Study guide
7.5 Step and Touch Potential and Ground Grid Design Criteria (IEEE 80)
NICET Electrical Power Testing Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Electrical Safety, Standards, and Work Practices (NFPA 70E & OSHA)
1.1 NFPA 70E Framework, Electrically Safe Work Conditions, and Approach Boundaries 1.2 Arc Flash Hazard Analysis, Incident Energy, and PPE Category Selection 1.3 Hazardous Energy Control: OSHA 1910.147 Lockout/Tagout & Grounding Procedures 1.4 Confined Spaces, Hazard Communication, and Job Site Safety Management 1.5 Voltage Classes, Approach Boundaries in Practice, and Equipment Isolation 1.6 Temporary Protective Grounding: ASTM F855, OSHA 1910.269(n), and the Equipotential Zone 1.7 Fall Protection, Ladders, Scaffolds, and Elevated Work 1.8 Fire Hazards, Extinguisher Classes, Emergency Response, First Aid, and CPR
2 Chapter 2: Electrical Power Theory, Test Instrumentation, and Basic Measurements
2.1 AC/DC Power Fundamentals, Three-Phase Systems, and Power Factor Concepts 2.2 Insulation Resistance Testing Fundamentals, Megohmmeters, DAR, and PI (IEEE 43) 2.3 Low-Resistance Measurement: Contact Resistance, DLROs, and Micro-ohmmeters 2.4 High-Voltage Test Equipment: AC/DC Hipots, VLF Sets, and Dielectric Withstand Principles 2.5 DC Circuit Analysis: Ohm's Law, Series and Parallel Networks, and Power 2.6 Test Equipment Identification, Selection, Ranges, and Calibration Control 2.7 Insulation Power Factor and Dissipation Factor Instrumentation: GST, GSTg, and UST Modes
3 Chapter 3: Power Transformers, Regulators, and Insulating Fluids
3.1 Transformer Visual Inspection, Nameplate Interpretation, and Vector Groups 3.2 Transformer Turns Ratio (TTR) and Winding Resistance Testing 3.3 Insulation Power Factor & Dissipation Factor Testing (Doble Test & Bushings) 3.4 Insulating Liquid Testing: Dielectric Breakdown (ASTM D877/D1816) and Physical Properties 3.5 Dissolved Gas Analysis (DGA, ASTM D3612), Duval Triangle, and Fault Interpretation 3.6 Excitation Current, Core Insulation, and Applied and Induced Potential Tests 3.7 Load Tap Changers, Voltage Regulators, and Insulating Liquid Processing
4 Chapter 4: Circuit Breakers, Switchgear, and Motor Control Centers
4.1 Low-Voltage Circuit Breakers (MCCB/LVPCB) and Electronic Trip Unit Testing (LSIG) 4.2 Medium- and High-Voltage Circuit Breakers: Vacuum, SF6, and Air Magnetic Breakers 4.3 Circuit Breaker Timing, Motion/Travel Analysis, and Contact Velocity 4.4 Switchgear, Switchboards, MCC Buswork, and Interlock Systems 4.5 Overcurrent Device Testing: Primary Injection, Secondary Injection, and Time-Current Curves 4.6 Vacuum Interrupter Integrity Testing and SF₆ Gas Quality Management 4.7 Fuses, Medium-Voltage Switches, and Disconnecting Devices
5 Chapter 5: Power Cables, Busways, and Terminations
5.1 Medium-Voltage Cable Construction, Shielding, and Termination Inspection 5.2 Cable Insulation Resistance, DC Withstand, and VLF Field Testing (IEEE 400.2) 5.3 Advanced Cable Diagnostics: Tan-Delta / Dissipation Factor and Partial Discharge (IEEE 400.3) 5.4 Busways, Duct Banks, and Cable Shield Continuity Testing 5.5 Cable Fault Location: TDR, Thumping, Arc Reflection, and Sectionalizing
6 Chapter 6: Protective Relaying and Instrument Transformers
6.1 Current Transformers (CTs): Ratio, Polarity, Excitation/Saturation, and Burden Testing 6.2 Voltage Transformers (VTs/PTs) and Control Power Transformers (CPTs) 6.3 Protective Relaying Fundamentals, Device ANSI Numbers (50/51, 87, 21, 27/59, 81), and Coordination 6.4 Electromechanical, Solid-State, and Digital/Microprocessor Relay Testing Methods 6.5 Differential Protection (87T, 87B, 87G) and Impedance/Distance Protection (21) 6.6 Overcurrent Relay Testing (50/51): Pickup, Timing, Reset, and Curve Selection 6.7 Protective Device Coordination, Short-Circuit, and Arc Flash Studies 6.8 Watt-Hour Meters, Transducers, and Power Quality Analysis 6.9 SCADA, Substation Automation, Functional Test Plans, and P&C Troubleshooting
7 Chapter 7: Grounding Systems and Ground-Fault Protection
7.1 Ground Resistance Testing: Fall-of-Potential (IEEE 81), 62% Rule, and Clamp-On Methods 7.2 Soil Resistivity Measurement (Wenner 4-Pin Method) and Ground Grid Integrity 7.3 Equipment Grounding, System Grounding, and Bonding Verification 7.4 Ground-Fault Protection Systems (GFPE): Sensor, Relay, and Injection Testing (NEC 230.95) 7.5 Step and Touch Potential and Ground Grid Design Criteria (IEEE 80)
8 Chapter 8: Rotating Machinery, Specialty Equipment, and Commissioning Management
