6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)

Oklahoma Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety

1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection

2 Chapter 2: General Electrical Theory & Calculations

2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments

3 Chapter 3: General Installation Requirements (NEC Article 110)

3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable

4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)

4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)

5 Chapter 5: Services & Service Equipment (NEC Article 230)

5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)

6 Chapter 6: Electrical Load Calculations (NEC Article 220)

6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)

7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)

7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)

8 Chapter 8: Grounding and Bonding (NEC Article 250)

8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)

9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)

9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)

10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems

10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)

11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)

11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)

12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)

12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)

13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)

13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)

14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems

14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)

6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)

Key Takeaways Explain This Topic AI

Commercial receptacle loads are calculated under NEC 220.14(I) at 180 VA per strap/yoke (whether single, duplex, or triplex on a single yoke), with demand factors under Table 220.47 allowing the first 10 kVA at 100% and the excess over 10 kVA at 50%.

Commercial kitchen equipment (cooking, dishwashing, booster heaters, water heaters) is calculated under NEC 220.56 and Table 220.56 with demand factors scaling from 100% for 1-2 appliances down to 65% for 6 or more appliances, provided the calculated feeder load is never less than the sum of the two largest appliances.

Show window lighting requires a minimum of 200 VA per linear foot under NEC 220.14(G) and 220.43(A); commercial sign lighting mandates at least 1,200 VA per 220.14(F) and 600.5; and track lighting is sized at 150 VA per 2 feet of track under 220.43(B).

Multi-family dwelling feeder and service loads can be calculated using the Optional Method of NEC 220.84 if the building has 3 or more dwelling units equipped with electric cooking and heating/cooling, applying Table 220.84 demand factors based on total unit count.

Continuous commercial loads (such as general store lighting, illuminated signs, and display windows) must be multiplied by 125% per NEC 210.20 and 215.2, and service feeders supplying motor loads must include 125% of the largest motor full-load current per NEC 430.24.

Last updated: August 2026

Commercial & Multi-Family Load Calculations (NEC Article 220)

Commercial and multi-family electrical installations present complex load dynamics that differ significantly from single-family residential dwellings. Commercial facilities incorporate continuous retail lighting, high-density receptacle layouts, dedicated show windows, commercial kitchen equipment, and three-phase motor loads. Multi-family buildings feature high unit diversity that allows substantial demand reductions on main services.

On the Oklahoma Journeyman Electrician examination, questions in this domain test your ability to apply commercial demand factors, size three-phase services, and execute multi-family calculations.

1. Commercial Receptacle Loads (NEC 220.14(I) & 220.47)

In non-dwelling occupancies, receptacle loads are calculated on a volt-amperes per yoke (strap) basis: +-----------------------------------------------------------------------------+

  • | COMMERCIAL RECEPTACLE LOAD RULES (NEC 220.14(I)) |
  • | |
  • | [YOKE / STRAP RATING] |
  • | • 180 VA for each single receptacle or duplex receptacle on ONE yoke. |
  • | • 360 VA for a two-gang box with two duplex receptacles (TWO yokes). |
  • | • Multi-outlet Assemblies (220.14(H)): 180 VA for each 5 ft standard, |
  • | or 180 VA for each 1 ft where appliances are used simultaneously. |
  • | |
  • | [TABLE 220.47 RECEPTACLE DEMAND FACTORS] |
  • | • First 10 kVA (10,000 VA) or less: 100% (1.00) |
  • | • Remainder over 10 kVA (10,000 VA): 50% (0.50) |
  • +-----------------------------------------------------------------------------+

Commercial Receptacle Calculation Example:

A commercial office has 150 standard duplex receptacle outlets installed on individual yokes.

Connected Receptacle Load: 150 × 180 VA = 27 , 000 VA 150 \times 180\text{ VA} = 27,000\text{ VA} 150 × 180 VA = 27 , 000 VA .

Apply NEC Table 220.47 Demand Factors:

First 10 , 000 VA @ 100 % = 10 , 000 VA 10,000\text{ VA} @ 100\% = 10,000\text{ VA} 10 , 000 VA @100% = 10 , 000 VA

Remaining 17 , 000 VA ( 27 , 000 − 10 , 000 ) @ 50 % = 8 , 500 VA 17,000\text{ VA} (27,000 - 10,000) @ 50\% = 8,500\text{ VA} 17 , 000 VA ( 27 , 000 − 10 , 000 ) @50% = 8 , 500 VA

Net Feeder Receptacle Load: 10 , 000 + 8 , 500 = 18 , 500 VA 10,000 + 8,500 = 18,500\text{ VA} 10 , 000 + 8 , 500 = 18 , 500 VA .

