come from different ASTM methods. D1816 uses spherical electrodes with a small gap and is far more sensitive to moisture and particles than D877's flat discs with a wider gap , so it yields a lower value on the same oil. Their limits are not interchangeable.