Study guide
10.3 Central Stations, Signal Types, and Path Supervision
New York Security or Fire Alarm Installer License Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Current Exam Facts 1.2 81-Hour Qualifying Education 1.3 Application, Fees, and Fingerprints
2 Who Must Be Licensed
2.1 License Required and Exemptions 2.2 Install, Service, Maintain, Assist, and Network 2.3 Master Electrician Waiver 2.4 NYS DOS License versus NYC FDNY and Local Inspection
3 Business Practice, Employees, and Discipline
3.1 Employees, ID Cards, and Fingerprints 3.2 Qualifying Officers, Display, Records, and Advertising 3.3 Discipline, Criminal Bars, and Penalties
4 Standards and Codes
4.1 Standards Organizations 4.2 New York Uniform Fire Prevention and Building Code and the AHJ 4.3 Listed Equipment, Compatibility, and AHJ Approval
5 NEC and Article 760
5.1 NEC Overview for Alarm Work 5.2 Power-Limited versus Non-Power-Limited Fire Alarm Circuits 5.3 Fire Alarm Cable Types, Plenums, Risers, and Abandoned Cable
6 Basic Electricity I
6.1 Voltage, Current, Resistance, and Ohm’s Law 6.2 Series and Parallel Circuits 6.3 Power, Energy, and Watt’s Law
7 Basic Electricity II
7.1 AC, DC, Transformers, and Low-Voltage Power Supplies 7.2 Batteries for Alarm Systems 7.3 Meters, Opens, Shorts, and Ground Faults
8 Control Devices
8.1 Control Panel Functions and Architecture 8.2 Conventional Zones and IDCs 8.3 Addressable Systems and Signaling Line Circuits
9 Circuits, Battery Calculations, and Job Planning
9.1 Notification Appliance Circuits and Circuit Classes 9.2 Secondary Power and Battery Calculations 9.3 Job Planning and Record Keeping
10 Alarm Transmission
10.1 Digital Alarm Communicators and Legacy Phone Paths 10.2 IP, Cellular, and Dual-Path Communications 10.3 Central Stations, Signal Types, and Path Supervision
11 Motion Detection
11.1 Passive Infrared Motion Detection 11.2 Microwave, Ultrasonic, and Dual-Technology Sensors 11.3 Placement, Pet Immunity, Masking, and Walk-Test
12 Perimeter, Video, Access Control, and False Alarms
12.1 Perimeter Systems 12.2 CCTV / Video Surveillance and Specialty Systems 12.3 Access Control 12.4 False Alarm Prevention
13 Fire Detection Devices
13.1 Fire Behavior and Detector Application 13.2 Smoke Detection 13.3 Heat Detection
14 Other Initiating Devices and Notification
14.1 Manual Stations, Waterflow, Supervisory, Duct, and CO 14.2 Horns, Strobes, Speakers, and Candela 14.3 Notification Placement, Public Mode, and Accessibility
15 Fire Alarm Systems
15.1 System Types and Occupancy Context 15.2 Pathways, Classes, and Survivability 15.3 Elevator Recall, HVAC Shutdown, Door Release, and Suppression Release
16 Job Safety and Professional Conduct
16.1 Job Safety 16.2 Overview and Professional Conduct 16.3 Service Role versus Installation Role
17 Testing and Inspection
17.1 Acceptance Testing and Commissioning 17.2 Periodic Inspection, Testing, and Maintenance Frequencies 17.3 ITM Documentation and Records
18 Troubleshooting and Device Service
18.1 Testing and Troubleshooting Methods 18.2 Panels, Alarm Devices, and Communications Service 18.3 Specialty Service Items
19 Maintenance, Programming, and False-Alarm Reporting
19.1 Maintenance Programs and Contracts 19.2 Maintenance, Inspection, and False Alarm Reporting 19.3 Programming, Access Codes, Bypass, and Hours of Operation
10.3 Central Stations, Signal Types, and Path Supervision
Key Takeaways Explain This Topic AI
19 NYCRR 195.1(b) defines a central station as an off-premises monitoring facility with special receiving equipment in communication with the subscriber’s protected premises; personnel are generally in attendance continuously to observe, record, and dispatch.
Central-station personnel may report alarm signals to police, fire, or other agencies; they may also provide runner response with security personnel or technicians to check and service the system.
