6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52)
Oklahoma Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety
1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection
2 Chapter 2: General Electrical Theory & Calculations
2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments
3 Chapter 3: General Installation Requirements (NEC Article 110)
3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable
4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)
4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)
5 Chapter 5: Services & Service Equipment (NEC Article 230)
5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)
6 Chapter 6: Electrical Load Calculations (NEC Article 220)
6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)
7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)
7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)
8 Chapter 8: Grounding and Bonding (NEC Article 250)
8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)
9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)
9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)
10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems
10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)
11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)
11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)
12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)
12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)
13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)
13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)
14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems
14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)
6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52)
Key Takeaways Explain This Topic AI
NEC 220.41 sets the dwelling unit minimum unit load at 3 volt-amperes per square foot, and that load already covers general-use receptacles rated 20 amperes or less plus the specified lighting outlets — no separate calculation is added for them.
NEC 220.11(C) computes floor area from outside dimensions, excluding open porches and excluding garages and unfinished spaces unless the area is adaptable for future use as a habitable room or occupiable space.
Non-dwelling unit lighting loads come from Table 220.42(A), whose values were substantially reduced in the 2023 edition — schools, universities, and sports arenas dropped from 3 VA/ft² to 1.5 VA/ft².
NEC 220.52 requires a minimum of two 20-ampere small-appliance branch circuits and one 20-ampere laundry branch circuit in a dwelling, each calculated at 1,500 volt-amperes.
Table 220.45 demand factors apply to the general illumination portion of the load: for dwelling units the first 3,000 VA is taken at 100 percent and the remainder to 120,000 VA at 35 percent.
Last updated: August 2026
General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52)
Accurate electrical load calculation is the cornerstone of safe power distribution design. Under Article 220 of the National Electrical Code (NEC), load calculations dictate the sizing of branch circuit conductors, feeder cables, service entrance equipment, panelboards, and overcurrent protective devices. Sizing equipment too small leads to severe overcurrent tripping, hazardous conductor overheating, and nuisance outages; oversizing leads to excessive material costs and code non-compliance.
On the Oklahoma Journeyman Electrician examination, Article 220 questions require mastery of general lighting loads, floor area measurement rules, dedicated residential branch circuits, and the mathematical application of demand factors.
1. Fundamentals of Load Calculations & Continuous Loads
Before calculating specific branch circuit or feeder loads, electricians must distinguish between fundamental load classifications and standard operating conditions:
Continuous Load (NEC Article 100 & 210.19(A), 215.2(A), 230.42(A)): A load where the maximum current is expected to continue for 3 hours or more (e.g., commercial office lighting, store show windows, electric vehicle charging, illuminated signs). Branch circuit and feeder conductors supplying continuous loads must be sized to carry 125% of the continuous load plus 100% of the non-continuous load ( I feeder = ( I continuous × 1.25 ) + I non-continuous I_{\text{feeder}} = (I_{\text{continuous}} \times 1.25) + I_{\text{non-continuous}} I feeder = ( I continuous × 1.25 ) + I non-continuous ).
Non-Continuous Load: Equipment that operates intermittently or for intervals shorter than 3 hours (e.g., residential kitchen appliances, garbage disposals, residential water heaters, bathroom exhaust fans).
Connected Load vs. Calculated Demand Load: The connected load is the simple arithmetic sum of all electrical equipment nameplates. The calculated demand load applies code-recognized diversity and demand factors reflecting the statistical reality that not all loads operate simultaneously at full capacity.