8.1 AC/DC Motors and Generators: Stator, Rotor, Surge Comparison, and High-Potential Testing 8.2 Stationary Battery Systems, UPS, and DC Distribution Testing (IEEE 450 / 1188) 8.3 Automatic Transfer Switches and Emergency Power Transfer 8.4 NETA Acceptance vs. Maintenance Standards, Test Data Trending, and Temperature Correction 8.5 Electrical Commissioning: The Phased Sequence from Receipt to Full Load 8.6 Surge Arresters: Types, MCOV, Application, and Field Evaluation 8.7 Capacitors, Reactors, and Harmonic Filter Banks
9 Chapter 9: Infrared Thermography and Condition-Based Assessment
9.1 Infrared Thermography Fundamentals: Emissivity, Reflectivity, and Camera Setup 9.2 Conducting and Evaluating Thermographic Surveys (NETA Section 9, Table 100.18) 9.3 Ultrasonic, Corona, and Vibration Survey Techniques
10 Chapter 10: Test Data Evaluation, Troubleshooting, and Failure Analysis
10.1 Reading Electrical Drawings: One-Lines, Three-Lines, Schematics, and Site Plans 10.2 Evaluating Test Results Against NETA, Manufacturer, and Baseline Data 10.3 Serviceability Determination and Energization Readiness 10.4 Failure Modes, Root-Cause Analysis, and Corrective Recommendations
11 Chapter 11: Documentation, Reporting, and Standards Literacy
11.1 IEEE C37.2 Device Function Numbers, IEEE 315 Symbols, and NEMA Ratings 11.2 Test Data Recording, Field Forms, and Data Integrity 11.3 Technical Report Writing, Data Trending, and Communicating Deficiencies 11.4 Standards and Regulatory Literacy: NETA, IEEE, NFPA, ASTM, ANSI, and OSHA
12 Chapter 12: Job Planning, Switching, Supervision, and Professional Practice
12.1 Site-Specific Safety Plans, Job Hazard Analysis, and Safety Audits 12.2 Project Testing (Job) Plans, Scheduling, and Resource Management 12.3 Switching Procedures: Development, Review, Confirmation, and Execution 12.4 Supervising Test Crews, Training, and Assigning Personnel 12.5 NICET Code of Ethics, Client Relations, and Certification Maintenance
7.5 Step and Touch Potential and Ground Grid Design Criteria (IEEE 80)
Key Takeaways Explain This Topic AI
Level II task 2.1i.2 names step potential and touch potential tests among the required ground grid measurements.
Touch potential is the voltage between an energized structure a person can touch and the earth about one metre away; step potential is the voltage between the feet about one metre apart.
A low grid resistance does not by itself make a substation safe; the safety criterion is that actual step and touch voltages stay below the tolerable limits for body weight and shock duration.
Tolerable voltage limits rise with faster fault clearing time, so protection speed is a grounding design parameter.
A surface layer of high-resistivity crushed rock raises the tolerable touch and step voltages substantially by adding resistance in series with the body path.
Last updated: August 2026
Step and Touch Potential and Ground Grid Design Criteria (IEEE 80)
Quick Answer: Level II task 2.1i.2 lists "step potential and touch potential tests" among the required knowledge for ground grid testing, alongside fall-of-potential, two-point, clamp-on, slope, intersecting curves, and earth resistivity. The governing insight: a low grid resistance does not by itself make a substation safe. Safety is determined by whether the voltages a person can actually be exposed to stay below tolerable limits — and a low-resistance grid with poor geometry can still be dangerous.
1. The four potentials
When fault current flows into the earth through a grounding grid, the earth surface develops a potential gradient — highest at the injection point, falling with distance. That gradient is where the hazard lives.
- Term Definition
- Ground potential rise (GPR) The voltage of the entire grid with respect to remote earth: GPR = I_G × R_g
Touch potential Voltage between an energized structure a person can touch and the earth surface about 1 metre away (arm's reach) — current path hand to feet
Step potential Voltage between two points on the earth surface 1 metre apart — current path foot to foot
Mesh potential The maximum touch potential within a grid mesh, at the centre of the mesh where the surface potential is lowest relative to the conductors
Transferred potential GPR carried outside the substation on a conductive path — a communication cable, a metallic water pipe, a fence, a neutral conductor — exposing someone at remote earth to nearly the full GPR
Touch is generally more dangerous than step. A hand-to-feet path drives current directly across the chest and the heart; a foot-to-foot path largely does not. Tolerable step voltages are correspondingly higher than tolerable touch voltages.
