Study guide
10.1 Earth Fault Loop Impedance
NZ EWRB Electrician Registration Regulations
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 Current Exam Facts 1.2 Open-Reference Strategy & Permitted Materials 1.3 Electrician Registration Pathway & Limits of Work 1.4 Which Editions Apply: ESR Schedule 2 & the 13 November 2025 Update
2 Electricity Act & EWRB Framework
2.1 Electricity Act 1992 Framework 2.2 EWRB Role, Register & Registration Classes 2.3 Practising Licence & Electrician Limits of Work
3 Electricity (Safety) Regulations 2010
3.1 ESR 2010 Structure & Key Definitions 3.2 Electrically Safe & Electrically Unsafe 3.3 Duties of Electrical Workers & Competence 3.4 Certification Timeframes & Notification Duties under ESR
4 Prescribed Electrical Work
4.1 What Is Prescribed Electrical Work 4.2 PEW Risk Categories: Low, General, High 4.3 Who May Carry Out and Supervise PEW 4.4 High-Risk Work & Electrical Inspector Requirements
5 Certification Documents (CoC, ESC, RoI)
5.1 Certificate of Compliance (Regulation 65) 5.2 Electrical Safety Certificate (Safe to Connect / Use) 5.3 Record of Inspection (Regulation 72) 5.4 Record-Keeping, Retention & the Certification Chain 5.5 Record-Keeping Duties & the Statutory Clocks (regs 72A, 74E–74H)
6 AS/NZS 3000 Fundamentals
6.1 Structure of AS/NZS 3000 & Open-Book Navigation 6.2 Multiple Earthed Neutral (MEN) System 6.3 Basic Protection vs Fault Protection 6.4 Protective Devices, Discrimination & Coordination
7 RCDs, Shock Protection & Disconnection Times
7.1 RCD Shock-Protection Requirements 7.2 RCD Types, Classification & Installation Contexts 7.3 Disconnection Times (0.4 s / 5 s) & Earth Fault Path 7.4 Damp Situations & Additional Protection
8 Circuits, Maximum Demand & Voltage Drop
8.1 Division of Circuits & Final Subcircuits 8.2 Maximum Demand Principles 8.3 Voltage Drop Requirements & Worked Examples
9 Testing & Verification Core
9.1 Visual Inspection Before Testing 9.2 Continuity of Earthing & Protective Bonding 9.3 Insulation Resistance Testing (500 V DC, 1 MΩ) 9.4 Polarity & Correct Circuit Connections
10 EFLI, RCD Tests & Verification Sequence
10.1 Earth Fault Loop Impedance 10.2 RCD Operation Tests & Prospective Fault Current 10.3 Mandatory Test Sequence & Documentation
11 Safe Isolation & Personal Safety
11.1 Physiological Effects of Current & Shock Factors 11.2 Prove–Test–Prove Safe Isolation 11.3 Lock-Out/Tag-Out & Safety Tag System 11.4 Live-Work Controls, Fault Finding & Unsafe Installations
12 Electrical Codes of Practice & Schedule 2
12.1 NZECP 34 Electrical Safe Distances 12.2 NZECP 50 Repair of Domestic Electrical Equipment 12.3 NZECP 51 Electrical Wiring Work in Domestic Premises 12.4 NZECP 54 Recessed Luminaires & Auxiliary Equipment 12.5 ESR Schedule 2 & Companion Standards Overview
13 Installation Requirements
13.1 Consumer Mains, Point of Supply & Switchboards 13.2 Conductor Identification, Isolation, Labelling & IP Ratings 13.3 Cable Selection (AS/NZS 3008.1.2 NZ Conditions) 13.4 Construction Sites, Appliance Testing & Special Installations 13.5 Periodic Assessment, Warrants of Electrical Fitness & AS/NZS 3019
14 Exam Strategy & Key Numbers
14.1 Must-Know Numbers, Times & Thresholds 14.2 Exam Tactics & Common Traps
10.1 Earth Fault Loop Impedance
Key Takeaways Explain This Topic AI
Earth fault loop impedance (Zs / EFLI) must be low enough for the protective device to disconnect within the required time (ADS)
The fault loop path includes source, active conductors, fault at the equipment, protective earthing, MEN link, and neutral return
Measure Zs live when supply is available; calculate or estimate from design when supply is not yet available
Live EFLI testing requires the MEN link in place and follows dead tests in the Section 8 sequence
High Zs often means poor connections, long/undersized runs, or missing/loose bonds—not “acceptable because an RCD is fitted”
Last updated: August 2026
Purpose of Earth Fault Loop Impedance Testing
After dead tests (visual, continuity, insulation resistance, polarity, correct connections), AS/NZS 3000 Section 8 moves into live verification . Earth fault loop impedance (EFLI; often written Zs at the circuit or point of test) answers one safety question:
Under an earth fault at this point, is the impedance of the complete return path low enough that fault current will operate the protective device within the required disconnection time ?
