Study guide

6.3 Power, Energy, and Watt’s Law

New York Security or Fire Alarm Installer License Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 Current Exam Facts 1.2 81-Hour Qualifying Education 1.3 Application, Fees, and Fingerprints

2 Who Must Be Licensed

2.1 License Required and Exemptions 2.2 Install, Service, Maintain, Assist, and Network 2.3 Master Electrician Waiver 2.4 NYS DOS License versus NYC FDNY and Local Inspection

3 Business Practice, Employees, and Discipline

3.1 Employees, ID Cards, and Fingerprints 3.2 Qualifying Officers, Display, Records, and Advertising 3.3 Discipline, Criminal Bars, and Penalties

4 Standards and Codes

4.1 Standards Organizations 4.2 New York Uniform Fire Prevention and Building Code and the AHJ 4.3 Listed Equipment, Compatibility, and AHJ Approval

5 NEC and Article 760

5.1 NEC Overview for Alarm Work 5.2 Power-Limited versus Non-Power-Limited Fire Alarm Circuits 5.3 Fire Alarm Cable Types, Plenums, Risers, and Abandoned Cable

6 Basic Electricity I

6.1 Voltage, Current, Resistance, and Ohm’s Law 6.2 Series and Parallel Circuits 6.3 Power, Energy, and Watt’s Law

7 Basic Electricity II

7.1 AC, DC, Transformers, and Low-Voltage Power Supplies 7.2 Batteries for Alarm Systems 7.3 Meters, Opens, Shorts, and Ground Faults

8 Control Devices

8.1 Control Panel Functions and Architecture 8.2 Conventional Zones and IDCs 8.3 Addressable Systems and Signaling Line Circuits

9 Circuits, Battery Calculations, and Job Planning

9.1 Notification Appliance Circuits and Circuit Classes 9.2 Secondary Power and Battery Calculations 9.3 Job Planning and Record Keeping

10 Alarm Transmission

10.1 Digital Alarm Communicators and Legacy Phone Paths 10.2 IP, Cellular, and Dual-Path Communications 10.3 Central Stations, Signal Types, and Path Supervision

11 Motion Detection

11.1 Passive Infrared Motion Detection 11.2 Microwave, Ultrasonic, and Dual-Technology Sensors 11.3 Placement, Pet Immunity, Masking, and Walk-Test

12 Perimeter, Video, Access Control, and False Alarms

12.1 Perimeter Systems 12.2 CCTV / Video Surveillance and Specialty Systems 12.3 Access Control 12.4 False Alarm Prevention

13 Fire Detection Devices

13.1 Fire Behavior and Detector Application 13.2 Smoke Detection 13.3 Heat Detection

14 Other Initiating Devices and Notification

14.1 Manual Stations, Waterflow, Supervisory, Duct, and CO 14.2 Horns, Strobes, Speakers, and Candela 14.3 Notification Placement, Public Mode, and Accessibility

15 Fire Alarm Systems

15.1 System Types and Occupancy Context 15.2 Pathways, Classes, and Survivability 15.3 Elevator Recall, HVAC Shutdown, Door Release, and Suppression Release

16 Job Safety and Professional Conduct

16.1 Job Safety 16.2 Overview and Professional Conduct 16.3 Service Role versus Installation Role

17 Testing and Inspection

17.1 Acceptance Testing and Commissioning 17.2 Periodic Inspection, Testing, and Maintenance Frequencies 17.3 ITM Documentation and Records

18 Troubleshooting and Device Service

18.1 Testing and Troubleshooting Methods 18.2 Panels, Alarm Devices, and Communications Service 18.3 Specialty Service Items

19 Maintenance, Programming, and False-Alarm Reporting

19.1 Maintenance Programs and Contracts 19.2 Maintenance, Inspection, and False Alarm Reporting 19.3 Programming, Access Codes, Bypass, and Hours of Operation

6.3 Power, Energy, and Watt’s Law

Key Takeaways Explain This Topic AI

Watt’s law is P = V × I = I² × R = V² / R; P = V × R is not a valid form.

A 24 V, 75 mA appliance dissipates 1.8 W; six in parallel dissipate 10.8 W at the loads.

A 4.7 kΩ EOL on 24 V dissipates about 0.12 W; a 470 Ω mix-up dissipates about 1.23 W and can overheat a ½ W resistor.

