2.4 Electrical Units, Formulas & Conversions
Oklahoma Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety
1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection
2 Chapter 2: General Electrical Theory & Calculations
2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments
3 Chapter 3: General Installation Requirements (NEC Article 110)
3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable
4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)
4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)
5 Chapter 5: Services & Service Equipment (NEC Article 230)
5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)
6 Chapter 6: Electrical Load Calculations (NEC Article 220)
6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)
7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)
7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)
8 Chapter 8: Grounding and Bonding (NEC Article 250)
8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)
9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)
9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)
10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems
10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)
11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)
11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)
12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)
12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)
13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)
13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)
14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems
14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)
2.4 Electrical Units, Formulas & Conversions
Key Takeaways Explain This Topic AI
Electrical units follow strict derived relationships: Potential in Volts (V = J/C), Current in Amperes (A = C/s), Resistance in Ohms (Ω = V/A), Power in Watts (W = J/s), Energy in Joules or Kilowatt-hours (1 kWh = 3,412 BTU = 3.6 MJ), Capacitance in Farads (F), and Inductance in Henrys (H).
Power and thermal conversion constants bridge mechanical and HVAC loads to electrical parameters: 1 Horsepower (HP) = 746 Watts; 1 Kilowatt (kW) = 3,412 BTU/hr; and 1 Ton of Air Conditioning = 12,000 BTU/hr = 3.517 kW (3,517 W).
Conductor cross-sectional area is measured in Circular Mils (cmil = d², where d is conductor diameter in mils and 1 mil = 0.001 inch), with large conductors rated in kcmil (thousands of circular mils).
Conductor voltage drop is calculated using VD = (2 × K × I × D) / cmil for single-phase circuits and VD = (1.732 × K × I × D) / cmil for three-phase circuits, where K-factor constants at 75°C are 12.9 Ω·cmil/ft for Copper and 21.2 Ω·cmil/ft for Aluminum.
National Electrical Code recommendations (NEC 210.19(A) Informational Note No. 4 and NEC 215.2(A)(1)(b) Informational Note No. 2) advise limiting voltage drop to a maximum of 3% on branch circuits or feeders, and no more than 5% total across the entire distribution system from the service disconnecting means to the farthest outlet.
Last updated: August 2026
Electrical Units, Formulas & Conversions
Precise unit conversions, conductor area calculations, and voltage drop evaluations are essential competencies for journeyman electricians. System performance, equipment longevity, and fire safety depend on selecting conductors capable of handling circuit continuous loads while restricting voltage drop within acceptable operating limits. This section provides a comprehensive technical reference for SI electrical units, thermal/mechanical conversions, conductor geometry (circular mils), exact voltage drop calculations, and equipment efficiency formulas.
1. Master Electrical Units & Derived Standards
Every electrical calculation utilizes fundamental units defined by the International System of Units (SI) and derived electromagnetic relationships.