If Zs is too high, fault current is too low. The MCB, fuse, or other overcurrent device may not clear in time (or at all under some conditions). Exposed conductive parts can remain at hazardous touch voltage while the fault persists. That is a failure of automatic disconnection of supply (ADS) —the core of fault protection in MEN installations.
Classic teaching pairs EFLI with the disconnection-time regime from earlier chapters: typically 0.4 s for many final subcircuits and 5 s for distribution/submains contexts (confirm exact application in your permitted AS/NZS 3000 edition). RCD residual protection is additional protection in many cases; it does not replace the need for a competent earth-fault loop for ADS design and verification where the rules require it.
Path Components of the Earth Fault Loop
Mentally walk the loop for a single-phase final circuit fault to earth:
- Segment What contributes impedance
- Source / distribution network Utility transformer and upstream supply impedance
- Active path Consumer mains, submains, and final-circuit active conductors to the fault point
- Fault Active-to-exposed-conductive-part (or earth) at the equipment
- Protective earthing path Circuit PEC, earth bar, main earthing conductor arrangement
- MEN link Neutral–earth link at the main earthing point
- Neutral return Neutral conductors back toward the source
Zs is the sum of these contributions as seen from the test point. A sound PE conductor can still yield high Zs if the MEN link is missing , a neutral joint is poor, or the run is long and undersized. Continuity of earthing (dead test) proves the metal path is continuous; EFLI proves the whole live loop is low enough for protective operation under actual supply conditions.
AS/NZS 3017 is the methods companion for instrument technique, probe points, and interpretation aligned with Section 8 outcomes. On the open-book exam, treat 3000 §8 as “what must be verified” and 3017 as “how the test is performed safely and consistently.”
- Measurement vs Calculation
- When supply is available (live measurement)
Use a suitable multifunction installation tester on the energised installation after dead tests pass and the installation is safe to liven for verification
Measure Zs (or related loop/impedance values per instrument method) at relevant points—commonly final-circuit extremities, socket outlets, fixed equipment earth points, and as required at distribution points
Compare results against maximum Zs limits for the protective device rating/type and the applicable disconnection time (tables and rules in your permitted edition / manufacturer data / AS/NZS guidance)
When supply is not yet available (design / calculation)
Calculate or estimate loop impedance from cable lengths, conductor sizes, and known or assumed external source impedance (Ze / external supply contribution)
Design selection of cable CSA and protective devices must leave headroom so that measured Zs after construction still meets disconnection requirements
Calculation is not a permanent substitute for live verification once the installation can be safely energised—exam stems often expect both: design competence and post-energisation measurement where required
Relationship to Disconnection Times and Trip Curves
Protective devices clear on current vs time characteristics:
Higher fault current (lower Zs at a given voltage) → faster operation on the device curve
Maximum Zs tables encode the impedance that still produces enough current for the device to operate within 0.4 s or 5 s as applicable
Using the wrong device type/rating, or comparing Zs to the wrong table, produces false “pass” confidence
Exam habit: link high Zs → low If → slow or failed disconnection , not “high ohms means good insulation.” EFLI ohms are loop impedance under fault , unrelated to megohm IR values.
Live Test Precautions — MEN Must Be in Place
EFLI is a live test (≈ 8.3.9 ). Prerequisites:
- Dead tests complete and satisfactory (visual through correct connections as applicable)
- Installation in a safe construction state for energisation
MEN link restored and confirmed at the main earthing point— live EFLI testing with MEN open is incorrect practice for a normal MEN installation verification story
Competent prove-live / instrument connection; PPE and isolation awareness for nearby live parts
Never “remove the MEN to see what happens” as a routine test shortcut. The MEN is part of the designed fault-return path. Continuity and visual stages already checked its presence; live testing assumes it is in circuit .
High Zs Causes Candidates Must Diagnose
- Common cause Why Zs rises
- Poor connections High-resistance joints on active, neutral, earth bar, MEN, or equipment terminals
- Long runs / undersized conductors Excess conductor impedance on long finals or submains
- Missing or loose bonds / PECs Fault current diverted poorly or path incomplete
- Open or high-R neutral joints Neutral return path degraded
- Wrong test point / method Measuring upstream of a series impedance or on a different circuit
Remediate and retest —do not certify a circuit that fails maximum Zs limits for its protective device and disconnection requirement. An RCD may still trip on residual current in some fault modes, but RCD presence does not excuse an EFLI fail when the verification requirement is ADS by overcurrent within time for that circuit arrangement.
- Exam traps
- Confusing Zs (low ohms good) with IR (high MΩ good)
- Skipping EFLI because “all circuits have 30 mA RCDs”
- Live testing before dead tests or with MEN removed
- Accepting high Zs as “old installation character” without remediation
- Study note
Sketch the MEN fault loop once from socket earth pin → earth bar → MEN → neutral → supply → active → fault. Flag 8.3.9 and maximum Zs / disconnection-time tables in your permitted AS/NZS 3000. Know that low Zs supports ADS; high Zs is a fail until fixed.