2. Floor Area Determination (NEC 220.11)
General lighting loads for most occupancies are calculated on a volt-amperes per square foot (VA/sq ft) basis. NEC 220.11 establishes precise structural measurement rules: +-----------------------------------------------------------------------------+
- | NEC 220.11 FLOOR AREA MEASUREMENT RULES |
- | |
- | [OUTSIDE DIMENSIONS OF BUILDING] |
- | • Measured from the exterior building surfaces for each floor level. |
- | |
- | [INCLUDED SPACES] [EXCLUDED SPACES] |
- | • All finished living areas • Open porches & breezeways |
- | • Habitable rooms, hallways, closets • Attached/detached garages |
- | • Finished basements & usable spaces • Unfinished basements not |
- | • Unfinished spaces adaptable for adaptable for future use |
- | future habitable living quarters • Unused/uninhabitable attics |
- +-----------------------------------------------------------------------------+
Practical Measurement Application:
A two-story single-family home has outside exterior dimensions of 30 ft × 50 ft 30\text{ ft} \times 50\text{ ft} 30 ft × 50 ft , an attached two-car garage measuring 20 ft × 22 ft 20\text{ ft} \times 22\text{ ft} 20 ft × 22 ft , a covered open front porch measuring 8 ft × 20 ft 8\text{ ft} \times 20\text{ ft} 8 ft × 20 ft , and an unfinished basement measuring 30 ft × 50 ft 30\text{ ft} \times 50\text{ ft} 30 ft × 50 ft designed for future living room conversion.
First Floor Area: 30 ft × 50 ft = 1 , 500 sq ft 30\text{ ft} \times 50\text{ ft} = 1,500\text{ sq ft} 30 ft × 50 ft = 1 , 500 sq ft
Second Floor Area: 30 ft × 50 ft = 1 , 500 sq ft 30\text{ ft} \times 50\text{ ft} = 1,500\text{ sq ft} 30 ft × 50 ft = 1 , 500 sq ft
Unfinished Basement (adaptable for future use): 30 ft × 50 ft = 1 , 500 sq ft 30\text{ ft} \times 50\text{ ft} = 1,500\text{ sq ft} 30 ft × 50 ft = 1 , 500 sq ft
Garage & Open Porch: Excluded per NEC 220.11.
Total Calculation Area: 1 , 500 + 1 , 500 + 1 , 500 = 4 , 500 sq ft 1,500 + 1,500 + 1,500 = 4,500\text{ sq ft} 1 , 500 + 1 , 500 + 1 , 500 = 4 , 500 sq ft .
- 3. General Lighting Loads (NEC 220.41 Dwellings & 220.42 Non-Dwellings)
- Dwelling Unit General Lighting (NEC 220.41)
For one-family, two-family, and multi-family dwelling units, the general lighting load is calculated at 3 VA per square foot 3\text{ VA per square foot} 3 VA per square foot ( 33 VA/m 2 33\text{ VA/m}^2 33 VA/m 2 ).
Critical Code Rule (NEC 220.41): In dwelling units, the 3 VA/sq ft 3\text{ VA/sq ft} 3 VA/sq ft unit load encompasses:
All general lighting fixtures and luminaires.
All general-use 15A and 20A receptacle outlets (such as in bedrooms, living rooms, hallways, basements, and home offices).
Outdoor convenience receptacles and bathroom receptacles. No additional load calculations are added for general-use receptacles in dwelling units. Dedicated small appliance and laundry circuits are calculated separately under 220.52.
Non-Dwelling Unit General Lighting (NEC 220.42)
For commercial, industrial, and institutional occupancies, the minimum unit lighting load comes from Table 220.42(A) , indexed by occupancy type. Two things about this table matter more than any single value:
The numbers changed in the 2023 edition. The unit loads were substantially reduced to track modern lighting power densities — schools, universities, and sports arenas dropped from 3 VA/ft² to 1.5 VA/ft² , and banks and office buildings fell from the 3-plus range into the low 1s. Any VA/ft² figure memorized from a 2020-based course is wrong on this exam. Oklahoma tests the 2023 NEC as adopted by the OUBCC.
You do not have to memorize it. This is an open-book exam. Tab Table 220.42(A) and read the row. What you must know cold is which table to open and how to apply it.
220.42(B) additionally permits the lighting load to be calculated using the values from the applicable energy code where the building is designed and constructed to comply with that energy code, subject to the conditions stated there — which is why a design engineer's calculation can legitimately show a smaller lighting load than the base table.
