6.2 Series and Parallel Circuits

New York Security or Fire Alarm Installer License Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 Current Exam Facts 1.2 81-Hour Qualifying Education 1.3 Application, Fees, and Fingerprints

2 Who Must Be Licensed

2.1 License Required and Exemptions 2.2 Install, Service, Maintain, Assist, and Network 2.3 Master Electrician Waiver 2.4 NYS DOS License versus NYC FDNY and Local Inspection

3 Business Practice, Employees, and Discipline

3.1 Employees, ID Cards, and Fingerprints 3.2 Qualifying Officers, Display, Records, and Advertising 3.3 Discipline, Criminal Bars, and Penalties

4 Standards and Codes

4.1 Standards Organizations 4.2 New York Uniform Fire Prevention and Building Code and the AHJ 4.3 Listed Equipment, Compatibility, and AHJ Approval

5 NEC and Article 760

5.1 NEC Overview for Alarm Work 5.2 Power-Limited versus Non-Power-Limited Fire Alarm Circuits 5.3 Fire Alarm Cable Types, Plenums, Risers, and Abandoned Cable

6 Basic Electricity I

6.1 Voltage, Current, Resistance, and Ohm’s Law 6.2 Series and Parallel Circuits 6.3 Power, Energy, and Watt’s Law

7 Basic Electricity II

7.1 AC, DC, Transformers, and Low-Voltage Power Supplies 7.2 Batteries for Alarm Systems 7.3 Meters, Opens, Shorts, and Ground Faults

8 Control Devices

8.1 Control Panel Functions and Architecture 8.2 Conventional Zones and IDCs 8.3 Addressable Systems and Signaling Line Circuits

9 Circuits, Battery Calculations, and Job Planning

9.1 Notification Appliance Circuits and Circuit Classes 9.2 Secondary Power and Battery Calculations 9.3 Job Planning and Record Keeping

10 Alarm Transmission

10.1 Digital Alarm Communicators and Legacy Phone Paths 10.2 IP, Cellular, and Dual-Path Communications 10.3 Central Stations, Signal Types, and Path Supervision

11 Motion Detection

11.1 Passive Infrared Motion Detection 11.2 Microwave, Ultrasonic, and Dual-Technology Sensors 11.3 Placement, Pet Immunity, Masking, and Walk-Test

12 Perimeter, Video, Access Control, and False Alarms

12.1 Perimeter Systems 12.2 CCTV / Video Surveillance and Specialty Systems 12.3 Access Control 12.4 False Alarm Prevention

13 Fire Detection Devices

13.1 Fire Behavior and Detector Application 13.2 Smoke Detection 13.3 Heat Detection

14 Other Initiating Devices and Notification

14.1 Manual Stations, Waterflow, Supervisory, Duct, and CO 14.2 Horns, Strobes, Speakers, and Candela 14.3 Notification Placement, Public Mode, and Accessibility

15 Fire Alarm Systems

15.1 System Types and Occupancy Context 15.2 Pathways, Classes, and Survivability 15.3 Elevator Recall, HVAC Shutdown, Door Release, and Suppression Release

16 Job Safety and Professional Conduct

16.1 Job Safety 16.2 Overview and Professional Conduct 16.3 Service Role versus Installation Role

17 Testing and Inspection

17.1 Acceptance Testing and Commissioning 17.2 Periodic Inspection, Testing, and Maintenance Frequencies 17.3 ITM Documentation and Records

18 Troubleshooting and Device Service

18.1 Testing and Troubleshooting Methods 18.2 Panels, Alarm Devices, and Communications Service 18.3 Specialty Service Items

19 Maintenance, Programming, and False-Alarm Reporting

19.1 Maintenance Programs and Contracts 19.2 Maintenance, Inspection, and False Alarm Reporting 19.3 Programming, Access Codes, Bypass, and Hours of Operation

6.2 Series and Parallel Circuits

Key Takeaways Explain This Topic AI

In series, the same current flows through every element, voltages add, and total resistance is the arithmetic sum.

In parallel, every branch sees the same voltage, branch currents add, and total resistance is less than the smallest branch.

A conventional Class B IDC uses a series wiring path to a listed EOL at the last device, with normally-open initiating devices in parallel across the pair.

NAC horns and strobes are parallel loads: six 75 mA appliances draw 450 mA at 24 V, not the 12.5 mA a series model would predict.

An open in the series wiring path is trouble; a short across a conventional IDC is typically alarm; a short on a NAC is trouble.

