9.3 Ultrasonic, Corona, and Vibration Survey Techniques

NICET Electrical Power Testing Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Electrical Safety, Standards, and Work Practices (NFPA 70E & OSHA)

1.1 NFPA 70E Framework, Electrically Safe Work Conditions, and Approach Boundaries 1.2 Arc Flash Hazard Analysis, Incident Energy, and PPE Category Selection 1.3 Hazardous Energy Control: OSHA 1910.147 Lockout/Tagout & Grounding Procedures 1.4 Confined Spaces, Hazard Communication, and Job Site Safety Management 1.5 Voltage Classes, Approach Boundaries in Practice, and Equipment Isolation 1.6 Temporary Protective Grounding: ASTM F855, OSHA 1910.269(n), and the Equipotential Zone 1.7 Fall Protection, Ladders, Scaffolds, and Elevated Work 1.8 Fire Hazards, Extinguisher Classes, Emergency Response, First Aid, and CPR

2 Chapter 2: Electrical Power Theory, Test Instrumentation, and Basic Measurements

2.1 AC/DC Power Fundamentals, Three-Phase Systems, and Power Factor Concepts 2.2 Insulation Resistance Testing Fundamentals, Megohmmeters, DAR, and PI (IEEE 43) 2.3 Low-Resistance Measurement: Contact Resistance, DLROs, and Micro-ohmmeters 2.4 High-Voltage Test Equipment: AC/DC Hipots, VLF Sets, and Dielectric Withstand Principles 2.5 DC Circuit Analysis: Ohm's Law, Series and Parallel Networks, and Power 2.6 Test Equipment Identification, Selection, Ranges, and Calibration Control 2.7 Insulation Power Factor and Dissipation Factor Instrumentation: GST, GSTg, and UST Modes

3 Chapter 3: Power Transformers, Regulators, and Insulating Fluids

3.1 Transformer Visual Inspection, Nameplate Interpretation, and Vector Groups 3.2 Transformer Turns Ratio (TTR) and Winding Resistance Testing 3.3 Insulation Power Factor & Dissipation Factor Testing (Doble Test & Bushings) 3.4 Insulating Liquid Testing: Dielectric Breakdown (ASTM D877/D1816) and Physical Properties 3.5 Dissolved Gas Analysis (DGA, ASTM D3612), Duval Triangle, and Fault Interpretation 3.6 Excitation Current, Core Insulation, and Applied and Induced Potential Tests 3.7 Load Tap Changers, Voltage Regulators, and Insulating Liquid Processing

4 Chapter 4: Circuit Breakers, Switchgear, and Motor Control Centers

4.1 Low-Voltage Circuit Breakers (MCCB/LVPCB) and Electronic Trip Unit Testing (LSIG) 4.2 Medium- and High-Voltage Circuit Breakers: Vacuum, SF6, and Air Magnetic Breakers 4.3 Circuit Breaker Timing, Motion/Travel Analysis, and Contact Velocity 4.4 Switchgear, Switchboards, MCC Buswork, and Interlock Systems 4.5 Overcurrent Device Testing: Primary Injection, Secondary Injection, and Time-Current Curves 4.6 Vacuum Interrupter Integrity Testing and SF₆ Gas Quality Management 4.7 Fuses, Medium-Voltage Switches, and Disconnecting Devices

5 Chapter 5: Power Cables, Busways, and Terminations

5.1 Medium-Voltage Cable Construction, Shielding, and Termination Inspection 5.2 Cable Insulation Resistance, DC Withstand, and VLF Field Testing (IEEE 400.2) 5.3 Advanced Cable Diagnostics: Tan-Delta / Dissipation Factor and Partial Discharge (IEEE 400.3) 5.4 Busways, Duct Banks, and Cable Shield Continuity Testing 5.5 Cable Fault Location: TDR, Thumping, Arc Reflection, and Sectionalizing