What to open For what
220.41 Dwelling unit minimum unit load — 3 VA/ft² , and it already includes general-use receptacles rated 20 A or less and the specified lighting outlets
- Table 220.42(A) Non-dwelling unit load by occupancy type (2023 values)
- 220.42(B) Energy-code-based alternative calculation
- Table 220.45 Demand factors applied to the general illumination portion of the calculated load
Warning
The 2023 NEC renumbered this whole area. If you learned load calculations on the 2020 Code, the section numbers you memorized will send you to the wrong page:
- 2020 NEC 2023 NEC
- 220.14(J) — dwelling unit lighting/receptacle load 220.41
- 220.12 / Table 220.12 — non-dwelling lighting load 220.42 / Table 220.42(A)
- 220.42 / Table 220.42 — general lighting demand factors 220.45 / Table 220.45
- 220.44 / Table 220.44 — non-dwelling receptacle demand 220.47 / Table 220.47
- 220.5(C) — floor area 220.11(C)
- 4. Small Appliance & Laundry Branch Circuits (NEC 210.11(C) & 220.52)
In addition to general lighting, the NEC mandates dedicated 20-ampere branch circuits in dwelling units to handle high-draw localized loads: +-----------------------------------------------------------------------------+
- | MANDATORY RESIDENTIAL 20A DEDICATED BRANCH CIRCUITS |
- | |
- | [SMALL APPLIANCE CIRCUITS] [LAUNDRY CIRCUIT] |
- | • NEC 210.11(C)(1) & 220.52(A) • NEC 210.11(C)(2) & 220.52(B) |
- | • Minimum: TWO (2) 20A circuits • Minimum: ONE (1) 20A circuit |
- | • Rating: 1,500 VA per circuit • Rating: 1,500 VA per circuit |
- | • Total Minimum = 3,000 VA • Total Minimum = 1,500 VA |
- | • Serves kitchen countertop, pantry, • Serves laundry room receptacle |
- | breakfast room, dining area outlets only |
- | • No lighting or other outlets allowed • No other outlets allowed |
- | |
- | [BATHROOM CIRCUIT (210.11(C)(3))] [GARAGE CIRCUIT (210.11(C)(4))] |
- | • Minimum: ONE (1) 20A circuit • Minimum: ONE (1) 20A circuit |
- | • Serves bathroom receptacle outlets • Serves garage receptacles |
- | • Load included in 3 VA/sq ft • Load included in 3 VA/sq ft |
- +-----------------------------------------------------------------------------+
Small Appliance Load Rules (NEC 220.52(A)):
Every dwelling unit must have at least two 20-ampere small appliance branch circuits .
In the feeder and service calculation, each small appliance circuit is assessed at 1 , 500 VA 1,500\text{ VA} 1 , 500 VA (minimum 2 × 1 , 500 VA = 3 , 000 VA 2 \times 1,500\text{ VA} = 3,000\text{ VA} 2 × 1 , 500 VA = 3 , 000 VA ).
If an installation includes 3 or 4 small appliance circuits, each additional circuit adds 1 , 500 VA 1,500\text{ VA} 1 , 500 VA to the connected general load.
Laundry Branch Circuit Rules (NEC 220.52(B)):
Every dwelling unit must have at least one 20-ampere laundry branch circuit supplying receptacle outlets for laundry equipment.
In the feeder/service calculation, the laundry circuit is assessed at 1 , 500 VA 1,500\text{ VA} 1 , 500 VA minimum.
Exception: A laundry circuit is not required in individual dwelling units of multi-family buildings where commercial laundry facilities are provided on the premises.
