Study guide

2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits

Oklahoma Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety

1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection

2 Chapter 2: General Electrical Theory & Calculations

2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments

3 Chapter 3: General Installation Requirements (NEC Article 110)

3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable

4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)

4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)

5 Chapter 5: Services & Service Equipment (NEC Article 230)

5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)

6 Chapter 6: Electrical Load Calculations (NEC Article 220)

6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)

7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)

7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)

8 Chapter 8: Grounding and Bonding (NEC Article 250)

8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)

9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)

9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)

10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems

10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)

11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)

11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)

12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)

12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)

13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)

13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)

14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems

14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)

2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits

Key Takeaways Explain This Topic AI

Ohm's Law governs direct current circuits through the mathematical relationship E = I × R (Voltage = Current × Resistance), with derived formulas I = E / R and R = E / I.

Watt's Law defines electrical power (P) in Watts as P = E × I, with algebraic substitutions yielding P = I² × R and P = E² / R to calculate power dissipation and thermal heat losses.

In series DC circuits, current is uniform throughout all components (I_T = I₁ = I₂ = ...), total resistance equals the arithmetic sum of individual resistances (R_T = R₁ + R₂ + ...), and Kirchhoff's Voltage Law (KVL) dictates that the sum of all voltage drops equals the source voltage.

In parallel DC circuits, voltage is identical across every branch (E_T = E₁ = E₂ = ...), total equivalent resistance is calculated by reciprocal summation (1/R_T = 1/R₁ + 1/R₂ + ...) and is always less than the smallest branch resistance, and Kirchhoff's Current Law (KCL) dictates that total circuit current equals the sum of branch currents.

Combination series-parallel circuits are solved systematically using the equivalent reduction technique: replacing parallel clusters with equivalent resistances, summing series elements, and back-calculating branch currents and component power dissipation.

Last updated: August 2026

Ohm's Law, Watt's Law & DC Series/Parallel Circuits

Mastery of direct current (DC) theory and fundamental electrical mathematics is the foundation upon which all trade calculations, circuit diagnostics, and National Electrical Code (NEC) load sizing requirements rest. Whether determining the voltage drop across branch circuit conductors, calculating heater element wattage, or analyzing control circuits in industrial panels, journeyman electricians must be able to fluidly apply Ohm's Law and Watt's Law across series, parallel, and combination circuit topologies.

1. Fundamentals of Ohm's Law

In 1827, German physicist Georg Simon Ohm formulated the relationship governing electrical conduction: the current flowing through a conductor between two points is directly proportional to the voltage across the two points and inversely proportional to the resistance between them. +-----------------------------------------------------------------------------------------+

  • | OHM'S LAW FORMULA MATRIX |
  • | |
  • | [ VOLTAGE (E or V) ] = [ CURRENT (I) ] × [ RESISTANCE (R) ] |
  • | |
  • | To Find Voltage (E): To Find Current (I): To Find Resistance (R):|
  • | E = I × R I = E / R R = E / I |
  • | (Volts = A × Ω) (Amps = V / Ω) (Ohms = V / A) |
  • +-----------------------------------------------------------------------------------------+

Primary Electrical Quantities and Physical Units:

Electromotive Force / Voltage ( E E E or V V V ): The electrical pressure or potential difference that drives charge carriers through a closed circuit. Measured in Volts (V) . One volt equals one Joule of work performed per Coulomb of charge moved ( 1 V = 1 J/C 1\text{ V} = 1\text{ J/C} 1 V = 1 J/C ).

Current ( I I I ): The rate of electrical charge flow past a given point in a conductor. Measured in Amperes (A) . One ampere equals one Coulomb of charge moving per second ( 1 A = 1 C/s = 6.242 × 10 18 electrons/second 1\text{ A} = 1\text{ C/s} = 6.242 \times 10^{18}\text{ electrons/second} 1 A = 1 C/s = 6.242 × 1 0 18 electrons/second ).

Resistance ( R R R ): The physical opposition to the flow of electric current, converting electrical energy into heat. Measured in Ohms ( Ω \Omega Ω ) . One ohm allows one ampere of current to flow when an electromotive force of one volt is applied ( 1 Ω = 1 V/A 1\ \Omega = 1\text{ V/A} 1 Ω = 1 V/A ).