Electrical Quantity Symbol Unit Name Unit Symbol Mathematical / Physical Derivation
Electromotive Force (Potential) E , V E, V E , V Volt V \text{V} V 1 V = 1 Joule / 1 Coulomb = 1 W / 1 A 1\text{ V} = 1\text{ Joule} / 1\text{ Coulomb} = 1\text{ W} / 1\text{ A} 1 V = 1 Joule /1 Coulomb = 1 W /1 A
Electric Current I I I Ampere A \text{A} A 1 A = 1 Coulomb / 1 second = 6.242 × 10 18 electrons/s 1\text{ A} = 1\text{ Coulomb} / 1\text{ second} = 6.242 \times 10^{18}\text{ electrons/s} 1 A = 1 Coulomb /1 second = 6.242 × 1 0 18 electrons/s
Electrical Resistance R R R Ohm Ω \Omega Ω 1 Ω = 1 Volt / 1 Ampere 1\ \Omega = 1\text{ Volt} / 1\text{ Ampere} 1 Ω = 1 Volt /1 Ampere
Electrical Conductance G G G Siemens (Mho) S \text{S} S G = 1 / R G = 1 / R G = 1/ R ; 1 S = 1 A / 1 V 1\text{ S} = 1\text{ A} / 1\text{ V} 1 S = 1 A /1 V
Electric Power P P P Watt W \text{W} W 1 W = 1 Joule / 1 second = 1 V × 1 A 1\text{ W} = 1\text{ Joule} / 1\text{ second} = 1\text{ V} \times 1\text{ A} 1 W = 1 Joule /1 second = 1 V × 1 A
Electric Energy / Work W , E W, E W , E Joule / kWh J, kWh \text{J, kWh} J, kWh 1 J = 1 W ⋅ s 1\text{ J} = 1\text{ W}\cdot\text{s} 1 J = 1 W ⋅ s ; 1 kWh = 3 , 600 , 000 J = 3.6 MJ 1\text{ kWh} = 3,600,000\text{ J} = 3.6\text{ MJ} 1 kWh = 3 , 600 , 000 J = 3.6 MJ
Electrostatic Capacitance C C C Farad F \text{F} F 1 F = 1 Coulomb / 1 Volt 1\text{ F} = 1\text{ Coulomb} / 1\text{ Volt} 1 F = 1 Coulomb /1 Volt
Magnetic Inductance L L L Henry H \text{H} H 1 H = 1 Volt ⋅ second / 1 Ampere 1\text{ H} = 1\text{ Volt}\cdot\text{second} / 1\text{ Ampere} 1 H = 1 Volt ⋅ second /1 Ampere
Frequency f f f Hertz Hz \text{Hz} Hz 1 Hz = 1 cycle / 1 second 1\text{ Hz} = 1\text{ cycle} / 1\text{ second} 1 Hz = 1 cycle /1 second
Electric Charge Q Q Q Coulomb C \text{C} C 1 C = 1 Ampere × 1 second 1\text{ C} = 1\text{ Ampere} \times 1\text{ second} 1 C = 1 Ampere × 1 second
Magnetic Flux Φ \Phi Φ Weber Wb \text{Wb} Wb 1 Wb = 1 Volt ⋅ second = 10 8 Maxwells 1\text{ Wb} = 1\text{ Volt}\cdot\text{second} = 10^8\text{ Maxwells} 1 Wb = 1 Volt ⋅ second = 1 0 8 Maxwells
Magnetic Flux Density B B B Tesla T \text{T} T 1 T = 1 Wb / m 2 = 10 , 000 Gauss 1\text{ T} = 1\text{ Wb}/\text{m}^2 = 10,000\text{ Gauss} 1 T = 1 Wb / m 2 = 10 , 000 Gauss
2. Power, Mechanical & Thermal Conversions
In commercial and residential trade work, electricians frequently interface with mechanical equipment rated in horsepower (HP) and HVAC/heating equipment rated in British Thermal Units (BTU). +-----------------------------------------------------------------------------------------+
- | ESSENTIAL CONVERSION CONSTANTS |
- | |
- | 1. Mechanical Power to Electrical Power: |
- | • 1 Horsepower (HP) = 746 Watts = 0.746 Kilowatts |
- | • Watts = HP × 746 |
- | • HP = Watts / 746 |
- | |
- | 2. Thermal Energy to Electrical Power: |
- | • 1 Kilowatt (kW) = 3,412 BTU/hr |
- | • 1 Kilowatt-hour (kWh) = 3,412 BTU of thermal heat |
- | • Heating Watts = (BTU/hr) / 3.412 |
- | |
- | 3. Air Conditioning & Refrigeration Capacity: |
- | • 1 Ton of Refrigeration = 12,000 BTU/hr |
- | • 1 Ton of Refrigeration = 12,000 / 3,412 = 3.517 kW = 3,517 Watts |
- +-----------------------------------------------------------------------------------------+
- Conversion Example: Commercial Duct Heater
A commercial building blueprint specifies a supplemental electric duct heater rated at 68 , 240 BTU/hr 68,240\text{ BTU/hr} 68 , 240 BTU/hr .
Electrical power required in Kilowatts: P = 68 , 240 BTU/hr 3 , 412 BTU/kWh = 20.0 kW = 20 , 000 Watts P = \frac{68,240\text{ BTU/hr}}{3,412\text{ BTU/kWh}} = 20.0\text{ kW} = 20,000\text{ Watts} P = 3 , 412 BTU/kWh 68 , 240 BTU/hr = 20.0 kW = 20 , 000 Watts .
If operating at 240 V 240\text{V} 240 V single-phase: Current I = 20 , 000 W 240 V = 83.33 A I = \frac{20,000\text{ W}}{240\text{V}} = 83.33\text{ A} I = 240 V 20 , 000 W = 83.33 A .