5. Lighting Demand Factors (NEC Table 220.45)
In standard calculation methods, general lighting, small appliance, and laundry loads are combined into a single total and derated using NEC Table 220.45 . +-----------------------------------------------------------------------------+
- | NEC TABLE 220.45 LIGHTING DEMAND FACTOR SCHEDULE |
- | |
- | OCCUPANCY TYPE PORTION OF VA LOAD DEMAND FACTOR |
- | ----------------------------------------------------------------------- |
- | Dwelling Units First 3,000 VA or less 100% |
- | (One-family, two-family, From 3,001 to 120,000 VA 35% |
- | multi-family) Remainder over 120,000 VA 25% |
- | ----------------------------------------------------------------------- |
- | Hospitals First 50,000 VA or less 40% |
- | Remainder over 50,000 VA 20% |
- | ----------------------------------------------------------------------- |
- | Hotels and Motels First 20,000 VA or less 50% |
- | (including apartment From 20,001 to 100,000 VA 40% |
- | houses w/o cooking) Remainder over 100,000 VA 30% |
- | ----------------------------------------------------------------------- |
- | Warehouses (Storage) First 12,500 VA or less 100% |
- | Remainder over 12,500 VA 50% |
- | ----------------------------------------------------------------------- |
- | All Other Occupancies Total Volt-Amperes 100% |
- | (Commercial, Retail, etc.) |
- +-----------------------------------------------------------------------------+
- 6. Step-by-Step Worked Calculation Examples
- Example 1: Single-Family Dwelling General Lighting & Appliance Load
Calculate the net general lighting, small appliance, and laundry feeder demand load for a single-family dwelling with 3 , 200 sq ft 3,200\text{ sq ft} 3 , 200 sq ft of living area, 3 small appliance circuits , and 1 laundry circuit . [STEP 1: Calculate General Lighting Load (NEC 220.41)]
3,200 sq ft × 3 VA/sq ft = 9,600 VA
- [STEP 2: Calculate Small Appliance & Laundry Loads (NEC 220.52)]
- Small Appliance: 3 circuits × 1,500 VA = 4,500 VA
- Laundry Circuit: 1 circuit × 1,500 VA = 1,500 VA
- [STEP 3: Calculate Total Connected General Load]
- Total = 9,600 VA + 4,500 VA + 1,500 VA = 15,600 VA
- [STEP 4: Apply NEC Table 220.45 Demand Factors]
- Tier 1 (First 3,000 VA @ 100%): 3,000 VA × 1.00 = 3,000 VA
- Tier 2 (Remaining 12,600 VA @ 35%): 12,600 VA × 0.35 = 4,410 VA
- ----------------------------------------------------------------------
- Net Calculated Feeder / Service Load = 7,410 VA
- Example 2: Commercial Storage Warehouse General Lighting Feeder Load
A commercial storage warehouse has an area of 60 , 000 sq ft 60,000\text{ sq ft} 60 , 000 sq ft with a general lighting unit load of 0.25 VA/sq ft 0.25\text{ VA/sq ft} 0.25 VA/sq ft per NEC Table 220.42(A). [STEP 1: Calculate Total Connected Lighting Load]
60,000 sq ft × 0.25 VA/sq ft = 15,000 VA
- [STEP 2: Apply Table 220.45 Warehouse Demand Factors]
- Tier 1 (First 12,500 VA @ 100%): 12,500 VA × 1.00 = 12,500 VA
- Tier 2 (Remaining 2,500 VA @ 50%): 2,500 VA × 0.50 = 1,250 VA
- ----------------------------------------------------------------------
- Net Calculated Feeder Lighting Load = 13,750 VA
- Example 3: 80-Room Hotel General Lighting Feeder Load
An 80-room hotel has a total connected general lighting load of 95 , 000 VA 95,000\text{ VA} 95 , 000 VA based on guest room and common area square footage. [STEP 1: Total Connected Lighting Load = 95,000 VA]
- [STEP 2: Apply Table 220.45 Hotel / Motel Demand Factors]
- Tier 1 (First 20,000 VA @ 50%): 20,000 VA × 0.50 = 10,000 VA
- Tier 2 (20,001 to 95,000 VA = 75,000 VA @ 40%): 75,000 × 0.40 = 30,000 VA
- ----------------------------------------------------------------------
- Net Calculated Feeder Lighting Load = 40,000 VA