Fire alarm, supervisory, trouble, and restore are different signal types; burglary and panic are different again and must not be programmed as if they were smoke or waterflow.
19 NYCRR 195.18: security personnel who respond to an alarm and secure a protected premises trigger Article 7 and Article 7-A; technicians who respond only to check or service the alarm system do not require Article 7 licensure for that technician-only model.
Programming account numbers, test timers, and failure-to-test handling is licensed 19 NYCRR 195.1 work; a missed test is a communications trouble that must be handled, not a paperwork courtesy.
Last updated: September 2026
Why the receiver end of the path is a licensing topic
Module 2.III is not finished when the DACT kissoffs. Someone has to observe , record , and dispatch . Independent ExamFinch teaching for the New York DOS Security or Fire Alarm Installer exam uses the definition DOS actually printed. 19 NYCRR 195.1(b) (January 2023 DOS compilation of GBL Article 6-D and Part 195) defines central station as follows, in substance:
An off-premises monitoring facility with special receiving equipment , in communication with the transmission equipment for a subscriber’s protected premises . The transmission equipment for the subscriber’s protected premises may be owned by the central station, the subscriber, or any other person . Personnel are generally in attendance on a continuous basis to observe, record, and dispatch personnel to investigate various alarms or trouble signals . They may report alarm signals to police, fire, or other agencies . Central stations may also provide response services to a protected premises with security personnel or with technicians to check and service the system.
Memorize the hinges, not a paraphrase that drops them:
Off-premises — a FACU in the electrical room is not a central station.
Special receiving equipment — an after-hours voicemail box is not a DACR.
Communication with the subscriber’s transmitter — ownership of that transmitter is flexible.
Continuous attendance — generally, people are there to watch the signals.
Observe, record, dispatch — three operator verbs.
May report to police or fire — retransmission is contemplated.
Security personnel or technicians — two different response models; 195.18 splits them.
NFPA 72 uses supervising station as the broader technical term (central station, remote station, proprietary supervising station). Chapter 15 returns to occupancy and system types. This section stays on what 195.1(b) named and what the communicator actually sends.
Signal types — alarm, supervisory, trouble, restore
The FACU does not have one yellow light called “something is wrong.” Off-premises reporting uses four families you must not collapse.
Signal What it means Typical fire example Typical off-premises handling
Alarm A fire (or life-safety) initiating condition Smoke, heat, manual station , waterflow Fire signals are commonly taught as immediately retransmitted to the communications center (fire service), subject to any verification rules the AHJ and NFPA 72 actually permit
Supervisory An off-normal condition of a supervised fire-protection system, not a detector in alarm Control valve shut, low air on dry pipe, low water tank, some generator or pump off-normal points Notify the owner or designated representative; this is not “treat it as a smoke alarm” and not “ignore it as trouble”
Trouble Impairment of the fire alarm system itself Open NAC, ground fault, AC fail, low battery, communicator failure , missed test Notify the owner / licensed service company so the system can be repaired
Restore The condition returned to normal Valve reopened, AC restored, zone restored, test completed The station records the restore; Contact ID commonly uses qualifier 3
A closed sprinkler valve is the classic supervisory item. The building is not reporting a fire. It is reporting that a suppression system is impaired. Dispatching engines as if smoke were showing is the wrong mental model; logging it as a “panel trouble” so nobody calls the owner is also wrong.
A cut NAC is trouble . The horns may not work. That is a system impairment. It is not waterflow.
A waterflow switch is alarm (fire). Water is moving in the sprinkler system. That is not a supervisory valve event.
Restore is how the station knows the valve was reopened or the communicator test succeeded. Programming restores off, or mapping restores into a different account, is how a building stays in perpetual alarm in the automation software.
Fire versus burglary versus panic
The same 195.1(a) alarm-system definition covers intrusion, break-in, theft, movement, sound, fire, heat, smoke, explosion . The communicator still must label the event so the operator does the right thing.
