2.2 AC Theory, Reactance, Impedance & Power Factor

Oklahoma Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety

1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection

2 Chapter 2: General Electrical Theory & Calculations

2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments

3 Chapter 3: General Installation Requirements (NEC Article 110)

3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable

4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)

4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)

5 Chapter 5: Services & Service Equipment (NEC Article 230)

5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)

6 Chapter 6: Electrical Load Calculations (NEC Article 220)

6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)

7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)

7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)

8 Chapter 8: Grounding and Bonding (NEC Article 250)

8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)

9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)

9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)

10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems

10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)

11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)

11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)

12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)

12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)

13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)

13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)

14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems

14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)

2.2 AC Theory, Reactance, Impedance & Power Factor

Key Takeaways Explain This Topic AI

Alternating current waveforms cycle sinusoidally at 60 Hz in North America (period T = 16.67 ms), with standard test meters measuring Root-Mean-Square (RMS) effective values (V_rms = 0.707 × V_peak) representing equivalent DC thermal energy dissipation.

Inductive reactance (X_L = 2πfL) opposes AC current through self-induced Counter-Electromotive Force (CEMF), causing current to lag voltage by 90 degrees in pure inductors ('ELI').

Capacitive reactance (X_C = 1 / (2πfC)) opposes voltage changes through electrostatic charge accumulation, causing current to lead voltage by 90 degrees in pure capacitors ('ICE').

Total circuit impedance (Z) is the vector sum of resistance and net reactance: Z = √(R² + (X_L - X_C)²); electrical resonance occurs when X_L = X_C, causing net reactance to drop to zero and circuit impedance to equal pure resistance (Z = R).

The Power Triangle relates True Power (P in Watts/kW), Reactive Power (Q in VAR/kVAR), and Apparent Power (S in VA/kVA) via S = √(P² + Q²); Power Factor (PF = P / S = cos θ) measures operational efficiency, and low power factor is corrected by adding shunt capacitors to cancel inductive VARs and reduce total line current.

Last updated: August 2026

AC Theory, Reactance, Impedance & Power Factor

Unlike direct current circuits where opposition to current flow is purely resistive, alternating current (AC) circuits introduce magnetic and electrostatic field phenomena that create reactive opposition. Inductors (motor windings, transformers, ballasts) and capacitors store and release energy cyclically, causing phase shifts between voltage and current. Journeyman electricians must understand waveform metrics, reactive properties, vector impedance, and power factor correction to ensure energy efficiency and code compliance.

1. AC Sinusoidal Waveforms & Measurement Standards

In North America, commercial and residential electric utilities supply alternating current generated as a pure sine wave alternating at 60 Hertz (Hz) (60 cycles per second). +-----------------------------------------------------------------------------------------+

  • | AC SINE WAVE CHARACTERISTICS |
  • | |
  • | +V_peak ---"""---. |
  • | / \ |
  • | +V_rms --+-----------+-- (0.707 × V_peak) |
  • | / \ |
  • | 0V -----+---------------+---------------+----- 0V (Zero Crossings) |
  • | \ / |
  • | +-----------+ -- (-0.707 × V_peak) |
  • | -V_peak -----------------""""""""""" |
  • | |<------- 1 Full Cycle (Period T = 1/60s = 16.67 ms) ------->| |
  • +-----------------------------------------------------------------------------------------+

Mathematical Metrics of AC Waveforms:

Frequency ( f f f ): Number of complete cycles completed per second, expressed in Hertz (Hz) ( f = 60 Hz f = 60\text{ Hz} f = 60 Hz in the USA).

Period ( T T T ): The time required in seconds to complete one full electrical cycle: T = 1 f = 1 60 Hz ≈ 0.01667 seconds = 16.67 milliseconds T = \frac{1}{f} = \frac{1}{60\text{ Hz}} \approx 0.01667\text{ seconds} = 16.67\text{ milliseconds} T = f 1 ​ = 60 Hz 1 ​ ≈ 0.01667 seconds = 16.67 milliseconds

Peak Voltage ( V peak V_{\text{peak}} V peak ​ ): Maximum instantaneous voltage amplitude measured from the zero axis to the positive or negative crest.

Peak-to-Peak Voltage ( V p-p V_{\text{p-p}} V p-p ​ ): Full voltage span from positive peak to negative peak ( V p-p = 2 × V peak V_{\text{p-p}} = 2 \times V_{\text{peak}} V p-p ​ = 2 × V peak ​ ).