Energy in watt-hours is P × hours: 150 mA at 24 V for 24 hours is 86.4 Wh, which is 3.6 Ah.

Full secondary-power battery sizing, including a 20% safety factor, is Chapter 9; this section only previews Wh and Ah.

Last updated: September 2026

Why power and energy show up on an installer exam

Ohm’s law tells you volts, amps, and ohms. Module 1.III also expects power (how hard a load works, in watts) and energy (power over time, in watt-hours). You will use these numbers to read nameplates, estimate heat in a resistor or in copper, and to preview battery calculations . Full secondary-power arithmetic — 24-hour standby, 5-minute alarm, 20% safety factor, and occupancy exceptions — is Chapter 9 . This section teaches the laws those later hours sit on.

Power also explains a design choice you already used: 24 V fire circuits versus 12 V security circuits . For the same wattage of horns, doubling voltage halves current (I = P / V) and therefore halves I × R voltage drop in the same copper. Fire NACs run 24 VDC for a reason.

Watt’s law — three forms, one relationship

Power P is the rate of energy conversion. The unit is the watt (W) . One watt equals one joule per second.

  • P = V × I
  • P = I² × R
  • P = V² / R

These three are the same law once Ohm’s law is substituted (because V = I × R). Pick the form that matches the values you already know. P = V × R is not a form of Watt’s law — that product is not power.

Worked example I — P = V × I (one appliance and a NAC)

Horn-strobe: 24 V, 75 mA.

75 mA = 0.075 A.

P = 24 × 0.075 = 1.80 W .

Six such appliances in parallel: 6 × 1.80 = 10.8 W at the loads.

Check with total current from Section 6.2: P = 24 × 0.450 = 10.8 W . Same number.

If those 10.8 W of appliances were fed at 12 V instead of 24 V, current would be I = P / V = 10.8 / 12 = 0.90 A — twice the 0.45 A you had at 24 V. Wire drop and copper heating would both get worse. That is the 24 V advantage in one line of Watt’s law.

Worked example J — P = I²R (heat in the wire)

From Section 6.1: I = 0.450 A, R_wire = 2.556 Ω.

P_wire = (0.450)² × 2.556 = 0.2025 × 2.556 = 0.52 W .

That half-watt is heat along 400 ft of 18 AWG — not a fire by itself, but it is exactly the 1.15 V drop expressed as power:

P = V_drop × I = 1.15 × 0.450 = 0.52 W .

Copper that is too small gets warm and starves the last strobe of voltage. Doubling current quadruples I²R heating. A NAC short is violent compared with 5 mA of EOL supervision for that reason: current may jump from milliamps toward the panel’s short-circuit limit, and heating in the fault and in the copper spikes with the square of I.

Worked example K — P = V² / R (EOL resistor wattage)

EOL 4.7 kΩ on 24 V:

P = (24)² / 4,700 = 576 / 4,700 = 0.123 W .

A typical listed EOL is a ½ W (0.5 W) resistor — about four times this dissipation, which is why substituting a ¼ W part is a poor field habit. The resistor still only sees about 24 V in alarm on a NAC as well; the appliances take the real power. The danger is installing the wrong resistance , not the EOL sharing horn wattage.

Wrong part: a technician grabs 470 Ω (yellow-violet-brown) instead of 4.7 kΩ (yellow-violet-red).

I = 24 / 470 = 0.0511 A = 51.1 mA (looks like a perpetual alarm or a trouble, depending on the panel).

P = (24)² / 470 = 576 / 470 = 1.23 W — more than twice a ½ W resistor’s rating. The part can overheat. Same Ohm’s law, now with Watt’s law telling you the resistor is in trouble.

On a 12 V security EOL of 2.2 kΩ: P = (12)² / 2,200 = 144 / 2,200 = 0.065 W . Still a ½ W part in most kits, with even more thermal margin at 12 V.

Energy, watt-hours, and a battery preview

Energy = power × time. If P is in watts and t is in hours , energy is in watt-hours (Wh) .

Wh = V × I × t (hours)

Ah (ampere-hours) = I × t (hours) — the language of battery capacity.

Wh = V × Ah for a constant-voltage estimate.