6 Chapter 6: Protective Relaying and Instrument Transformers

6.1 Current Transformers (CTs): Ratio, Polarity, Excitation/Saturation, and Burden Testing 6.2 Voltage Transformers (VTs/PTs) and Control Power Transformers (CPTs) 6.3 Protective Relaying Fundamentals, Device ANSI Numbers (50/51, 87, 21, 27/59, 81), and Coordination 6.4 Electromechanical, Solid-State, and Digital/Microprocessor Relay Testing Methods 6.5 Differential Protection (87T, 87B, 87G) and Impedance/Distance Protection (21) 6.6 Overcurrent Relay Testing (50/51): Pickup, Timing, Reset, and Curve Selection 6.7 Protective Device Coordination, Short-Circuit, and Arc Flash Studies 6.8 Watt-Hour Meters, Transducers, and Power Quality Analysis 6.9 SCADA, Substation Automation, Functional Test Plans, and P&C Troubleshooting

7 Chapter 7: Grounding Systems and Ground-Fault Protection

7.1 Ground Resistance Testing: Fall-of-Potential (IEEE 81), 62% Rule, and Clamp-On Methods 7.2 Soil Resistivity Measurement (Wenner 4-Pin Method) and Ground Grid Integrity 7.3 Equipment Grounding, System Grounding, and Bonding Verification 7.4 Ground-Fault Protection Systems (GFPE): Sensor, Relay, and Injection Testing (NEC 230.95) 7.5 Step and Touch Potential and Ground Grid Design Criteria (IEEE 80)

8 Chapter 8: Rotating Machinery, Specialty Equipment, and Commissioning Management

8.1 AC/DC Motors and Generators: Stator, Rotor, Surge Comparison, and High-Potential Testing 8.2 Stationary Battery Systems, UPS, and DC Distribution Testing (IEEE 450 / 1188) 8.3 Automatic Transfer Switches and Emergency Power Transfer 8.4 NETA Acceptance vs. Maintenance Standards, Test Data Trending, and Temperature Correction 8.5 Electrical Commissioning: The Phased Sequence from Receipt to Full Load 8.6 Surge Arresters: Types, MCOV, Application, and Field Evaluation 8.7 Capacitors, Reactors, and Harmonic Filter Banks

9 Chapter 9: Infrared Thermography and Condition-Based Assessment

9.1 Infrared Thermography Fundamentals: Emissivity, Reflectivity, and Camera Setup 9.2 Conducting and Evaluating Thermographic Surveys (NETA Section 9, Table 100.18) 9.3 Ultrasonic, Corona, and Vibration Survey Techniques

10 Chapter 10: Test Data Evaluation, Troubleshooting, and Failure Analysis

10.1 Reading Electrical Drawings: One-Lines, Three-Lines, Schematics, and Site Plans 10.2 Evaluating Test Results Against NETA, Manufacturer, and Baseline Data 10.3 Serviceability Determination and Energization Readiness 10.4 Failure Modes, Root-Cause Analysis, and Corrective Recommendations

11 Chapter 11: Documentation, Reporting, and Standards Literacy

11.1 IEEE C37.2 Device Function Numbers, IEEE 315 Symbols, and NEMA Ratings 11.2 Test Data Recording, Field Forms, and Data Integrity 11.3 Technical Report Writing, Data Trending, and Communicating Deficiencies 11.4 Standards and Regulatory Literacy: NETA, IEEE, NFPA, ASTM, ANSI, and OSHA

12 Chapter 12: Job Planning, Switching, Supervision, and Professional Practice

12.1 Site-Specific Safety Plans, Job Hazard Analysis, and Safety Audits 12.2 Project Testing (Job) Plans, Scheduling, and Resource Management 12.3 Switching Procedures: Development, Review, Confirmation, and Execution 12.4 Supervising Test Crews, Training, and Assigning Personnel 12.5 NICET Code of Ethics, Client Relations, and Certification Maintenance

9.3 Ultrasonic, Corona, and Vibration Survey Techniques

Key Takeaways Explain This Topic AI

Airborne ultrasound detects partial discharge, corona, tracking, arcing, and pressure leaks that produce no measurable heat and therefore no infrared signature.