Root-Mean-Square (RMS / Effective Voltage): The effective value of an AC sine wave that produces the exact same heating effect in a resistor as an equivalent DC voltage: V rms = V peak 2 ≈ 0.7071 × V peak V_{\text{rms}} = \frac{V_{\text{peak}}}{\sqrt{2}} \approx 0.7071 \times V_{\text{peak}} V rms ​ = 2 ​ V peak ​ ​ ≈ 0.7071 × V peak ​ V peak = 2 × V rms ≈ 1.4142 × V rms V_{\text{peak}} = \sqrt{2} \times V_{\text{rms}} \approx 1.4142 \times V_{\text{rms}} V peak ​ = 2 ​ × V rms ​ ≈ 1.4142 × V rms ​ Key Trade Rule: All standard electrical test meters (DMMs), panelboard ratings, nameplates, and NEC references specify RMS values unless explicitly stated otherwise.

Average Voltage ( V avg V_{\text{avg}} V avg ​ ): The mathematical average of one rectified half-cycle sine wave: V avg = 2 π × V peak ≈ 0.637 × V peak ≈ 0.90 × V rms V_{\text{avg}} = \frac{2}{\pi} \times V_{\text{peak}} \approx 0.637 \times V_{\text{peak}} \approx 0.90 \times V_{\text{rms}} V avg ​ = π 2 ​ × V peak ​ ≈ 0.637 × V peak ​ ≈ 0.90 × V rms ​

2. Inductive Reactance ( X L X_L X L ​ ) & The "ELI" Concept

When alternating current passes through a coil (inductor), the expanding and collapsing magnetic field induces a Counter-Electromotive Force (CEMF) that opposes changes in current (Lenz's Law). This reactive opposition is called Inductive Reactance ( X L X_L X L ​ ) . +-----------------------------------------------------------------------------------------+

  • | INDUCTIVE REACTANCE FORMULA |
  • | |
  • | X_L = 2π × f × L |
  • | |
  • | • X_L = Inductive Reactance in Ohms (Ω) |
  • | • f = Frequency in Hertz (Hz) |
  • | • L = Inductance in Henrys (H) |
  • | • 2π = 2 × 3.14159 ≈ 6.2832 |
  • +-----------------------------------------------------------------------------------------+

Phase Relationship in Inductors:

In a purely inductive circuit, the induced CEMF delays the buildup of current. Consequently, Voltage leads Current by 90 ∘ 90^\circ 9 0 ∘ (or Current lags Voltage by 90 ∘ 90^\circ 9 0 ∘ ).

Mnemonic: "ELI" — E (Voltage) leads I (Current) in an L (Inductor).

Frequency Impact:

Inductive reactance is directly proportional to frequency. As frequency increases, the magnetic flux lines collapse and expand more rapidly, creating higher CEMF and greater inductive reactance ( f ↑ ⟹ X L ↑ f \uparrow \implies X_L \uparrow f ↑ ⟹ X L ​ ↑ ).

3. Capacitive Reactance ( X C X_C X C ​ ) & The "ICE" Concept

A capacitor consists of two conductive plates separated by an insulating dielectric material. When connected to an AC source, charge carriers continuously accumulate on and discharge from the plates, creating opposition to voltage changes called Capacitive Reactance ( X C X_C X C ​ ) . +-----------------------------------------------------------------------------------------+

  • | CAPACITIVE REACTANCE FORMULA |
  • | |
  • | X_C = 1 / (2π × f × C) |
  • | |
  • | • X_C = Capacitive Reactance in Ohms (Ω) |
  • | • f = Frequency in Hertz (Hz) |
  • | • C = Capacitance in Farads (F) [1 µF = 1 × 10⁻⁶ F] |
  • | • 2π = 2 × 3.14159 ≈ 6.2832 |
  • +-----------------------------------------------------------------------------------------+

Phase Relationship in Capacitors:

When AC voltage is applied, maximum current flows initially to charge the uncharged plates, while voltage across the plates is zero. As voltage peaks, current drops to zero. Consequently, Current leads Voltage by 90 ∘ 90^\circ 9 0 ∘ .

Mnemonic: "ICE" — I (Current) leads E (Voltage) in a C (Capacitor).

Combined Mnemonic: "ELI the ICE man" .

Frequency Impact:

Capacitive reactance is inversely proportional to frequency. At higher frequencies, the plates charge and discharge before significant opposing charge builds up, reducing reactance ( f ↑ ⟹ X C ↓ f \uparrow \implies X_C \downarrow f ↑ ⟹ X C ​ ↓ ).