Last updated: September 2026

Why series and parallel decide alarm behavior

Ohm’s law describes one resistor. Field circuits are networks. A conventional initiating circuit is a series wiring path that must stay continuous out to the end-of-line (EOL) resistor, with normally-open devices in parallel across that pair. A notification appliance circuit (NAC) is a parallel load of horns, strobes, and speakers on a shared 24 V pair, with an EOL at the last appliance for supervision. If you mix up current is the same with voltage is the same, you will mis-size wire, leave the EOL on the panel terminals, and misread trouble versus alarm.

The DOS exam covers security and fire . A burglary loop of normally-closed contacts is often a true series string — one open door or one cut wire opens the whole loop. A conventional fire IDC is usually the opposite geometry: devices across the pair, EOL at the end. Do not copy a burglary series habit onto a fire zone.

Series rules — current the same; voltages add

In a series circuit there is one path. The same current I flows through every element. Voltages across elements add up to the source ( Kirchhoff’s voltage law ). Total resistance is the arithmetic sum:

  • R_T = R1 + R2 + R3 + …
  • I = V_T / R_T (this I is the same everywhere)
  • V_n = I × R_n and V_T = V1 + V2 + …

The largest resistor drops the largest voltage. If any element opens , current in the whole loop becomes zero.

Worked example E — EOL in series with copper

Take the 24 V source, the 4.7 kΩ typical listed EOL, and 3.2 Ω of copper (18 AWG at the Section 6.1 rate, about 500 ft round-trip).

R_T = 4,700 + 3.2 = 4,703.2 Ω .

I = 24 / 4,703.2 = 0.005103 A = 5.10 mA . That current is the same through the wire and through the EOL.

V_wire = 0.005103 × 3.2 = 0.016 V (16 mV — negligible on a meter).

V_EOL = 0.005103 × 4,700 = 23.98 V .

Check KVL: 0.016 + 23.98 = 24.00 V.

Teaching point: during supervision , the EOL dominates. Almost all of the 24 V appears across the 4.7 kΩ resistor. Wire resistance barely matters until the circuit goes into a low-resistance alarm state or you are calculating NAC appliance voltage.

Voltage-divider form of the same math: V_EOL = V_T × (R_EOL / R_T) = 24 × (4,700 / 4,703.2) ≈ 23.98 V.

Three resistors in series (pure arithmetic)

24 V, resistors 100 Ω, 200 Ω, and 300 Ω.

R_T = 100 + 200 + 300 = 600 Ω .

I = 24 / 600 = 0.040 A = 40 mA (same in each).

V_100 = 0.040 × 100 = 4 V; V_200 = 8 V; V_300 = 12 V; 4 + 8 + 12 = 24 V.

If the 200 Ω resistor opens, I = 0 everywhere and the full 24 V appears across the open — the qualitative open preview from Section 6.1, now with KVL underneath it.

Conventional IDC — series path, parallel contacts

Do not memorize a cartoon that says the smoke detectors are in series. On a typical conventional Class B IDC :

Two conductors leave the IDC terminals.

Each initiating device (manual station, 4-wire dry contact, waterflow, 2-wire smoke) lands across the pair — electrically in parallel with the other devices and with the EOL.

The EOL resistor lands across the pair at the last device, so supervision current is forced to travel the entire installed length.

In the normal condition (contacts open), the intended load is the EOL plus the tiny 2-wire smoke standby currents.

A break anywhere in the series wiring path stops EOL current → trouble .

A closed contact (or a 2-wire smoke in alarm) places a low resistance across the pair → alarm .

The EOL value is a typical listed value printed on the panel door . 4.7 kΩ is a widely used example in this guide; 2.2 kΩ is also common. Installing the wrong value, or leaving the factory EOL on the terminals instead of moving it to the last device, is a classic failed inspection.

If you install the EOL at the panel, the panel still sees a resistor and may show normal even when the field wiring is cut. That is why the resistor belongs at the end of the line .

Resistor color code, because the wrong part looks similar: 4.7 kΩ is yellow-violet-red (4, 7, ×100). 2.2 kΩ is red-red-red. A 470 Ω part is yellow-violet-brown — ten times too small. Section 6.3 shows that 470 Ω on 24 V dissipates more than a typical ½ W EOL can survive.

Class A versus Class B returns, including whether a particular circuit uses an EOL or a return pair, belong in Chapter 9. For this section, remember Class B: one path out, EOL at the last device.

Parallel rules — voltage the same; currents add

In a parallel circuit every branch sees the same voltage . Currents in the branches add ( Kirchhoff’s current law ). Total resistance is less than the smallest branch .

