4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)

Oklahoma Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety

1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection

2 Chapter 2: General Electrical Theory & Calculations

2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments

3 Chapter 3: General Installation Requirements (NEC Article 110)

3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable

4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)

4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)

5 Chapter 5: Services & Service Equipment (NEC Article 230)

5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)

6 Chapter 6: Electrical Load Calculations (NEC Article 220)

6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)

7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)

7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)

8 Chapter 8: Grounding and Bonding (NEC Article 250)

8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)

9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)

9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)

10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems

10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)

11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)

11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)

12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)

12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)

13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)

13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)

14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems

14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)

4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)

Key Takeaways Explain This Topic AI

Feeder conductors and overcurrent protective devices must be sized with an allowable ampacity not less than 100% of the non-continuous load plus 125% of the continuous load (NEC 215.2(A)(1) and 215.3).

NEC 215.2(A) Informational Note 2 and 210.19(A) Informational Note 4 recommend sizing conductors to limit feeder voltage drop to a maximum of 3%, and total combined feeder and branch circuit voltage drop to a maximum of 5% for overall system efficiency.

Overhead conductor clearances from grade under NEC 225.18 require minimums of 10 feet above pedestrian walkways, 12 feet over residential driveways, 18 feet over public roads and commercial truck areas, and 24.5 feet over railroad tracks.

NEC 225.26 strictly prohibits the use of vegetation, such as live trees, for the support of overhead conductor spans or outdoor lighting equipment.

A separate building or structure supplied by a feeder must have a disconnecting means (NEC 225.31) with a maximum of six switches or circuit breakers (225.33), an equipment grounding conductor run with the feeder, and an isolated neutral at the subpanel (NEC 250.32).

Last updated: August 2026

Outside Branch Circuits & Feeders (NEC Articles 215 & 225)

Feeders are the primary arteries of an electrical distribution network, carrying bulk power from the service equipment or separately derived source to downstream subpanels and branch circuit overcurrent devices. When feeders and branch circuits extend outdoors to supply remote buildings, security lighting, or detached workshops, they encounter extreme physical stresses including wind loads, ice accumulation, thermal expansion, vehicle traffic, and environmental deterioration. NEC Article 215 (Feeders) and Article 225 (Outside Branch Circuits and Feeders) establish the engineering standards required to ensure electrical safety and long-term reliability.

1. Feeder Conductor Sizing & Overcurrent Protection (NEC Article 215)

A feeder consists of all circuit conductors between the service equipment, the source of a separately derived system, or other power supply source, and the final branch-circuit overcurrent device. +-----------------------------------------------------------------------------+

  • | FEEDER SIZING FORMULA (NEC 215.2(A)(1)) |
  • | |
  • | MINIMUM FEEDER AMPACITY: |
  • | Ampacity >= (100% of Non-Continuous Load) + (125% of Continuous Load) |
  • | |
  • | FEEDER OVERCURRENT PROTECTION (NEC 215.3): |
  • | OCPD Rating >= (100% of Non-Continuous Load) + (125% of Continuous Load) |
  • +-----------------------------------------------------------------------------+

Feeder Neutral Sizing (NEC 220.61):

The feeder grounded conductor (neutral) must be sized to carry the maximum unbalanced load between the neutral and any one ungrounded conductor.

Demand Reductions Permitted: In dwellings, a 70% demand factor is applied to electric range and electric dryer neutral loads per NEC 220.61(B)(1).

Harmonic Non-Linear Loads (220.61(C)(2)): No neutral reduction is permitted for that portion of the load consisting of non-linear loads (LED lighting drivers, computers, VFDs), as third-order triplen harmonics add constructively in the neutral conductor.

2. Feeder Voltage Drop Calculations (NEC 215.2(A) Inf. Note 2)

While the NEC does not make voltage drop mandatory for general branch circuits and feeders in the base code text, Informational Note 2 to NEC 215.2(A) and Informational Note 4 to NEC 210.19(A) specify critical engineering design standards:

Maximum Feeder Voltage Drop: Not to exceed 3% under full design load.

Maximum Combined Feeder + Branch Circuit Voltage Drop: Not to exceed 5% total to the farthest outlet. +-----------------------------------------------------------------------------+

  • | VOLTAGE DROP CALCULATION FORMULAS |
  • | |
  • | SINGLE-PHASE CIRCUITS: THREE-PHASE CIRCUITS: |
  • | 2 x K x I x L 1.732 x K x I x L |
  • | VD = ----------------- VD = -------------------- |
  • | CM CM |
  • | |
  • | Where: |
  • | - K = Conductor Resistivity (Copper = 12.9 ohms-cmil/ft; Al = 21.2) |
  • | - I = Circuit Load Current in Amperes |
  • | - L = One-Way Length of Feeder in Feet |
  • | - CM = Conductor Cross-Sectional Area in Circular Mils (Chapter 9 Table 8)|
  • +-----------------------------------------------------------------------------+

Worked Voltage Drop Example:

A 240V single-phase commercial feeder carries an 80A continuous load a one-way distance of 180 feet using #3 AWG Copper conductors ( C M = 52 , 620 CM = 52,620 CM = 52 , 620 from Chapter 9, Table 8). V D = 2 × 12.9 × 80 × 180 52 , 620 = 371 , 520 52 , 620 = 7.06 Volts VD = \frac{2 \times 12.9 \times 80 \times 180}{52,620} = \frac{371,520}{52,620} = \mathbf{7.06\text{ Volts}} V D = 52 , 620 2 × 12.9 × 80 × 180 ​ = 52 , 620 371 , 520 ​ = 7.06 Volts % V D = ( 7.06 V 240 V ) × 100 = 2.94 % \%VD = \left(\frac{7.06\text{ V}}{240\text{ V}}\right) \times 100 = \mathbf{2.94\%} % V D = ( 240 V 7.06 V ​ ) × 100 = 2.94%

Because 2.94 % < 3.0 % 2.94\% < 3.0\% 2.94% < 3.0% , the feeder complies with the 3% maximum recommended voltage drop.