4. Total Impedance ( Z Z Z ) & Series RLC Circuits

Impedance ( Z Z Z ) is the total opposition to alternating current flow, combining pure Resistance ( R R R ) and net Reactance ( X X X ). Because inductive reactance and capacitive reactance operate 180 ∘ 180^\circ 18 0 ∘ out of phase with each other, they cancel each other directly: X net = X L − X C X_{\text{net}} = X_L - X_C X net ​ = X L ​ − X C ​

Because resistance and net reactance operate at a 90 ∘ 90^\circ 9 0 ∘ phase angle, they must be added vectorially using the Pythagorean theorem. +-----------------------------------------------------------------------------------------+

  • | IMPEDANCE TRIANGLE FORMULAS |
  • | |
  • | Z = √[ R² + (X_L - X_C)² ] or Z = √[ R² + X_net² ] |
  • | |
  • | • Z = Total Impedance in Ohms (Ω) |
  • | • R = Pure Resistance in Ohms (Ω) [Horizontal Base] |
  • | • X_net = (X_L - X_C) in Ohms (Ω) [Vertical Leg] |
  • | • Phase Angle θ = arctan( X_net / R ) |
  • | • Circuit Current: I = E / Z |
  • +-----------------------------------------------------------------------------------------+

Electrical Resonance in Series RLC Circuits:

Resonance occurs at the specific frequency where inductive reactance exactly equals capacitive reactance ( X L = X C X_L = X_C X L ​ = X C ​ ):

Net reactance becomes zero: X net = X L − X C = 0 Ω X_{\text{net}} = X_L - X_C = 0\ \Omega X net ​ = X L ​ − X C ​ = 0 Ω .

Total impedance drops to its absolute minimum value: Z = R 2 + 0 2 = R Z = \sqrt{R^2 + 0^2} = R Z = R 2 + 0 2 ​ = R .

Circuit current reaches its absolute maximum: I = E R I = \frac{E}{R} I = R E ​ .

Power factor reaches 1.0 1.0 1.0 (Unity) with zero phase shift ( θ = 0 ∘ \theta = 0^\circ θ = 0 ∘ ).

Resonant Frequency Formula: f r = 1 2 π L C f_r = \frac{1}{2\pi\sqrt{LC}} f r ​ = 2 π L C ​ 1 ​ .

5. The Power Triangle & Power Factor Analysis

In AC circuits with reactive components, current and voltage are out of phase, creating three distinct forms of power represented by the Power Triangle . +-----------------------------------------------------------------------------------------+

  • | THE AC POWER TRIANGLE |
  • | |
  • | /| |
  • | / | |
  • | Apparent Power / | Reactive Power (Q) |
  • | (S) / | (VAR / kVAR) |
  • | [in VA] / | [Non-working reactive field power] |
  • | / | |
  • | /θ_____| |
  • | True Power (P) (Watts / kW) |
  • | [Useful working thermal / mechanical power] |
  • | |
  • | 1. True Power (P) = E × I × cos θ [Units: Watts (W) or Kilowatts (kW)] |
  • | 2. Reactive Power (Q) = E × I × sin θ [Units: Volt-Amps Reactive (VAR / kVAR)] |
  • | 3. Apparent Power (S) = E × I [Units: Volt-Amps (VA) or Kilovolt-Amps (kVA)] |
  • | 4. Vector Sum: S = √( P² + Q² ) |
  • +-----------------------------------------------------------------------------------------+

Power Factor Definition:

Power Factor (PF) is the ratio of True Power (useful work performed) to Apparent Power (total electrical capacity delivered by the utility): PF = True Power ( P ) Apparent Power ( S ) = cos ⁡ θ \text{PF} = \frac{\text{True Power } (P)}{\text{Apparent Power } (S)} = \cos\theta PF = Apparent Power ( S ) True Power ( P ) ​ = cos θ

Unity Power Factor ( 1.0 1.0 1.0 or 100 % 100\% 100% ): Voltage and current are perfectly in phase ( θ = 0 ∘ \theta = 0^\circ θ = 0 ∘ ). All delivered power performs real work ( P = S P = S P = S ).

Lagging Power Factor: Current lags voltage (inductive loads like induction motors, transformers, welding equipment, and magnetic ballasts).

Leading Power Factor: Current leads voltage (capacitive loads or overexcited synchronous motors).

6. Power Factor Correction Calculations for Journeyman Electricians

Operating commercial or industrial facilities with low lagging power factors results in severe operational penalties:

Excess Line Current: For a given kW load, lower PF forces higher current through cables and switchgear ( I = P E × PF I = \frac{P}{E \times \text{PF}} I = E × PF P ​ ).

Increased I 2 R I^2R I 2 R Cable Losses: Higher line current causes excessive thermal heating in distribution conductors.

Increased Voltage Drop: Higher current drops feeder voltage across long distribution runs.