Corona produces a steady buzz at the 60 Hz reference while tracking and arcing produce erratic crackling, which is how ultrasonic signatures are distinguished.

Solar-blind ultraviolet cameras image corona directly by detecting the narrow UV band that reaches the ground through the solar-blind atmospheric window.

Corona generates ozone and nitric acid, so an ozone smell inside switchgear is a discharge indicator that requires investigation before the enclosure is opened.

Vibration analysis complements electrical testing on rotating machinery because misalignment, unbalance, bearing wear, and electrical faults produce distinguishable frequency signatures.

Last updated: August 2026

Ultrasonic, Corona, and Vibration Survey Techniques

Quick Answer: Infrared finds resistive heating . It is largely blind to partial discharge, corona, and surface tracking , which release very little energy as heat but a great deal as high-frequency sound and ultraviolet light . A survey program that relies on infrared alone will miss the entire class of insulation defects that kills medium-voltage switchgear.

1. Why infrared is not enough

A loose connection converts electrical energy into heat, and heat is what a camera sees. A partial discharge inside a switchgear compartment converts electrical energy into acoustic energy, light, ozone, and localized erosion of the insulation — with a thermal signature so small it is generally undetectable through an open door, let alone a viewing window.

The failure progression is real and fast: a small void or a contaminated surface begins discharging, the discharge erodes a track, the track grows, and the eventual result is a phase-to-ground or phase-to-phase flashover inside energized switchgear. The complementary technologies exist because that progression is invisible to a thermal camera until the moment it is not.

2. Airborne ultrasound

What it detects. Electrical discharge produces broadband sound extending well above the audible range. An ultrasonic detector listens in a narrow band, typically centred around 40 kHz , and heterodynes it down into the audible range so the technician can hear it in headphones.

Listening at 40 kHz rather than in the audible band is the key design choice: it sits above almost all mechanical and environmental background noise, so the signal-to-noise ratio for a small discharge is enormously better than it would be at audible frequencies.

What it finds:

  • Condition Signature
  • Corona Steady, uniform buzz , strongly locked to the 60 Hz cycle
  • Surface tracking Erratic crackling and popping , irregular in time
  • Arcing Sharp, irregular cracks , often louder and more violent
  • Loose connection / partial contact Intermittent frying or sizzling
  • Pressure or vacuum leak Steady rushing hiss — used on SF₆ compartments and compressed air systems

Distinguishing corona from tracking and arcing is the interpretive skill. Corona is steady and periodic because it re-ignites at the same point on each half cycle. Tracking and arcing are erratic because they follow a physical path that changes as it erodes. Instruments that display the signal against a 60 Hz phase reference make this distinction visible rather than merely audible, and a discharge that is locked to the power frequency and shows a characteristic double-hump pattern per cycle is a classic corona signature.

Field technique:

Use the contact (structure-borne) probe for enclosed equipment where sound cannot escape into the air, and the airborne dish or open probe for radiated sound.

Scan the seams — door gaps, ventilation louvres, cable entries, bushing boots, viewing windows. Ultrasound leaks out of openings, so the loudest point at a seam localizes the source inside.

Compare across phases and across identical cubicles , exactly as with infrared.

Ultrasound works through a closed door where infrared cannot, because sound escapes through gaps. This makes it a genuinely lower-risk survey tool: much of the scan can be performed without opening an enclosure.

3. Corona and ultraviolet imaging

Corona is partial ionization of the air adjacent to a conductor where the local electric field exceeds the breakdown strength of air, without a complete breakdown across the gap. It occurs at sharp points, damaged strands, contaminated insulators, poor terminations, and hardware with inadequate corona shielding.

Why it matters:

It erodes. Corona chemically attacks polymer insulation and hardware over time.