3. Conductor Geometry, Mils & Circular Mils (cmil)
In North American electrical engineering and NEC tables, wire sizes are expressed in American Wire Gauge (AWG) from 18 AWG up to 4/0 AWG, and in kcmil (thousands of circular mils) for conductors 250 kcmil 250\text{ kcmil} 250 kcmil and larger. +-----------------------------------------------------------------------------------------+
- | CIRCULAR MIL DEFINITIONS & AREA |
- | |
- | • 1 Mil = 0.001 inch (one-thousandth of an inch) |
- | • Diameter (d) in Mils = Diameter in inches × 1,000 |
- | • Circular Mil Area (cmil) = d² (where d is diameter in mils) |
- | |
- | Comparison between Square Mils and Circular Mils: |
- | • Area in Square Mils = (π / 4) × d² ≈ 0.7854 × cmil |
- | • Area in Circular Mils = Area in Square Mils / 0.7854 ≈ 1.2732 × Square Mils |
- +-----------------------------------------------------------------------------------------+
NEC Chapter 9, Table 8 Conductor Properties (Key Copper Standards):
14 AWG: 4 , 110 cmil 4,110\text{ cmil} 4 , 110 cmil (Solid diameter ≈ 64.1 mils \approx 64.1\text{ mils} ≈ 64.1 mils )
12 AWG: 6 , 530 cmil 6,530\text{ cmil} 6 , 530 cmil (Solid diameter ≈ 80.8 mils \approx 80.8\text{ mils} ≈ 80.8 mils )
10 AWG: 10 , 380 cmil 10,380\text{ cmil} 10 , 380 cmil (Solid diameter ≈ 101.9 mils \approx 101.9\text{ mils} ≈ 101.9 mils )
- 8 AWG: 16 , 510 cmil 16,510\text{ cmil} 16 , 510 cmil
- 6 AWG: 26 , 240 cmil 26,240\text{ cmil} 26 , 240 cmil
- 4 AWG: 41 , 740 cmil 41,740\text{ cmil} 41 , 740 cmil
- 3 AWG: 52 , 620 cmil 52,620\text{ cmil} 52 , 620 cmil
- 2 AWG: 66 , 360 cmil 66,360\text{ cmil} 66 , 360 cmil
- 1 AWG: 83 , 690 cmil 83,690\text{ cmil} 83 , 690 cmil
- 1/0 AWG: 105 , 600 cmil 105,600\text{ cmil} 105 , 600 cmil
- 2/0 AWG: 133 , 100 cmil 133,100\text{ cmil} 133 , 100 cmil
- 3/0 AWG: 167 , 800 cmil 167,800\text{ cmil} 167 , 800 cmil
- 4/0 AWG: 211 , 600 cmil 211,600\text{ cmil} 211 , 600 cmil
- 250 kcmil 250\text{ kcmil} 250 kcmil : 250 , 000 cmil 250,000\text{ cmil} 250 , 000 cmil
- 500 kcmil 500\text{ kcmil} 500 kcmil : 500 , 000 cmil 500,000\text{ cmil} 500 , 000 cmil
Rectangular Copper Busbar Calculation:
A copper switchboard busbar measures 1 / 4 inch × 2 inches 1/4\text{ inch} \times 2\text{ inches} 1/4 inch × 2 inches in cross-section.
Convert dimensions to mils: 0.250 in = 250 mils 0.250\text{ in} = 250\text{ mils} 0.250 in = 250 mils ; 2.000 in = 2 , 000 mils 2.000\text{ in} = 2,000\text{ mils} 2.000 in = 2 , 000 mils .
Area in square mils: A sq mils = 250 × 2 , 000 = 500 , 000 sq mils A_{\text{sq mils}} = 250 \times 2,000 = 500,000\text{ sq mils} A sq mils = 250 × 2 , 000 = 500 , 000 sq mils .
Convert square mils to circular mils: cmil = 500 , 000 0.7854 = 636 , 618 cmil ≈ 636.6 kcmil \text{cmil} = \frac{500,000}{0.7854} = 636,618\text{ cmil} \approx 636.6\text{ kcmil} cmil = 0.7854 500 , 000 = 636 , 618 cmil ≈ 636.6 kcmil .