2. Watt's Law and Electrical Power Relationships

Electrical power represents the rate at which electrical energy is converted into another form of energy (such as heat, light, or mechanical work). James Watt's mathematical relationships, combined with Ohm's Law, form the standard twelve-formula electrical calculation wheel. +-----------------------------------------------------------------------------------------+

  • | THE 12 OHM'S / WATT'S FORMULAS |
  • | |
  • | [ POWER (P) in Watts ] [ VOLTAGE (E) in Volts ] [ CURRENT (I) in Amps ] |
  • | • P = E × I • E = I × R • I = E / R |
  • | • P = I² × R • E = P / I • I = P / E |
  • | • P = E² / R • E = √(P × R) • I = √(P / R) |
  • | |
  • | [ RESISTANCE (R) in Ohms ] |
  • | • R = E / I |
  • | • R = E² / P |
  • | • R = P / I² |
  • +-----------------------------------------------------------------------------------------+

Power Relationships and I 2 R I^2R I 2 R Heat Losses:

P = E × I P = E \times I P = E × I : Direct product of applied potential and total current.

P = I 2 × R P = I^2 \times R P = I 2 × R (Joule's Law / Copper Loss): Demonstrates that power dissipation through resistance increases with the square of the current. If circuit current doubles, heat loss in conductors and connections quadruples ( 2 2 = 4 2^2 = 4 2 2 = 4 ).

P = E 2 R P = \frac{E^2}{R} P = R E 2 ​ : Demonstrates the impact of voltage fluctuations on resistive loads. If voltage supplied to a fixed resistance heating element drops by 10 % 10\% 10% (to 90 % 90\% 90% nominal), heat output drops to 0.90 2 = 81 % 0.90^2 = 81\% 0.9 0 2 = 81% of rated output.

Trade Application Example: Industrial Strip Heater Sizing

An industrial drying oven operates two 240 V 240\text{V} 240 V resistive heating elements rated at 2 , 400 W 2,400\text{W} 2 , 400 W each.

Resistance of each element: R = E 2 P = 240 2 2 , 400 = 57 , 600 2 , 400 = 24 Ω R = \frac{E^2}{P} = \frac{240^2}{2,400} = \frac{57,600}{2,400} = 24\ \Omega R = P E 2 ​ = 2 , 400 24 0 2 ​ = 2 , 400 57 , 600 ​ = 24 Ω .

Current drawn by each element at 240 V 240\text{V} 240 V : I = P E = 2 , 400 240 = 10 A I = \frac{P}{E} = \frac{2,400}{240} = 10\text{ A} I = E P ​ = 240 2 , 400 ​ = 10 A .

If voltage drops to 208 V 208\text{V} 208 V , the power output of each element becomes: P new = E 2 R = 208 2 24 = 43 , 264 24 = 1 , 802.67 W P_{\text{new}} = \frac{E^2}{R} = \frac{208^2}{24} = \frac{43,264}{24} = 1,802.67\text{ W} P new ​ = R E 2 ​ = 24 20 8 2 ​ = 24 43 , 264 ​ = 1 , 802.67 W (a 24.9 % 24.9\% 24.9% reduction in heating capacity).

3. Series DC Circuits & Kirchhoff's Voltage Law (KVL)

A series circuit provides only one continuous path for current to flow. All components are connected end-to-end. +-----------------------------------------------------------------------------------------+

  • | SERIES DC CIRCUIT RULES |
  • | |
  • | 1. Current is CONSTANT: I_Total = I₁ = I₂ = I₃ = ... = I_n |
  • | 2. Resistance is ADDITIVE: R_Total = R₁ + R₂ + R₃ + ... + R_n |
  • | 3. Voltage Drops are ADDITIVE: E_Total = V₁ + V₂ + V₃ + ... + V_n |
  • | 4. Total Power is ADDITIVE: P_Total = P₁ + P₂ + P₃ + ... + P_n |
  • +-----------------------------------------------------------------------------------------+

Kirchhoff's Voltage Law (KVL):

Kirchhoff's Voltage Law states that the algebraic sum of all voltages around any closed loop in an electrical network is equal to zero: ∑ V = 0 \sum V = 0 ∑ V = 0 . In practical terms, the source voltage applied to a series circuit equals the sum of the individual voltage drops across each series component ( E source = V 1 + V 2 + ⋯ + V n E_{\text{source}} = V_1 + V_2 + \dots + V_n E source ​ = V 1 ​ + V 2 ​ + ⋯ + V n ​ ).