It produces ozone (O₃) and, with moisture, nitric acid , both of which are corrosive to insulation, metals, and equipment.

It generates radio interference and audible noise.

It is an early indicator — corona often precedes tracking, which precedes flashover.

The smell test is a genuine field technique. The sharp, sweet, chlorine-like smell of ozone at a switchgear lineup is a discharge indicator. It is also a warning to investigate before opening the enclosure — an ozone smell means active discharge inside energized equipment, and opening the door casually is exactly the wrong response. Also look for white or grey powder deposits (nitric acid reaction products), surface tracking marks, and pitting on hardware.

Solar-blind UV cameras. Corona emits ultraviolet light, but sunlight swamps most of the UV band. The solar-blind window is a narrow band around 240-280 nm in which atmospheric ozone absorbs virtually all solar UV before it reaches ground level. A camera filtered to that band sees essentially no background from the sun, so a corona discharge appears as a bright, unambiguous point even in full daylight . Modern instruments overlay the UV image on a visible image so the discharge is located precisely on the hardware.

This is the standard tool for outdoor substation and transmission hardware inspection, where the equipment is inaccessible and the defect produces no heat.

4. Where each technology belongs

  • Defect Infrared Ultrasound UV corona
  • Loose or corroded connection Primary Secondary No
  • Overloaded conductor Primary No No
  • Partial discharge in switchgear Poor Primary Limited (enclosed)
  • Corona on outdoor hardware Poor Good Primary
  • Surface tracking on insulators Poor Good Good
  • SF₆ or compressed air leak No Primary No
  • Failing arrester Good Secondary Good
  • Bearing degradation Secondary Good No

The programme point: these are complements, not alternatives. A defect that one technology cannot see is often the one the other detects first.

5. Vibration analysis on rotating machinery

Electrical testing establishes the condition of a motor's insulation and windings . It says almost nothing about its mechanical condition, and most motors are removed from service for mechanical reasons.

The diagnostic principle: different faults produce vibration at different, identifiable frequencies expressed as multiples of running speed (1×, 2×, and so on).

  • Fault Characteristic signature
  • Unbalance Dominant 1× running speed , radial
  • Misalignment 2× running speed prominent, with significant axial vibration
  • Mechanical looseness Multiple harmonics — 1×, 2×, 3×, and often half-order components

Bearing defects High-frequency, non-synchronous components at bearing defect frequencies specific to the bearing geometry

  • Rotor bar problems Sidebands around running speed spaced at pole-pass frequency
  • Electrical unbalance / stator issues Vibration at 2× line frequency (120 Hz)
  • Resonance Large amplitude at a specific speed that disappears above and below it

Two signatures worth committing to memory because they distinguish electrical from mechanical causes:

2× line frequency (120 Hz) vibration points to an electrical cause — stator eccentricity, unbalanced supply, shorted laminations. The give-away test: remove power and watch. Electrically induced vibration disappears instantly ; mechanically induced vibration coasts down with the rotor.

Pole-pass sidebands around the running speed peak indicate broken or cracked rotor bars , which is a fault that no insulation test detects at all and which shows up as gradual loss of torque and eventual failure to start under load.

Bearing current damage is an increasingly common finding on VFD-driven motors: common-mode voltage from the inverter drives current through the bearing, producing electrical discharge machining that leaves a characteristic fluting pattern on the race. Detection combines vibration analysis with shaft voltage measurement; the remedies are insulated bearings, shaft grounding rings, and output filters. This is a genuinely modern failure mode and a good Level IV analysis scenario, because the symptom is mechanical and the cause is electrical.

Exam trap: A question describes a switchgear compartment where an infrared survey through the viewing window found nothing, yet operators report a sharp ozone smell. Infrared is largely blind to partial discharge because it releases very little heat. The indicated tools are ultrasonic detection and, where the hardware is visible, UV corona imaging — and the enclosure should not be opened casually while active discharge is suspected.