Transferred potential is the most dangerous of all , because the person is standing at remote earth (essentially zero volts) while touching something at nearly the full GPR. A grid with a 5,000 V GPR presents almost the entire 5,000 V across a person who touches a fence bonded to the grid while standing outside it. This is why substation fences, communication circuits, and metallic piping receive specific isolation or bonding treatment, and it is a favourite exam scenario.
2. Why grid resistance alone is the wrong criterion
The "25 ohm rule" familiar from NEC 250.53 applies to a single made electrode at a service and has nothing to do with substation grid safety. Likewise a substation target such as "1 ohm or less" is a design convention, not a safety proof.
Consider two grids with identical 0.5 Ω resistance. One is a dense mesh with closely spaced conductors and a deep crushed-rock surface layer; the other is a sparse perimeter loop on bare soil. Both have the same GPR for a given fault current. The dense grid keeps the earth surface potential close to the conductor potential everywhere, so mesh and step voltages are small. The sparse grid lets the surface potential sag deeply between conductors, producing large mesh voltages. Same resistance, very different safety.
The correct chain of reasoning is therefore:
Determine the fault current flowing into the grid (I_G) — not the total fault current, since some returns via overhead ground wires, neutrals, and cable shields.
Compute the GPR .
Compute the actual mesh and step voltages from grid geometry, conductor spacing, burial depth, and soil model.
Compare against the tolerable step and touch voltages.
If actual exceeds tolerable, change the design — more conductors, closer spacing, ground rods, a deeper or higher-resistivity surface layer, or faster fault clearing.
3. Tolerable limits and what moves them
IEEE 80 derives tolerable body current from the Dalziel relationship, in which the tolerable current is inversely proportional to the square root of the shock duration. Two consequences dominate:
Faster fault clearing raises the tolerable voltage. Protection speed is therefore a grounding design parameter , not merely a protection parameter. Upgrading relaying to clear in 5 cycles instead of 30 can bring a marginal grid into compliance without touching the copper. This linkage between protection and grounding is exactly the kind of cross-domain reasoning Level III and IV questions are written to test.
Body weight matters. IEEE 80 gives separate criteria for a 50 kg and a 70 kg body; the 50 kg criterion is more conservative and is the usual design basis where the public or lighter personnel may be present.
The surface layer. A layer of high-resistivity crushed rock — typically 4 to 6 inches of clean, washed stone — placed over the substation yard adds resistance in series with the body's foot contact , and this substantially raises both tolerable touch and tolerable step voltage. Two field-critical points:
The rock must be clean and washed . Fines, dirt, and organic debris that accumulate over years, and especially wet contaminated rock , dramatically reduce its resistivity and erode the safety margin the design depended on. A yard that has not been re-surfaced in decades may no longer meet the design it was built to.
Depth matters , and a thin or eroded layer does not deliver the assumed derating factor.
Assessing surface layer condition is a legitimate and often-overlooked field observation during a grounding survey.
4. Measuring step and touch potential
Calculations are validated by measurement, typically by injecting current into the grid from a remote electrode and measuring the resulting voltages, then scaling the results to the design fault current.
Touch measurement: a voltmeter between the structure under test and a probe placed in the earth 1 metre from the structure, with a resistor (commonly 1,000 Ω) in the measuring circuit to represent body resistance.
Step measurement: two probes 1 metre apart on the earth surface, again through a body-representing resistance.
Scaling: the measured voltage per ampere of injected current is multiplied by the design grid current. Because injection is typically tens of amperes against a design fault of thousands, the scaling factor is large and any measurement error scales with it.
Interference rejection: substation yards carry substantial stray 60 Hz current, so measurements use an offset frequency or a filtered instrument, exactly as in fall-of-potential testing.
Locations to test: operating handles of switches and breakers, fences (particularly at gates and corners, and where a fence leaves the grid perimeter), transformer and equipment enclosures, control building doors, and the perimeter where the gradient is steepest.
5. Common grid deficiencies found in the field
Corroded or broken connections. Exothermic (Cadweld) connections are the standard for buried joints because bolted connections corrode; a bolted buried joint is a deficiency.
Equipment risers disconnected or theft-cut. Copper theft has become a routine finding on unmanned sites.
Fence bonding incorrect. Either unbonded where the design requires bonding, or bonded where it creates a transferred potential path to the outside.
Additions not bonded. New equipment installed without a riser to the grid.
Surface layer degraded , as above.
Soil resistivity changed — a site model built on a dry-season survey may not represent seasonal extremes, and the design should use the worst applicable case.
Exam trap: A question states that a substation grid measures 0.4 Ω and asks whether the grounding system is adequate. Grid resistance alone answers nothing about safety. The question that determines adequacy is whether the calculated step and touch voltages stay below the tolerable limits for the design fault current, the clearing time, and the surface layer in place.