Voltage Divider Rule:

The voltage drop across any individual resistor ( R x R_x R x ​ ) in a series circuit is directly proportional to its share of the total circuit resistance: V x = E Total × ( R x R Total ) V_x = E_{\text{Total}} \times \left(\frac{R_x}{R_{\text{Total}}}\right) V x ​ = E Total ​ × ( R Total ​ R x ​ ​ )

Step-by-Step Series Calculation:

A 120 V 120\text{V} 120 V DC control circuit connects three field resistors in series: R 1 = 15 Ω R_1 = 15\ \Omega R 1 ​ = 15 Ω , R 2 = 25 Ω R_2 = 25\ \Omega R 2 ​ = 25 Ω , and R 3 = 20 Ω R_3 = 20\ \Omega R 3 ​ = 20 Ω .

Total Resistance ( R T R_T R T ​ ): R T = 15 + 25 + 20 = 60 Ω R_T = 15 + 25 + 20 = 60\ \Omega R T ​ = 15 + 25 + 20 = 60 Ω .

Total Current ( I T I_T I T ​ ): I T = E T R T = 120 V 60 Ω = 2.0 A I_T = \frac{E_T}{R_T} = \frac{120\text{V}}{60\ \Omega} = 2.0\text{ A} I T ​ = R T ​ E T ​ ​ = 60 Ω 120 V ​ = 2.0 A .

Individual Voltage Drops:

V 1 = I T × R 1 = 2.0 A × 15 Ω = 30 V V_1 = I_T \times R_1 = 2.0\text{ A} \times 15\ \Omega = 30\text{V} V 1 ​ = I T ​ × R 1 ​ = 2.0 A × 15 Ω = 30 V

V 2 = I T × R 2 = 2.0 A × 25 Ω = 50 V V_2 = I_T \times R_2 = 2.0\text{ A} \times 25\ \Omega = 50\text{V} V 2 ​ = I T ​ × R 2 ​ = 2.0 A × 25 Ω = 50 V

V 3 = I T × R 3 = 2.0 A × 20 Ω = 40 V V_3 = I_T \times R_3 = 2.0\text{ A} \times 20\ \Omega = 40\text{V} V 3 ​ = I T ​ × R 3 ​ = 2.0 A × 20 Ω = 40 V

Verification (KVL): 30 V + 50 V + 40 V = 120 V 30\text{V} + 50\text{V} + 40\text{V} = 120\text{V} 30 V + 50 V + 40 V = 120 V .

Power Dissipation:

P 1 = 30 V × 2 A = 60 W P_1 = 30\text{V} \times 2\text{ A} = 60\text{W} P 1 ​ = 30 V × 2 A = 60 W ; P 2 = 50 V × 2 A = 100 W P_2 = 50\text{V} \times 2\text{ A} = 100\text{W} P 2 ​ = 50 V × 2 A = 100 W ; P 3 = 40 V × 2 A = 80 W P_3 = 40\text{V} \times 2\text{ A} = 80\text{W} P 3 ​ = 40 V × 2 A = 80 W .

P T = 60 + 100 + 80 = 240 W P_T = 60 + 100 + 80 = 240\text{W} P T ​ = 60 + 100 + 80 = 240 W ( P T = 120 V × 2 A = 240 W P_T = 120\text{V} \times 2\text{ A} = 240\text{W} P T ​ = 120 V × 2 A = 240 W ).

