2.3 Three-Phase Power Systems (Delta & Wye Configurations)
Oklahoma Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety
1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection
2 Chapter 2: General Electrical Theory & Calculations
2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments
3 Chapter 3: General Installation Requirements (NEC Article 110)
3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable
4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)
4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)
5 Chapter 5: Services & Service Equipment (NEC Article 230)
5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)
6 Chapter 6: Electrical Load Calculations (NEC Article 220)
6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)
7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)
7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)
8 Chapter 8: Grounding and Bonding (NEC Article 250)
8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)
9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)
9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)
10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems
10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)
11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)
11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)
12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)
12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)
13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)
13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)
14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems
14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)
2.3 Three-Phase Power Systems (Delta & Wye Configurations)
Key Takeaways Explain This Topic AI
Three-phase AC power generation utilizes three sinusoidal voltages displaced 120 electrical degrees apart, delivering continuous non-pulsating torque to motors and providing a √3 (1.732) power capacity increase with substantial conductor copper savings over single-phase circuits.
In a balanced Wye (Star / Y) 4-wire system, Line-to-Line voltage is √3 (1.732) times the Line-to-Neutral phase voltage (V_Line = 1.732 × V_Phase), while Line current equals Phase winding current (I_Line = I_Phase); common standard systems are 208Y/120V and 480Y/277V.
In a balanced Delta (Δ) system, Line voltage equals Phase winding voltage (V_Line = V_Phase), while Line current is √3 (1.732) times Phase winding current (I_Line = 1.732 × I_Phase).
A 4-wire High-Leg Delta system (240/120V) provides 120V single-phase power from Phases A and C to neutral, 240V three-phase power across all phases, and a 'high leg' (Phase B) measuring 208V to neutral (120V × √3 = 208V), which NEC 110.15 mandates must be identified with orange marking and NEC 408.3(E) mandates must occupy the B-phase center bus in panelboards.
Total three-phase power is calculated using line values: True Power P = √3 × V_Line × I_Line × PF (Watts/kW) and Apparent Power S = √3 × V_Line × I_Line (VA/kVA), regardless of whether the system is connected in Wye or Delta.
Last updated: August 2026
Three-Phase Power Systems (Delta & Wye Configurations)
Three-phase electrical systems are the backbone of modern commercial and industrial electrical distribution. Compared to single-phase systems, three-phase power provides constant instantaneous power transfer, eliminates the need for auxiliary starting windings or capacitors on commercial motors, and delivers significantly greater power per pound of conductor copper. Oklahoma journeyman electricians must master the geometric and mathematical distinctions between Wye and Delta configurations, understand the regulatory requirements governing high-leg systems, and accurately calculate three-phase electrical loads.
1. Fundamentals of Three-Phase AC Power Generation
A three-phase AC generator (alternator) contains three sets of armature windings physically positioned 120 ∘ 120^\circ 12 0 ∘ apart around the stator circumference. When rotated through a magnetic field, the generator produces three identical sinusoidal voltages with an electrical phase displacement of 120 ∘ 120^\circ 12 0 ∘ ( 1 / 3 1/3 1/3 of a cycle) between phases. +-----------------------------------------------------------------------------------------+
- | THREE-PHASE VOLTAGE SINE WAVES |
- | |
- | Phase A (0°) Phase B (120°) Phase C (240°) |
- | +---"""---. +---"""---. +---"""---. |
- | / \ / \ / \ |
- | 0V --+-------------+-------+-------------+-------+-------------+-- 0V |
- | \ / \ / \ / |
- | `---------" `---------" `---------" |
- | |<--- 120° --->|<--- 120° --->|<--- 120° --->| |
- +-----------------------------------------------------------------------------------------+
Distinct Trade Advantages of Three-Phase Power:
Constant Instantaneous Power: While single-phase power pulses to zero twice every cycle ( 120 120 120 times per second at 60 Hz 60\text{ Hz} 60 Hz ), the mathematical sum of instantaneous power in a balanced three-phase system is completely constant: p ( t ) = P constant p(t) = P_{\text{constant}} p ( t ) = P constant . This eliminates mechanical vibration and torque pulsations in rotating machinery.
Self-Starting Motors: The 120 ∘ 120^\circ 12 0 ∘ phase offset inherently establishes a rotating magnetic field in the stator of three-phase induction motors, providing high starting torque without centrifugal switches, start capacitors, or auxiliary windings.
Conductor Material Efficiency: To deliver the same electrical power, a three-phase three-wire system requires only 75 % 75\% 75% of the conductor copper mass of an equivalent single-phase two-wire system ( 1.732 1.732 1.732 times more power using only 1.5 1.5 1.5 times the copper).