2. Commercial Kitchen Equipment (NEC 220.56 & Table 220.56)

Commercial food service establishments (restaurants, cafeterias, hotel kitchens) operate thermostatically controlled and duty-cycled electric cooking, dishwashing, and water heating equipment. NEC 220.56 permits demand factors from Table 220.56 : +-----------------------------------------------------------------------------+

  • | NEC TABLE 220.56 COMMERCIAL KITCHEN DEMAND FACTORS |
  • | |
  • | NUMBER OF EQUIPMENT UNITS DEMAND FACTOR (%) |
  • | ----------------------------------------------------------------------- |
  • | 1 Unit 100% |
  • | 2 Units 100% |
  • | 3 Units 90% |
  • | 4 Units 80% |
  • | 5 Units 70% |
  • | 6 or More Units 65% |
  • +-----------------------------------------------------------------------------+

The "Two Largest Loads" Rule (NEC 220.56): "In no case shall the feeder or service load be less than the sum of the largest two kitchen equipment loads."

Qualifying Equipment:

Commercial ranges, deep fryers, griddles, ovens, conveyor toasters, commercial dishwashers with booster heaters, electric water heaters, and steam tables.

Kitchen Demand Calculation Example:

A restaurant kitchen contains 6 commercial appliances :

Range ( 15 kW 15\text{ kW} 15 kW ), Deep Fryer ( 10 kW 10\text{ kW} 10 kW ), Convection Oven ( 8 kW 8\text{ kW} 8 kW ), Dishwasher ( 6 kW 6\text{ kW} 6 kW ), Booster Heater ( 9 kW 9\text{ kW} 9 kW ), Food Warmer ( 4 kW 4\text{ kW} 4 kW ).

Total Connected Nameplate: 15 + 10 + 8 + 6 + 9 + 4 = 52 kW = 52 , 000 VA 15 + 10 + 8 + 6 + 9 + 4 = 52\text{ kW} = 52,000\text{ VA} 15 + 10 + 8 + 6 + 9 + 4 = 52 kW = 52 , 000 VA .

Apply Table 220.56 Demand (6+ units = 65%): 52 , 000 VA × 0.65 = 33 , 800 VA 52,000\text{ VA} \times 0.65 = 33,800\text{ VA} 52 , 000 VA × 0.65 = 33 , 800 VA .

Check Minimum Limit (Sum of 2 Largest): Range ( 15 kW 15\text{ kW} 15 kW ) + Deep Fryer ( 10 kW 10\text{ kW} 10 kW ) = 25 kW = 25 , 000 VA 25\text{ kW} = 25,000\text{ VA} 25 kW = 25 , 000 VA .

Since 33 , 800 VA ≥ 25 , 000 VA 33,800\text{ VA} \ge 25,000\text{ VA} 33 , 800 VA ≥ 25 , 000 VA , the net calculated feeder load is 33 , 800 VA 33,800\text{ VA} 33 , 800 VA .

3. Specialized Commercial Loads +-----------------------------------------------------------------------------+

  • | SPECIALIZED COMMERCIAL LOAD SIZING RULES |
  • | |
  • | [SHOW WINDOW LIGHTING (NEC 220.14(G) & 220.43(A))] |
  • | • Sized at 200 VA per linear foot of show window measured at the base. |
  • | • Continuous load: Sized at 125% for branch circuits & feeders. |
  • | |
  • | [OUTLINE & SIGN LIGHTING (NEC 220.14(F) & 600.5)] |
  • | • Minimum 1,200 VA rating per required commercial sign circuit. |
  • | • Continuous load: Sized at 125% for branch circuits & feeders. |
  • | |
  • | [TRACK LIGHTING (NEC 220.43(B))] |
  • | • In non-dwelling occupancies: 150 VA for every 2 ft of track or fraction.|
  • +-----------------------------------------------------------------------------+
  • 4. Multi-Family Dwelling Calculations (NEC 220.84 Optional Method)

For multi-family residential apartment buildings, NEC 220.84 provides an Optional Multi-Family Calculation that applies high diversity factors to the aggregate building load.

Eligibility Criteria (NEC 220.84(A)):

Each dwelling unit is equipped with complete electric cooking equipment.

Each dwelling unit is equipped with electric space heating and/or air conditioning (or individual gas heating with individual metering).

The building contains three (3) or more dwelling units supplied by a common service or feeder. +-----------------------------------------------------------------------------+

  • | NEC TABLE 220.84 MULTI-FAMILY OPTIONAL DEMAND FACTORS |
  • | |
  • | NUMBER OF DWELLING UNITS DEMAND FACTOR (%) |
  • | ----------------------------------------------------------------------- |
  • | 3 to 5 Units 45% |
  • | 6 to 7 Units 44% |
  • | 8 to 10 Units 43% |
  • | 11 to 13 Units 42% |
  • | 14 to 17 Units 41% |
  • | 18 to 21 Units 40% |
  • | 22 to 25 Units 39% |
  • | 26 to 30 Units 38% |
  • | 31 to 35 Units 37% |
  • | 36 to 40 Units 36% |
  • | 41 to 45 Units 35% |
  • | 46 to 50 Units 34% |
  • | 51 to 55 Units 33% |
  • | 56 to 61 Units 32% |
  • | 62 Units and Over 30% |
  • +-----------------------------------------------------------------------------+
  • 5. Master Worked Commercial Example: Retail Clothing Store

Commercial Store Specifications (120/208V 3-Phase 4-Wire Service):