Alarm batteries are rated in ampere-hours at a stated discharge rate. Chapter 9 converts standby current and alarm current into Ah, then applies a safety factor. Here we only build the energy intuition. Do not treat the following numbers as a finished battery size.

Worked example L — 24-hour standby energy

A FACU draws 150 mA standby from a 24 V battery for 24 hours . 24-hour standby is a common NFPA 72 secondary-power concept for many fire alarm systems; confirm the required hours for the occupancy and system type in Chapter 9 and the adopted NFPA 72 edition (New York’s 2025 Uniform Code references NFPA 72—22). 150 mA is a teaching standby current, not a particular panel’s datasheet.

Ah_standby = 0.150 A × 24 h = 3.60 Ah .

Wh_standby = 24 V × 3.60 Ah = 86.4 Wh .

Or P = 24 × 0.150 = 3.6 W, then 3.6 W × 24 h = 86.4 Wh .

Worked example M — 5-minute alarm energy

Same system, alarm current 2.00 A at 24 V for 5 minutes (5/60 = 0.0833 h). Five minutes of alarm is the duration many fire alarm systems use for secondary-power alarm time; emergency voice/alarm communication systems often use a longer alarm period — again, Chapter 9.

Ah_alarm = 2.00 × (5/60) = 0.167 Ah .

Wh_alarm = 24 × 2.00 × (5/60) = 4.00 Wh .

Standby energy ( 86.4 Wh ) dwarfs alarm energy ( 4 Wh ) in this example because 24 hours is long and 5 minutes is short. A panel that is idle but hungry (high standby current from communicators, smoke-detector power, or a hungry keypad on a security panel) kills batteries faster than a loud 5-minute NAC.

Rough combined draw before a safety factor: 3.60 + 0.167 = 3.77 Ah . Chapter 9 will multiply by 1.20 (20% safety factor as industry/NFPA practice) and add all NAC, auxiliary, and communicator loads. 3.77 Ah is not a finished battery size.

Worked example N — do not double-count the EOL

The 4.7 kΩ EOL at 0.123 W for 24 hours: 0.123 × 24 = 2.95 Wh . That energy is already inside the panel’s standby current if supervision current comes from the battery. Do not add 2.95 Wh again in Chapter 9.

Kilowatt-hours (kWh) are utility energy: 1 kWh = 1,000 Wh. A 7 Ah, 24 V battery stores about 24 × 7 = 168 Wh = 0.168 kWh . This exam almost never discusses alarm batteries in kWh; stay in Wh and Ah .

Power, polarity, opens, and shorts

Power in a resistor is always positive (heat). On a battery, current out of the positive terminal is discharge (the battery supplies energy); current into the positive terminal is charge. Chapter 7.2 covers charging; here you only need the sign of energy flow.

Reversed polarity on a polarized appliance means the device dissipates about 0 W (it does not operate) even though voltage is present — a DMM can still show about 24 V. Measuring voltage without considering current is how technicians miss a reverse-polarity NAC.

Open versus short, restated in power language (still a preview of Chapter 7.3):

Open: I ≈ 0, so P ≈ 0 in the load, even if voltage is present at the source.

Short: V_load ≈ 0, so P_load ≈ 0 at the load, but power in the remaining resistance and in the source can be very large.

  • Quantity Formula Use on this exam
  • Instantaneous power P = V × I Nameplate watts; NAC load
  • Heating in a known R P = I² × R Wire dissipation; short-circuit heat
  • Power from V and R P = V² / R EOL wattage; wrong-resistor check
  • Energy E = P × t (hours) Watt-hours
  • Battery capacity preview Ah = I × t (hours) Chapter 9 full calc
  • Exam traps

Using P = V × R.

Leaving milliamperes unconverted so 24 × 75 becomes 1,800 W instead of 1.8 W.

Reporting 3.6 Ah as 3.6 Wh (missing the × 24 V).

Treating the Chapter 9 20% factor as optional decoration rather than part of the later calc.

Sizing a ½ W EOL, then installing 470 Ω at 24 V.

You now have voltage, current, resistance, series/parallel, power, and energy. Chapter 7 applies them to AC/DC supplies, batteries, and meters. Chapter 9 puts Ah on a job sheet.

Loading diagram... Watt’s law to watt-hours to battery ampere-hours

Teaching example: watt-hours from 24 h standby vs 5 min alarm