4. Parallel DC Circuits & Kirchhoff's Current Law (KCL)

A parallel circuit connects components across common electrical nodes, creating multiple independent branches for current flow. +-----------------------------------------------------------------------------------------+

  • | PARALLEL DC CIRCUIT RULES |
  • | |
  • | 1. Voltage is CONSTANT: E_Total = V₁ = V₂ = V₃ = ... = V_n |
  • | 2. Current is ADDITIVE: I_Total = I₁ + I₂ + I₃ + ... + I_n |
  • | 3. Resistance is RECIPROCAL: 1/R_Total = 1/R₁ + 1/R₂ + 1/R₃ + ... + 1/R_n |
  • | 4. Total Power is ADDITIVE: P_Total = P₁ + P₂ + P₃ + ... + P_n |
  • +-----------------------------------------------------------------------------------------+

Kirchhoff's Current Law (KCL):

Kirchhoff's Current Law states that the algebraic sum of currents entering and leaving any node (junction) is zero: ∑ I enter = ∑ I leave \sum I_{\text{enter}} = \sum I_{\text{leave}} ∑ I enter ​ = ∑ I leave ​ . In a parallel circuit, the total supply current entering the main junction equals the sum of the currents flowing through each parallel branch.

Methods for Calculating Equivalent Parallel Resistance ( R T R_T R T ​ ):

General Reciprocal Formula (Any number of branches): R T = 1 1 R 1 + 1 R 2 + 1 R 3 + ⋯ + 1 R n R_T = \frac{1}{\frac{1}{R_1} + \frac{1}{R_2} + \frac{1}{R_3} + \dots + \frac{1}{R_n}} R T ​ = R 1 ​ 1 ​ + R 2 ​ 1 ​ + R 3 ​ 1 ​ + ⋯ + R n ​ 1 ​ 1 ​

Product-Over-Sum Formula (Strictly for Two Parallel Branches): R T = R 1 × R 2 R 1 + R 2 R_T = \frac{R_1 \times R_2}{R_1 + R_2} R T ​ = R 1 ​ + R 2 ​ R 1 ​ × R 2 ​ ​

Equal Resistors Formula ( N N N identical resistors of value R R R ): R T = R N R_T = \frac{R}{N} R T ​ = N R ​

Critical Rule: The total equivalent resistance ( R T R_T R T ​ ) of any parallel circuit is always less than the resistance of the smallest branch resistor .

Current Divider Rule (Two Parallel Branches): I 1 = I T × ( R 2 R 1 + R 2 ) , I 2 = I T × ( R 1 R 1 + R 2 ) I_1 = I_T \times \left(\frac{R_2}{R_1 + R_2}\right), \quad I_2 = I_T \times \left(\frac{R_1}{R_1 + R_2}\right) I 1 ​ = I T ​ × ( R 1 ​ + R 2 ​ R 2 ​ ​ ) , I 2 ​ = I T ​ × ( R 1 ​ + R 2 ​ R 1 ​ ​ )

Step-by-Step Parallel Calculation:

A 24 V 24\text{V} 24 V DC industrial control power supply feeds three parallel branches: R 1 = 12 Ω R_1 = 12\ \Omega R 1 ​ = 12 Ω , R 2 = 20 Ω R_2 = 20\ \Omega R 2 ​ = 20 Ω , and R 3 = 30 Ω R_3 = 30\ \Omega R 3 ​ = 30 Ω .

Equivalent Total Resistance ( R T R_T R T ​ ): 1 R T = 1 12 + 1 20 + 1 30 = 5 60 + 3 60 + 2 60 = 10 60 = 1 6 ⟹ R T = 6 Ω \frac{1}{R_T} = \frac{1}{12} + \frac{1}{20} + \frac{1}{30} = \frac{5}{60} + \frac{3}{60} + \frac{2}{60} = \frac{10}{60} = \frac{1}{6} \implies R_T = 6\ \Omega R T ​ 1 ​ = 12 1 ​ + 20 1 ​ + 30 1 ​ = 60 5 ​ + 60 3 ​ + 60 2 ​ = 60 10 ​ = 6 1 ​ ⟹ R T ​ = 6 Ω

Branch Currents:

  • I 1 = 24 V 12 Ω = 2.0 A I_1 = \frac{24\text{V}}{12\ \Omega} = 2.0\text{ A} I 1 ​ = 12 Ω 24 V ​ = 2.0 A
  • I 2 = 24 V 20 Ω = 1.2 A I_2 = \frac{24\text{V}}{20\ \Omega} = 1.2\text{ A} I 2 ​ = 20 Ω 24 V ​ = 1.2 A
  • I 3 = 24 V 30 Ω = 0.8 A I_3 = \frac{24\text{V}}{30\ \Omega} = 0.8\text{ A} I 3 ​ = 30 Ω 24 V ​ = 0.8 A