Retail Floor Area: 6 , 000 sq ft 6,000\text{ sq ft} 6 , 000 sq ft ( 3.0 VA/sq ft 3.0\text{ VA/sq ft} 3.0 VA/sq ft standard general lighting)

  • Show Window: 30 linear feet 30\text{ linear feet} 30 linear feet
  • Track Lighting: 60 linear feet 60\text{ linear feet} 60 linear feet
  • General Receptacles: 50 duplex yokes ( 180 VA 180\text{ VA} 180 VA each)
  • Commercial Sign Outlet: 1 sign circuit ( 1 , 200 VA 1,200\text{ VA} 1 , 200 VA minimum)

Breakroom / Kitchenette Appliances (3 units):

  • Commercial Microwave: 1 , 800 VA 1,800\text{ VA} 1 , 800 VA
  • Built-in Dishwasher: 1 , 500 VA 1,500\text{ VA} 1 , 500 VA
  • Electric Water Heater: 3 , 000 VA 3,000\text{ VA} 3 , 000 VA

Rooftop HVAC Units (3-Phase 208V):

Two 5-ton packaged units, full load current = 18 A 18\text{ A} 18 A each at 208 V 208\text{V} 208 V 3-phase

Total HVAC Apparent Power: 2 × ( 208 V × 3 × 18 A ) = 2 × 6 , 485 VA = 12 , 970 VA 2 \times (208\text{V} \times \sqrt{3} \times 18\text{A}) = 2 \times 6,485\text{ VA} = 12,970\text{ VA} 2 × ( 208 V × 3 ​ × 18 A ) = 2 × 6 , 485 VA = 12 , 970 VA

Largest motor 25% addition ( 18 A × 0.25 = 4.5 A 18\text{A} \times 0.25 = 4.5\text{A} 18 A × 0.25 = 4.5 A ): 208 V × 3 × 4.5 A = 1 , 621 VA 208\text{V} \times \sqrt{3} \times 4.5\text{A} = 1,621\text{ VA} 208 V × 3 ​ × 4.5 A = 1 , 621 VA ===============================================================================

  • COMMERCIAL RETAIL STORE LOAD CALCULATION WORKSHEET
  • ===============================================================================

1. GENERAL LIGHTING LOAD (NEC 220.42 & Continuous 125% Factor):

  • 6,000 sq ft × 3.0 VA/sq ft = 18,000 VA
  • Continuous Factor: 18,000 VA × 1.25 = 22,500 VA
  • > Net General Lighting Load = 22,500 VA

2. SHOW WINDOW LIGHTING (NEC 220.14(G), 220.43(A) & Continuous 125%):

  • 30 linear feet × 200 VA/ft = 6,000 VA
  • Continuous Factor: 6,000 VA × 1.25 = 7,500 VA
  • > Net Show Window Load = 7,500 VA

3. TRACK LIGHTING (NEC 220.43(B) & Continuous 125%):

  • 60 ft / 2 ft = 30 segments × 150 VA = 4,500 VA
  • Continuous Factor: 4,500 VA × 1.25 = 5,625 VA
  • > Net Track Lighting Load = 5,625 VA

4. RECEPTACLE LOAD (NEC 220.14(I) & Table 220.47 Demand):

  • 50 yokes × 180 VA = 9,000 VA
  • Table 220.47 Demand (First 10,000 VA @ 100%) = 9,000 VA
  • > Net Receptacle Load = 9,000 VA

5. COMMERCIAL SIGN OUTLET (NEC 220.14(F), 600.5 & Continuous 125%):

  • 1 Required Sign Circuit = 1,200 VA
  • Continuous Factor: 1,200 VA × 1.25 = 1,500 VA
  • > Net Sign Load = 1,500 VA

6. KITCHEN APPLIANCES (NEC 220.56 & Table 220.56):

  • Microwave (1.8k) + Dishwasher (1.5k) + Water Heater (3.0k) = 6,300 VA
  • Apply Table 220.56 (3 appliances @ 90% demand): 6,300 × 0.90 = 5,670 VA
  • Check 2 Largest (3,000 + 1,800 = 4,800 VA < 5,670 VA -> OK)
  • > Net Kitchen Appliance Load = 5,670 VA

7. ROOFTOP HVAC & MOTOR LOADS (NEC 430.24):

  • Base HVAC Load (Two 18A 208V 3-Phase Units) = 12,970 VA
  • Largest Motor 25% Addition = 1,621 VA
  • --------------------------------------------------------------
  • > Net HVAC & Motor Load = 14,591 VA
  • ===============================================================================
  • TOTAL CALCULATED COMMERCIAL SERVICE LOAD = 66,386 VA

THREE-PHASE SERVICE ENTRANCE CURRENT CALCULATION (120/208V 3-Phase):

  • Current (Amperes) = Total VA / (Line Voltage × √3)
  • Current (Amperes) = 66,386 VA / (208 Volts × 1.73205)
  • Current (Amperes) = 66,386 VA / 360.267 Volts = 184.27 Amperes
  • STANDARD COMMERCIAL SERVICE RATING: 200A or 225A 3-Phase 4-Wire Service
  • ===============================================================================

Loading diagram... Commercial & Multi-Family Load Calculation Architecture