2. Wye (Star / Y) Connected Systems
In a Wye configuration, one end of each of the three transformer secondary windings is connected to a common central junction point, termed the neutral point ( X 0 X_0 X 0 or Star Point) . The opposite ends of the windings extend outward to provide the three line conductors ( A A A , B B B , and C C C ). +-----------------------------------------------------------------------------------------+
- | WYE SYSTEM CHARACTERISTICS |
- | |
- | Phase A |
- | o |
- | \ |
- | \ Winding A |
- | \ |
- | *--- Neutral (X0, N) |
- | / \ |
- | Winding B / \ Winding C |
- | / \ |
- | o o |
- | Phase B Phase C |
- | |
- | 1. Line Voltage (V_Line) = √3 × Phase Voltage (V_Phase) ≈ 1.732 × V_Phase |
- | 2. Line Current (I_Line) = Phase Winding Current (I_Phase) |
- +-----------------------------------------------------------------------------------------+
Standard Wye Distribution Voltages:
208 Y / 120 V 208\text{Y}/120\text{V} 208 Y /120 V , 3-Phase, 4-Wire:
Phase Voltage (Line-to-Neutral): 120 V 120\text{V} 120 V (Phases A - N A\text{-}N A - N , B - N B\text{-}N B - N , C - N C\text{-}N C - N ). Used for standard convenience receptacles, appliances, and office equipment.
Line Voltage (Line-to-Line): 120 V × 3 = 120 × 1.73205 = 207.85 V ≈ 208 V 120\text{V} \times \sqrt{3} = 120 \times 1.73205 = 207.85\text{V} \approx 208\text{V} 120 V × 3 = 120 × 1.73205 = 207.85 V ≈ 208 V (Phases A - B A\text{-}B A - B , B - C B\text{-}C B - C , C - A C\text{-}A C - A ). Used for commercial cooking equipment, small 3-phase motors, and water heaters.
480 Y / 277 V 480\text{Y}/277\text{V} 480 Y /277 V , 3-Phase, 4-Wire:
Phase Voltage (Line-to-Neutral): 277 V 277\text{V} 277 V (Phases A - N A\text{-}N A - N , B - N B\text{-}N B - N , C - N C\text{-}N C - N ). Extensively used for commercial LED/fluorescent high-bay lighting.
Line Voltage (Line-to-Line): 277 V × 3 = 277 × 1.73205 = 479.78 V ≈ 480 V 277\text{V} \times \sqrt{3} = 277 \times 1.73205 = 479.78\text{V} \approx 480\text{V} 277 V × 3 = 277 × 1.73205 = 479.78 V ≈ 480 V (Phases A - B A\text{-}B A - B , B - C B\text{-}C B - C , C - A C\text{-}A C - A ). Used for large commercial HVAC chillers, industrial machinery, and distribution transformers.
Neutral Current in Wye Systems:
Balanced Linear Loads: When identical single-phase loads are connected across all three phases ( I A = I B = I C I_A = I_B = I_C I A = I B = I C ), the return currents vectorially cancel at the neutral point, resulting in 0 Amps 0\text{ Amps} 0 Amps on the neutral ( I N = 0 A I_N = 0\text{ A} I N = 0 A ).
Unbalanced 4-Wire Formula: I N = I A 2 + I B 2 + I C 2 − ( I A I B + I B I C + I C I A ) I_N = \sqrt{I_A^2 + I_B^2 + I_C^2 - (I_A I_B + I_B I_C + I_C I_A)} I N = I A 2 + I B 2 + I C 2 − ( I A I B + I B I C + I C I A )
Nonlinear Triplen Harmonics: Electronic loads (LED drivers, variable frequency drives, computer power supplies) generate 3 rd , 9 th , 15 th 3^{\text{rd}}, 9^{\text{th}}, 15^{\text{th}} 3 rd , 9 th , 1 5 th harmonic currents that do not cancel but rather add arithmetically in the neutral conductor, requiring full-sized or oversized neutral conductors per NEC 220.61(C) and NEC 310.15(E).
3. Delta ( Δ \Delta Δ ) Connected Systems
In a Delta configuration, the three transformer secondary windings are connected head-to-tail in a closed triangle or loop. Line conductors ( A A A , B B B , C C C ) are tapped directly from the three vertices of the triangle. +-----------------------------------------------------------------------------------------+
- | DELTA SYSTEM CHARACTERISTICS |
- | |
- | Phase A |
- | o |
- | / \ |
- | / \ |
- | Winding 1 / \ Winding 3 |
- | / \ |
- | / \ |
- | o-----------o |
- | Phase B Winding 2 Phase C |
- | |
- | 1. Line Voltage (V_Line) = Phase Winding Voltage (V_Phase) |
- | 2. Line Current (I_Line) = √3 × Phase Winding Current (I_Phase) ≈ 1.732 × I_Phase |
- +-----------------------------------------------------------------------------------------+
Configurations of Delta Systems:
3-Wire 240V or 480V Delta (Ungrounded or Corner-Grounded): Typically used in heavy industrial manufacturing facilities dedicated strictly to three-phase motor loads without single-phase lighting requirements.