Total Current Verification (KCL):

I T = I 1 + I 2 + I 3 = 2.0 + 1.2 + 0.8 = 4.0 A I_T = I_1 + I_2 + I_3 = 2.0 + 1.2 + 0.8 = 4.0\text{ A} I T ​ = I 1 ​ + I 2 ​ + I 3 ​ = 2.0 + 1.2 + 0.8 = 4.0 A .

Using Ohm's Law: I T = E T R T = 24 V 6 Ω = 4.0 A I_T = \frac{E_T}{R_T} = \frac{24\text{V}}{6\ \Omega} = 4.0\text{ A} I T ​ = R T ​ E T ​ ​ = 6 Ω 24 V ​ = 4.0 A .

5. Combination (Series-Parallel) DC Circuits

Real-world electrical installations—such as conductor runs with line resistance feeding parallel equipment banks—are combination circuits containing both series and parallel elements. +-----------------------------------------------------------------------------------------+

  • | STEP-BY-STEP CIRCUIT REDUCTION METHODOLOGY |
  • | |
  • | [STEP 1: Identify Sub-Networks] |
  • | Locate purely series or purely parallel resistor groups furthest from source. |
  • | | |
  • | v |
  • | [STEP 2: Calculate Equivalent Resistance of Clusters] |
  • | Solve parallel groups with reciprocal / product-over-sum: R_parallel = (R_a × R_b) / (R_a + R_b)|
  • | | |
  • | v |
  • | [STEP 3: Redraw the Simplified Equivalent Circuit] |
  • | Replace each cluster with a single equivalent resistor symbol. |
  • | | |
  • | v |
  • | [STEP 4: Calculate Total Circuit Resistance and Source Current] |
  • | Sum remaining series elements: R_Total = R_series + R_parallel. Then I_Total = E / R_Total|
  • | | |
  • | v |
  • | [STEP 5: Step Forward to Solve Individual Drops and Branch Currents] |
  • | Use V = I × R for series drops, then apply KVL and KCL across internal branches. |
  • +-----------------------------------------------------------------------------------------+

Comprehensive Worked Reduction Problem:

Consider a 120 V 120\text{V} 120 V DC circuit where resistor R 1 = 10 Ω R_1 = 10\ \Omega R 1 ​ = 10 Ω is connected in series with a parallel branch consisting of R 2 = 30 Ω R_2 = 30\ \Omega R 2 ​ = 30 Ω and R 3 = 60 Ω R_3 = 60\ \Omega R 3 ​ = 60 Ω , followed by another series resistor R 4 = 10 Ω R_4 = 10\ \Omega R 4 ​ = 10 Ω .

Simplify Parallel Cluster ( R 2 , 3 R_{2,3} R 2 , 3 ​ ): R 2 , 3 = R 2 × R 3 R 2 + R 3 = 30 × 60 30 + 60 = 1800 90 = 20 Ω R_{2,3} = \frac{R_2 \times R_3}{R_2 + R_3} = \frac{30 \times 60}{30 + 60} = \frac{1800}{90} = 20\ \Omega R 2 , 3 ​ = R 2 ​ + R 3 ​ R 2 ​ × R 3 ​ ​ = 30 + 60 30 × 60 ​ = 90 1800 ​ = 20 Ω

Calculate Total Circuit Resistance ( R T R_T R T ​ ): R T = R 1 + R 2 , 3 + R 4 = 10 Ω + 20 Ω + 10 Ω = 40 Ω R_T = R_1 + R_{2,3} + R_4 = 10\ \Omega + 20\ \Omega + 10\ \Omega = 40\ \Omega R T ​ = R 1 ​ + R 2 , 3 ​ + R 4 ​ = 10 Ω + 20 Ω + 10 Ω = 40 Ω

Calculate Total Circuit Current ( I T I_T I T ​ ): I T = E T R T = 120 V 40 Ω = 3.0 A I_T = \frac{E_T}{R_T} = \frac{120\text{V}}{40\ \Omega} = 3.0\text{ A} I T ​ = R T ​ E T ​ ​ = 40 Ω 120 V ​ = 3.0 A