3. Outside Overhead Conductors & Clearances (NEC Article 225)

Overhead conductors running between buildings, poles, or structures must maintain mandatory physical clearances to prevent contact with vehicles, pedestrians, and machinery: +-----------------------------------------------------------------------------+

  • | OVERHEAD CLEARANCES ABOVE FINISHED GRADE (NEC 225.18) |
  • | |
  • | [24.5 FEET] --- Over Track Rails of Railroads |
  • | |
  • | [18.0 FEET] --- Over Public Streets, Roads, Alleys, Parking Areas Subject |
  • | to Truck Traffic, & Commercial Driveways |
  • | |
  • | [15.0 FEET] --- Over Residential Driveways & Commercial Non-Truck Areas |
  • | (Circuits > 300V to Ground) |
  • | |
  • | [12.0 FEET] --- Over Residential Property, Driveways & Commercial |
  • | Non-Truck Areas (Circuits <= 300V to Ground) |
  • | |
  • | [10.0 FEET] --- Above Finished Grade, Sidewalks, or Pedestrian-Only |
  • | Platforms (Circuits <= 150V to Ground) |
  • +-----------------------------------------------------------------------------+

Clearances from Buildings (NEC 225.19):

Roofs (225.19(A)): Overhead conductors must maintain a vertical clearance of not less than 8.0 feet (2.44 m) above the roof surface. For steep-pitch roofs (slope not less than 4 inches in 12 inches), clearance may be reduced to 3.0 feet (914 mm) .

Roof Overhang Exception: Where a feeder passes over not more than 4 feet of roof overhang and terminates in a through-the-roof raceway/mast, clearance may be reduced to 18 inches (450 mm) .

Windows, Doors, & Fire Escapes (225.19(D)): Conductors shall have a clearance of at least 3.0 feet (900 mm) from windows that are designed to open, doors, porches, balconies, or fire escapes.

Overhead Spans & Conductor Minimum Sizes (NEC 225.6):

Spans Up to 50 Feet: Minimum #10 AWG Copper or #8 AWG Aluminum .

Spans Over 50 Feet: Minimum #8 AWG Copper or #6 AWG Aluminum .

Festoon Lighting Spans (225.6(B)): Overhead conductors for festoon lighting must be at least #12 AWG and must be supported by a messenger wire with listed strain insulators if the span exceeds 40 feet .

Support on Vegetation Prohibited (NEC 225.26):

"Vegetation such as trees shall not be used for support of overhead conductor spans."

Electricians must never attach overhead spans, messenger wires, or outside feeder cables to live trees. Trees sway in storms, grow continuously, and shed limbs, creating extreme shock, fire, and wire-drop hazards.

4. Disconnecting Means for Separate Buildings (NEC 225.31–225.39 & 250.32)

When a feeder or branch circuit supplies a detached building or structure (such as a detached garage, commercial warehouse, or agricultural barn), NEC 225 mandates a local disconnecting means: +-----------------------------------------------------------------------------+

  • | DETACHED STRUCTURE DISCONNECT & GROUNDING (NEC 225 & 250.32) |
  • | |
  • | [MAIN BUILDING PANEL] [DETACHED BUILDING SUBPANEL] |
  • | Feeder Hot 1 ----------------------------> [ Main Disconnect / Breaker ] |
  • | Feeder Hot 2 ----------------------------> [ Max 6 Disconnects (225.33)] |
  • | Feeder Neutral --------------------------> [ ISOLATED NEUTRAL BUSBAR ] |
  • | Equipment Ground (EGC) ------------------> [ EQUIPMENT GROUND BUSBAR ] |
  • | | |
  • | [ Grounding Electrode System]|
  • | (Ground Rods / Concrete Ufer)|
  • +-----------------------------------------------------------------------------+

Detached Building Disconnect Rules:

Location (NEC 225.32): Installed at a readily accessible location either outside the building/structure or inside nearest the point of entrance of the supply conductors.

Maximum Number of Disconnects (NEC 225.33 - "Rule of Six"): The disconnecting means shall consist of not more than six switches or six circuit breakers mounted in a single enclosure or group of separate enclosures.

Grouping (NEC 225.34): The two to six disconnects must be grouped together.

Minimum Disconnect Ratings (NEC 225.39):

Single-circuit installation: 15 Amperes minimum .

Two-circuit installation: 30 Amperes minimum .

Single-family dwelling: 100 Amperes 3-wire minimum .

All other installations (commercial/workshops): 60 Amperes minimum .

Grounding & Neutral Isolation (NEC 250.32):

An Equipment Grounding Conductor (EGC) must be run with the feeder.

A Grounding Electrode System (ground rods, ground ring, or concrete-encased electrode) must be established at the detached building.

The Neutral and EGC must remain ISOLATED at the subpanel. The main bonding jumper is NOT installed; bonding neutral to ground at a subpanel creates dangerous parallel ground return paths.

Loading diagram... Outside Overhead Conductor Clearances Profile (NEC 225.18 & 225.19)