3.2 Control Units & Power Supplies

Key Takeaways Explain This Topic AI

The fire alarm control unit (FACP) receives initiating inputs, prioritizes alarm over supervisory over trouble, and commands notification and auxiliary functions.

Primary power is a dedicated branch circuit with an over-current device that is mechanically protected and marked in red, often locked, and labeled FIRE ALARM CIRCUIT.

Most protected-premises systems require secondary (standby) power for 24 hours of standby followed by 5 minutes of full alarm load.

Battery sizing sums standby amp-hours and alarm amp-hours, then multiplies the total by a derating safety factor of about 1.2 for battery aging.

Loss of AC primary power produces an audible and visible trouble signal at the FACP and remote annunciators, and the batteries carry the load.

Last updated: June 2026

The Fire Alarm Control Unit (FACP)

The fire alarm control unit (FACP) , also called the fire alarm control panel, is the brain of the system. It is roughly the hub that every initiating, notification, and power topic on FAS-I connects back to. Its core jobs are:

Receive inputs from initiating devices and circuits (IDCs and SLCs) - alarm, supervisory, and trouble conditions.

Process and prioritize those inputs. The standard priority is alarm first, then supervisory, then trouble . An alarm always overrides a lower-priority condition on the display and signaling.

Command outputs - activate NACs (horns/strobes), and drive auxiliary functions such as elevator recall, HVAC shutdown, door release, and relay modules.

Supervise itself and its field wiring - monitor circuit integrity, battery condition, charger operation, and ground faults, annunciating any fault as a trouble signal.

Annunciate the system state locally and at remote annunciators so responders can see status and zone information away from the main panel.

Knowing this input-process-output model lets you reason through most panel questions even without memorizing a specific manufacturer.

Primary (Main) Power

The primary power supply is the building's AC service. NFPA 72 requires the fire alarm system to be fed from a dedicated branch circuit - it serves the fire alarm system and nothing else. That circuit's over-current device (breaker) must be:

Mechanically protected against accidental shutoff, commonly with a breaker lock .

Identified in red and clearly marked, typically labeled "FIRE ALARM CIRCUIT."

Accessible only to authorized personnel.

The point is simple: nobody should be able to kill the fire alarm system by flipping the wrong breaker, and if the breaker does open, it must be obvious which one it is.

Secondary (Standby) Power

If primary AC fails, the system must keep protecting the building. The secondary (standby) power supply is almost always a set of sealed lead-acid storage batteries kept charged by the panel. The battery charger continuously float-charges and supervises the batteries; a failed charger or a low/disconnected battery is annunciated as a trouble signal.

The governing requirement for most protected-premises systems is:

24 hours of standby (system quietly monitoring on battery), followed by

5 minutes of full alarm load (all required notification appliances energized).

Different occupancies have different numbers - emergency voice/alarm communication systems and certain supervising-station equipment use longer standby (for example 24 hours standby plus 15 minutes alarm for EVACS, or 60 hours for some central-station units) - but 24 hours + 5 minutes is the baseline number to know cold for FAS-I.