Calculate Series Voltage Drops ( V R 1 V_{R1} V R 1 ​ and V R 4 V_{R4} V R 4 ​ ):

V R 1 = I T × R 1 = 3.0 A × 10 Ω = 30 V V_{R1} = I_T \times R_1 = 3.0\text{ A} \times 10\ \Omega = 30\text{V} V R 1 ​ = I T ​ × R 1 ​ = 3.0 A × 10 Ω = 30 V

V R 4 = I T × R 4 = 3.0 A × 10 Ω = 30 V V_{R4} = I_T \times R_4 = 3.0\text{ A} \times 10\ \Omega = 30\text{V} V R 4 ​ = I T ​ × R 4 ​ = 3.0 A × 10 Ω = 30 V

Calculate Parallel Bank Voltage Drop ( V parallel V_{\text{parallel}} V parallel ​ ):

Applying KVL: V parallel = E T − V R 1 − V R 4 = 120 V − 30 V − 30 V = 60 V V_{\text{parallel}} = E_T - V_{R1} - V_{R4} = 120\text{V} - 30\text{V} - 30\text{V} = 60\text{V} V parallel ​ = E T ​ − V R 1 ​ − V R 4 ​ = 120 V − 30 V − 30 V = 60 V .

Or via Ohm's Law: V parallel = I T × R 2 , 3 = 3.0 A × 20 Ω = 60 V V_{\text{parallel}} = I_T \times R_{2,3} = 3.0\text{ A} \times 20\ \Omega = 60\text{V} V parallel ​ = I T ​ × R 2 , 3 ​ = 3.0 A × 20 Ω = 60 V .

Calculate Individual Branch Currents ( I R 2 I_{R2} I R 2 ​ and I R 3 I_{R3} I R 3 ​ ):

I R 2 = V parallel R 2 = 60 V 30 Ω = 2.0 A I_{R2} = \frac{V_{\text{parallel}}}{R_2} = \frac{60\text{V}}{30\ \Omega} = 2.0\text{ A} I R 2 ​ = R 2 ​ V parallel ​ ​ = 30 Ω 60 V ​ = 2.0 A

I R 3 = V parallel R 3 = 60 V 60 Ω = 1.0 A I_{R3} = \frac{V_{\text{parallel}}}{R_3} = \frac{60\text{V}}{60\ \Omega} = 1.0\text{ A} I R 3 ​ = R 3 ​ V parallel ​ ​ = 60 Ω 60 V ​ = 1.0 A

KCL Check: I T = 2.0 A + 1.0 A = 3.0 A I_T = 2.0\text{ A} + 1.0\text{ A} = 3.0\text{ A} I T ​ = 2.0 A + 1.0 A = 3.0 A .

Total Power Summary:

P R 1 = 30 V × 3.0 A = 90 W P_{R1} = 30\text{V} \times 3.0\text{ A} = 90\text{W} P R 1 ​ = 30 V × 3.0 A = 90 W

P R 2 = 60 V × 2.0 A = 120 W P_{R2} = 60\text{V} \times 2.0\text{ A} = 120\text{W} P R 2 ​ = 60 V × 2.0 A = 120 W

  • P R 3 = 60 V × 1.0 A = 60 W P_{R3} = 60\text{V} \times 1.0\text{ A} = 60\text{W} P R 3 ​ = 60 V × 1.0 A = 60 W
  • P R 4 = 30 V × 3.0 A = 90 W P_{R4} = 30\text{V} \times 3.0\text{ A} = 90\text{W} P R 4 ​ = 30 V × 3.0 A = 90 W

P Total = 90 + 120 + 60 + 90 = 360 W P_{\text{Total}} = 90 + 120 + 60 + 90 = 360\text{W} P Total ​ = 90 + 120 + 60 + 90 = 360 W ( P T = 120 V × 3.0 A = 360 W P_T = 120\text{V} \times 3.0\text{ A} = 360\text{W} P T ​ = 120 V × 3.0 A = 360 W ).

Loading diagram... DC Combination Circuit Reduction & Current Flow