4. Comprehensive Voltage Drop Calculations & NEC Guidelines
When electrical current travels through a circuit conductor, the internal resistance of the wire creates an unavoidable voltage drop ( I × R I \times R I × R ). If conductors are undersized or circuit runs are excessively long, the reduced operating voltage causes motor overheating, contactor chattering, dim lighting, and electronic device failure. +-----------------------------------------------------------------------------------------+
- | VOLTAGE DROP FORMULAS |
- | |
- | 1. Single-Phase Voltage Drop: VD = ( 2 × K × I × D ) / cmil |
- | |
- | 2. Three-Phase Voltage Drop: VD = ( √3 × K × I × D ) / cmil |
- | = ( 1.732 × K × I × D ) / cmil |
- | |
- | 3. Sizing Conductor Area (cmil): |
- | • Single-Phase: cmil = ( 2 × K × I × D ) / VD_allowable |
- | • Three-Phase: cmil = ( 1.732 × K × I × D ) / VD_allowable |
- | |
- | Where: |
- | • K = Specific Conductor Resistance at 75°C: |
- | - Copper (Cu): K = 12.9 Ω·cmil/ft |
- | - Aluminum (Al): K = 21.2 Ω·cmil/ft |
- | • I = Load Current in Amperes |
- | • D = One-Way Circuit Distance in Feet |
- | • cmil = Conductor Cross-Sectional Area in Circular Mils (NEC Ch 9, Table 8) |
- | • Factor '2' in single-phase accounts for out-and-back conductor loop |
- | • Factor '√3' (1.732) in three-phase accounts for 120° vector phase relationship |
- +-----------------------------------------------------------------------------------------+
National Electrical Code Voltage Drop Standards (Informational Notes):
NEC 210.19(A) Informational Note No. 4 (Branch Circuits): Recommends that branch circuit conductors be sized to limit voltage drop to no more than 3 % 3\% 3% of nominal circuit voltage at the farthest outlet supplying power, heating, or lighting loads.
NEC 215.2(A)(1)(b) Informational Note No. 2 (Feeders): Recommends that feeder conductors be sized to limit voltage drop to no more than 3 % 3\% 3% .
Total Combined System Limit: The maximum total combined voltage drop on both the feeder and the branch circuit combined should not exceed 5 % 5\% 5% from the service disconnecting means to the final load outlet.
Maximum Allowable Voltage Drops by System Voltage:
120 V 120\text{V} 120 V Circuit: 3 % = 3.60 V 3\% = 3.60\text{V} 3% = 3.60 V ; 5 % = 6.00 V 5\% = 6.00\text{V} 5% = 6.00 V
208 V 208\text{V} 208 V Circuit: 3 % = 6.24 V 3\% = 6.24\text{V} 3% = 6.24 V ; 5 % = 10.40 V 5\% = 10.40\text{V} 5% = 10.40 V
240 V 240\text{V} 240 V Circuit: 3 % = 7.20 V 3\% = 7.20\text{V} 3% = 7.20 V ; 5 % = 12.00 V 5\% = 12.00\text{V} 5% = 12.00 V
277 V 277\text{V} 277 V Circuit: 3 % = 8.31 V 3\% = 8.31\text{V} 3% = 8.31 V ; 5 % = 13.85 V 5\% = 13.85\text{V} 5% = 13.85 V
480 V 480\text{V} 480 V Circuit: 3 % = 14.40 V 3\% = 14.40\text{V} 3% = 14.40 V ; 5 % = 24.00 V 5\% = 24.00\text{V} 5% = 24.00 V
Step-by-Step Worked Problems:
Problem 1: Evaluating Single-Phase Voltage Drop & Upsizing
A 120 V 120\text{V} 120 V , single-phase parking lot lighting branch circuit carries a continuous load of 16 A 16\text{ A} 16 A copper conductors over a one-way distance of 175 feet 175\text{ feet} 175 feet using 12 AWG 12\text{ AWG} 12 AWG THHN copper ( 6 , 530 cmil 6,530\text{ cmil} 6 , 530 cmil ).
Calculate Actual Voltage Drop: VD = 2 × K × I × D cmil = 2 × 12.9 × 16 A × 175 ft 6 , 530 cmil = 72 , 240 6 , 530 = 11.06 V \text{VD} = \frac{2 \times K \times I \times D}{\text{cmil}} = \frac{2 \times 12.9 \times 16\text{ A} \times 175\text{ ft}}{6,530\text{ cmil}} = \frac{72,240}{6,530} = 11.06\text{V} VD = cmil 2 × K × I × D = 6 , 530 cmil 2 × 12.9 × 16 A × 175 ft = 6 , 530 72 , 240 = 11.06 V
Calculate Percentage Drop: % VD = ( 11.06 V 120 V ) × 100 % = 9.22 % ( Fails 3% limit of 3.60V ) \%\text{VD} = \left(\frac{11.06\text{V}}{120\text{V}}\right) \times 100\% = 9.22\% \quad (\text{Fails 3\% limit of 3.60V}) % VD = ( 120 V 11.06 V ) × 100% = 9.22% ( Fails 3% limit of 3.60V )
Calculate Minimum Circular Mils to Meet 3% Limit ( 3.60 V 3.60\text{V} 3.60 V max drop): cmil required = 2 × 12.9 × 16 × 175 3.60 V = 72 , 240 3.60 = 20 , 066.67 cmil \text{cmil}_{\text{required}} = \frac{2 \times 12.9 \times 16 \times 175}{3.60\text{V}} = \frac{72,240}{3.60} = 20,066.67\text{ cmil} cmil required = 3.60 V 2 × 12.9 × 16 × 175 = 3.60 72 , 240 = 20 , 066.67 cmil
Select Conductor from NEC Chapter 9, Table 8:
8 AWG = 16 , 510 cmil 8\text{ AWG} = 16,510\text{ cmil} 8 AWG = 16 , 510 cmil (Too small)
6 AWG = 26 , 240 cmil 6\text{ AWG} = 26,240\text{ cmil} 6 AWG = 26 , 240 cmil (Complies; actual drop with 6 AWG = 2.75 V = 2.29 % 6\text{ AWG} = 2.75\text{V} = 2.29\% 6 AWG = 2.75 V = 2.29% ).