Two resistors: R_T = (R1 × R2) / (R1 + R2) (product over sum).

n equal resistors of value R: R_T = R / n .

  • General: 1/R_T = 1/R1 + 1/R2 + …
  • I_n = V / R_n and I_T = I1 + I2 + …

Opening one parallel branch stops only that branch. The others keep running. That is why five strobes still flash when the sixth is disconnected — and why a NAC still needs an EOL path to prove the wiring, not the appliances, is intact.

Worked example F — NAC appliances in parallel

24 V NAC. Six listed horn-strobes, each 75 mA at 24 V (each equivalent to 320 Ω from Section 6.1).

Because they share the pair, each still sees (ideally) 24 V, so each still draws 75 mA.

I_T = 6 × 0.075 = 0.450 A = 450 mA .

R_T = 320 / 6 = 53.3 Ω .

Check: I_T = 24 / 53.3 ≈ 0.450 A.

If you wrongly treated them as series, you would predict I = 24 / (6 × 320) = 12.5 mA — about 36 times too small — and both the battery and the NAC would be undersized. Notification appliances on a NAC are parallel loads .

Add a seventh appliance at 125 mA (equivalent 192 Ω):

I_T = 0.450 + 0.125 = 0.575 A .

Always add nameplate currents at the listed voltage, then apply voltage-drop (Ohm’s law on the wire) as a second step. Manufacturer NAC voltage-drop worksheets do the same arithmetic.

Worked example G — two unequal branches, product-over-sum check

24 V across 320 Ω (75 mA appliance) in parallel with 192 Ω (125 mA appliance).

I1 = 24 / 320 = 0.075 A; I2 = 24 / 192 = 0.125 A; I_T = 0.200 A .

R_T = 24 / 0.200 = 120 Ω .

Product over sum: (320 × 192) / (320 + 192) = 61,440 / 512 = 120 Ω . Same answer, two routes. Use current-addition on NACs; use product-over-sum when a problem hands you two resistors and no nameplate milliamperes.

Worked example H — two EOL resistors in parallel (fault)

Someone leaves a 4.7 kΩ on the panel terminals and installs another 4.7 kΩ at the last device. Those two resistors are in parallel across the IDC.

R_T = 4,700 / 2 = 2,350 Ω .

I = 24 / 2,350 = 10.2 mA — about twice the designed supervision current.

Some panels will show trouble (current too high). Some may appear normal but will not detect an open in the field if the panel-mounted resistor still completes a local path. Either way, it is wrong. One listed EOL, at the last device, value as specified on the door.

Combination circuits and alarm implications

Most field circuits are series-parallel: series copper plus parallel devices . Collapse the parallel loads into one equivalent resistance, add the series wire, apply Ohm’s law for the total current, then expand back to find branch currents and the voltage at the last device (Section 6.1 Example C is that method).

  • Property Series Parallel
  • Path One Two or more
  • Current Same through every part Splits; branches add to I_T
  • Voltage Splits; drops add to V_T Same across every branch
  • Opening one element Entire circuit stops Only that branch stops
  • R_T Sum; always larger than any single R Reciprocal sum; always smaller than smallest R
  • Alarm example Wiring path to the EOL Horns/strobes on a NAC; NO contacts across an IDC

Opens and shorts, restated for these two circuits:

An open in a series path is trouble on both IDC and NAC (supervision current cannot return).

A short across a conventional IDC is typically an alarm (the panel sees a low-resistance initiating condition).

A short across a NAC is a trouble (and often a short-circuit disconnect of that NAC), because the panel must not dump unprotected current into a bolted pair.

Chapter 7.3 puts a meter on those faults. Chapter 9 covers circuit classes and the return pair on Class A.

Security take-home: a string of normally-closed door contacts is a true series loop. One open contact opens the loop. Fire conventional initiating devices are usually normally open , paralleled, with EOL supervision. Same Ohm’s law; opposite rest condition.

Exam traps

Adding parallel resistances instead of using the reciprocal (or current addition).

Predicting NAC current as if appliances were in series.

Leaving the EOL on the FACU terminals.

Treating a burglary NC loop and a fire NO IDC as the same drawing.

Forgetting that the wiring to the EOL is series even when the devices are parallel.

Section 6.3 turns these currents into watts and watt-hours so Chapter 9 can size batteries.

Loading diagram... Series path to the EOL versus parallel NAC loads

NAC current in mA: parallel loads versus a series mistake