Family Typical Contact ID (commonly taught) Local sounding Who is called
Fire 110 fire, 111 smoke, 113 waterflow, 115 pull Temporal-three / EVACS as designed Fire communications center
Burglary 130 burglary, 131 perimeter, 132 interior Siren or bell as designed Police , often after a verification call-down the subscriber contracted
Panic / holdup / duress 120 panic, 121 duress, 122 silent, 123 audible Often silent Police ; not the fire service
Medical (where used) 100-series medical Varies Medical / other agencies as contracted
Panic that sounds a siren can turn a holdup into a hostage problem. Fire that is programmed as burglary sends the wrong agency. Burglary that is programmed as fire sends engines to a door contact. Those are protocol errors under 195.1, not “monitoring preferences.”
Security opening/closing (arm/disarm) reports are not fire alarms. They are commonly Contact ID 400-family events. A missed opening can be a security supervisory-style event for the subscriber. It is still not waterflow.
Path supervision at the station — missed tests
Section 10.2 taught the timer . This section teaches the human . If the 60-minute single-path check-in, the 6-hour multiple-path test, or the DACT daily/6-hour test does not arrive, the DACR / automation must show a failure to test or communications trouble . 195.1(b) says personnel observe alarms or trouble signals . A missed test is a trouble signal. It is not optional wallpaper.
The licensed installer/service company is who fixes the path. The operator is who notices it. Programming the account to suppress fail-to-test, or telling the subscriber “we turned off the timer because the cell path was noisy,” takes the premises off the supervised path. That programming is 195.1 servicing.
Runner service versus technician-only — 19 NYCRR 195.18
195.1(b) allows a central station to send security personnel or technicians . Those are not the same license stack.
19 NYCRR 195.18 special licensure under Articles 7 and 7-A :
(a) A business licensed under Article 6-D that employs security guards as defined in GBL Article 7-A must also be licensed under Article 7 (Private Investigator, Watch, Guard or Patrol Agency) and must comply with Article 7-A security-guard registration . The regulation’s own example: the use of security personnel to respond to an alarm and secure a protected premises .
(b) A licensed alarm business that does not provide security response and does not otherwise employ security guards, but provides response with technicians only to check or service the alarm system , does not require Article 7 licensure for that model.
Exam application:
Runner / guard who arrives, locks doors , walks out loiterers , holds the scene — that is securing the premises . Article 7 and 7-A are in play. Alarm-installer IDs under Part 195 are not a guard card.
Technician who arrives, silences , resets , tests the communicator, replaces a battery, reports the FACU clear — that is checking or servicing the alarm system . Article 6-D covers it. Article 7 is not required by 195.18(b) for that technician-only response.
A technician who is told to “just stay until the owner gets there and keep people out” has been turned into a guard . The job description, not the van logo, decides.
Chapter 3 already treated discipline and Article 7/7-A as a business-practice overlay. This section is the transmission reason it appears: central stations dispatch people, and DOS drew a bright line between securing premises and servicing systems .
Putting the whole path on one drawing
Closed-book, walk the chain:
An initiating device (smoke, valve, door contact, holdup button) changes state.
The FACU or security control processes it as alarm, supervisory, trouble, or restore.
The communicator (DACT, IP, cellular, or dual-path) seizes a path and delivers Contact ID or another listed format.
The DACR / supervising-station automation handshakes , records, and kissoffs .
The operator observes and records, then dispatches the right agency and/or the right runner or technician.
A restore or a successful test closes the event. A missed test opens a trouble.
Ownership of the box on the wall does not remove the need for a licensed installer to program it. 195.1 still includes communication equipment and system protocol whether the central station, the subscriber, or “any other person” owns the transmitter.
Exam traps
Calling the FACU a central station because it has a communicator card.
Treating supervisory valve-off-normal as a fire alarm or as a wiring trouble.
Sending panic to the fire service, or waterflow to a burglary call list.
Claiming technician-only service response requires an Article 7 guard license.
Claiming guard/runner “secure the building” work is only Article 6-D.
Inventing a New York-only operator stopwatch (for example a unique DOS 90-second dispatch minute). Fire alarm retransmission is commonly taught NFPA 72 as immediate to the communications center; do not replace that with a fabricated statewide second-count.
When you can quote 195.1(b), split alarm/supervisory/trouble/restore, split fire/burg/panic, and split 195.18 runners from technicians, you have finished Module 2.III alarm transmission. Fire-technology chapters later reuse these signal types on detectors, waterflow, and notification. Service chapters reuse fail-to-test as a maintenance complaint.