Problem 2: Sizing Three-Phase Feeder for Voltage Drop
A 480 V 480\text{V} 480 V , 3-phase commercial building feeder supplies an industrial rooftop chiller drawing 75 A 75\text{ A} 75 A over a one-way distance of 350 feet 350\text{ feet} 350 feet using copper conductors. Sizing for a maximum 3 % 3\% 3% voltage drop ( 14.40 V 14.40\text{V} 14.40 V maximum allowable drop):
Calculate Required Circular Mil Area: cmil = 1.732 × K × I × D VD allowable = 1.732 × 12.9 × 75 A × 350 ft 14.40 V = 586 , 482 14.40 = 40 , 727.9 cmil \text{cmil} = \frac{1.732 \times K \times I \times D}{\text{VD}_{\text{allowable}}} = \frac{1.732 \times 12.9 \times 75\text{ A} \times 350\text{ ft}}{14.40\text{V}} = \frac{586,482}{14.40} = 40,727.9\text{ cmil} cmil = VD allowable 1.732 × K × I × D = 14.40 V 1.732 × 12.9 × 75 A × 350 ft = 14.40 586 , 482 = 40 , 727.9 cmil
Select Conductor from NEC Chapter 9, Table 8:
6 AWG = 26 , 240 cmil 6\text{ AWG} = 26,240\text{ cmil} 6 AWG = 26 , 240 cmil (Too small)
4 AWG = 41 , 740 cmil 4\text{ AWG} = 41,740\text{ cmil} 4 AWG = 41 , 740 cmil (Properly sized to comply with 3 % 3\% 3% threshold).
5. Electrical Equipment Efficiency Formulas
Efficiency ( η \eta η ) measures how effectively electrical equipment converts electrical input power into useful mechanical or thermal output power without wasting energy as heat. +-----------------------------------------------------------------------------------------+
- | EQUIPMENT EFFICIENCY FORMULAS |
- | |
- | 1. Efficiency (η) = ( Power Output / Power Input ) × 100% |
- | = ( Watts_Out / Watts_In ) × 100% |
- | |
- | 2. Input Power (Watts_In) = Watts_Out / η |
- | |
- | 3. Single-Phase Motor Input Current: |
- | I = ( HP × 746 ) / ( Voltage × PF × η ) |
- | |
- | 4. Three-Phase Motor Input Current: |
- | I = ( HP × 746 ) / ( √3 × Voltage × PF × η ) |
- +-----------------------------------------------------------------------------------------+
Motor Efficiency Worked Example:
A 15 HP 15\text{ HP} 15 HP , 230 V 230\text{V} 230 V , single-phase motor has an efficiency rating of 86 % 86\% 86% ( 0.86 0.86 0.86 ) and operates at a power factor of 0.88 0.88 0.88 .
Mechanical Output Power: P out = 15 HP × 746 W/HP = 11 , 190 Watts P_{\text{out}} = 15\text{ HP} \times 746\text{ W/HP} = 11,190\text{ Watts} P out = 15 HP × 746 W/HP = 11 , 190 Watts .
Electrical Input Power: P in = 11 , 190 W 0.86 = 13 , 011.63 Watts P_{\text{in}} = \frac{11,190\text{ W}}{0.86} = 13,011.63\text{ Watts} P in = 0.86 11 , 190 W = 13 , 011.63 Watts .
Full-Load Current Drawn: I = 13 , 011.63 W 230 V × 0.88 = 13 , 011.63 202.4 = 64.29 Amperes I = \frac{13,011.63\text{ W}}{230\text{V} \times 0.88} = \frac{13,011.63}{202.4} = 64.29\text{ Amperes} I = 230 V × 0.88 13 , 011.63 W = 202.4 13 , 011.63 = 64.29 Amperes