Utility Surcharges: Electric utilities impose severe billing penalties when industrial customers operate below a target threshold (typically 0.90 0.90 0.90 or 0.95 PF 0.95\text{ PF} 0.95 PF ). +-----------------------------------------------------------------------------------------+

  • | POWER FACTOR CORRECTION STEP-BY-STEP WORKFLOW |
  • | |
  • | [STEP 1: Determine Existing True Power and Reactive Power] |
  • | - P = kW (remains constant because work does not change) |
  • | - S_initial = P / PF_initial |
  • | - kVAR_initial = √[ S_initial² - P² ] |
  • | | |
  • | v |
  • | [STEP 2: Calculate Target Apparent Power and Reactive Power] |
  • | - S_target = P / PF_target |
  • | - kVAR_target = √[ S_target² - P² ] |
  • | | |
  • | v |
  • | [STEP 3: Determine Sizing of Shunt Capacitor Bank] |
  • | - kVAR_capacitors = kVAR_initial - kVAR_target |
  • | | |
  • | v |
  • | [STEP 4: Calculate Feeder Current Reduction] |
  • | - Line Current Reduction = (S_initial / E) - (S_target / E) |
  • +-----------------------------------------------------------------------------------------+

Comprehensive Worked Correction Problem:

An industrial manufacturing facility draws 120 kW 120\text{ kW} 120 kW of real power from a 480 V 480\text{V} 480 V single-phase distribution feeder with an uncorrected lagging power factor of 0.60 0.60 0.60 .

Analyze Uncorrected Conditions:

Initial Apparent Power: S 1 = P PF 1 = 120 kW 0.60 = 200 kVA S_1 = \frac{P}{\text{PF}_1} = \frac{120\text{ kW}}{0.60} = 200\text{ kVA} S 1 ​ = PF 1 ​ P ​ = 0.60 120 kW ​ = 200 kVA .

Initial Feeder Current: I 1 = S 1 E = 200 , 000 VA 480 V = 416.67 A I_1 = \frac{S_1}{E} = \frac{200,000\text{ VA}}{480\text{V}} = 416.67\text{ A} I 1 ​ = E S 1 ​ ​ = 480 V 200 , 000 VA ​ = 416.67 A .

Initial Reactive Power: Q 1 = 200 2 − 120 2 = 40 , 000 − 14 , 400 = 25 , 600 = 160 kVAR Q_1 = \sqrt{200^2 - 120^2} = \sqrt{40,000 - 14,400} = \sqrt{25,600} = 160\text{ kVAR} Q 1 ​ = 20 0 2 − 12 0 2 ​ = 40 , 000 − 14 , 400 ​ = 25 , 600 ​ = 160 kVAR .

Analyze Corrected Target Conditions ( 0.95 PF 0.95\text{ PF} 0.95 PF Lagging):

Target Apparent Power: S 2 = P PF 2 = 120 kW 0.95 = 126.32 kVA S_2 = \frac{P}{\text{PF}_2} = \frac{120\text{ kW}}{0.95} = 126.32\text{ kVA} S 2 ​ = PF 2 ​ P ​ = 0.95 120 kW ​ = 126.32 kVA .

Target Feeder Current: I 2 = S 2 E = 126 , 316 VA 480 V = 263.16 A I_2 = \frac{S_2}{E} = \frac{126,316\text{ VA}}{480\text{V}} = 263.16\text{ A} I 2 ​ = E S 2 ​ ​ = 480 V 126 , 316 VA ​ = 263.16 A .

Target Reactive Power: Q 2 = 126.32 2 − 120 2 = 15 , 956.74 − 14 , 400 = 1 , 556.74 ≈ 39.46 kVAR Q_2 = \sqrt{126.32^2 - 120^2} = \sqrt{15,956.74 - 14,400} = \sqrt{1,556.74} \approx 39.46\text{ kVAR} Q 2 ​ = 126.3 2 2 − 12 0 2 ​ = 15 , 956.74 − 14 , 400 ​ = 1 , 556.74 ​ ≈ 39.46 kVAR .

Calculate Required Capacitor Rating ( Q C Q_C Q C ​ ):

Q C = Q 1 − Q 2 = 160 kVAR − 39.46 kVAR = 120.54 kVAR Q_C = Q_1 - Q_2 = 160\text{ kVAR} - 39.46\text{ kVAR} = 120.54\text{ kVAR} Q C ​ = Q 1 ​ − Q 2 ​ = 160 kVAR − 39.46 kVAR = 120.54 kVAR .

Installing a 120 kVAR 120\text{ kVAR} 120 kVAR power factor correction capacitor bank reduces feeder current from 416.67 A 416.67\text{ A} 416.67 A down to 263.16 A 263.16\text{ A} 263.16 A —releasing 153.51 A 153.51\text{ A} 153.51 A ( 36.8 % 36.8\% 36.8% ) of feeder and transformer capacity while eliminating utility penalty surcharges.

Loading diagram... Impedance Triangle and AC Power Triangle Vector Relationships