Corner-Grounded Delta: One corner phase conductor (typically Phase B) is intentionally connected to ground. It establishes a fixed voltage reference to ground ( 480 V 480\text{V} 480 V between ungrounded conductors, 480 V 480\text{V} 480 V to ground from the two ungrounded phases, and 0 V 0\text{V} 0 V from the grounded phase to ground). The grounded phase must be identified per NEC 200.6 with white or gray markings.
4. High-Leg Delta Systems ( 240 / 120 V 240/120\text{V} 240/120 V 4-Wire) & NEC Mandates
The 4-Wire High-Leg Delta system (also known historically in the field as the "wild leg", "stinger leg", or "orange leg") is widely utilized in commercial automotive shops, light industrial facilities, and fabrication buildings where the facility requires a large 240 V 240\text{V} 240 V 3-phase motor load combined with a modest 120 V 120\text{V} 120 V lighting and convenience receptacle load. +-----------------------------------------------------------------------------------------+
- | 4-WIRE HIGH-LEG DELTA CONFIGURATION |
- | |
- | Phase B (HIGH LEG) |
- | o |
- | / \ |
- | 240V Winding / \ 240V Winding |
- | / \ |
- | Phase A / | \ Phase C |
- | o-----/----+----\-----o |
- | \ / | \ / |
- | 120V \ / | 208V \ / 120V |
- | o-------+-------o |
- | | |
- | Neutral Point (N) |
- | (Center Tap of A-C) |
- | |
- | • Line-to-Line Voltages: A-B = 240V, B-C = 240V, C-A = 240V |
- | • Standard Single-Phase: A-N = 120V, C-N = 120V |
- | • High-Leg to Neutral: B-N = 120V × √3 ≈ 208V |
- +-----------------------------------------------------------------------------------------+
Mathematical Proof of High-Leg Voltage ( 208 V 208\text{V} 208 V to Neutral):
The center tap on transformer winding A - C A\text{-}C A - C divides the 240 V 240\text{V} 240 V winding into two 120 V 120\text{V} 120 V halves. The vertical altitude of the equilateral triangle represents the voltage from the High Leg (Phase B) to Neutral (N): V B - N = V Line 2 − ( V Line 2 ) 2 = 240 2 − 120 2 = 57 , 600 − 14 , 400 = 43 , 200 ≈ 207.85 V ≈ 208 V V_{B\text{-}N} = \sqrt{V_{\text{Line}}^2 - \left(\frac{V_{\text{Line}}}{2}\right)^2} = \sqrt{240^2 - 120^2} = \sqrt{57,600 - 14,400} = \sqrt{43,200} \approx 207.85\text{V} \approx 208\text{V} V B - N = V Line 2 − ( 2 V Line ) 2 = 24 0 2 − 12 0 2 = 57 , 600 − 14 , 400 = 43 , 200 ≈ 207.85 V ≈ 208 V V B - N = 120 V × 3 = 120 × 1.73205 = 207.85 V V_{B\text{-}N} = 120\text{V} \times \sqrt{3} = 120 \times 1.73205 = 207.85\text{V} V B - N = 120 V × 3 = 120 × 1.73205 = 207.85 V
Mandatory National Electrical Code Requirements:
NEC 110.15 High-Leg Identification:
"On a 4-wire, delta-connected system where the midpoint of one phase winding is grounded, only the conductor or busbar having the higher phase voltage to ground shall be durably and permanently marked by an outer finish that is orange in color , by tagging, or by other effective means. Such identification shall be made at each point where a connection is made if the grounded conductor is also present."
NEC 408.3(E)(1) Switchboard and Panelboard Bus Arrangement:
In switchboards, switchgear, and panelboards, phase busbars must be arranged A, B, C from left-to-right, top-to-bottom, or front-to-back .
On 3-phase, 4-wire high-leg delta systems, the high-leg conductor ( 208 V 208\text{V} 208 V to neutral) must connect to the "B" phase (center busbar) .
Exception: Metering equipment installations where utility company requirements mandate the high leg to occupy the right-hand (C-phase) socket position.
Catastrophic Hazard Warning:
Single-pole circuit breakers for 120 V 120\text{V} 120 V circuits must never be connected to the B-phase high-leg busbar. Connecting a 120 V 120\text{V} 120 V appliance or lighting circuit to the high leg exposes the equipment to 208 V 208\text{V} 208 V , resulting in immediate dielectric breakdown, smoke, catastrophic component destruction, and severe fire hazard.
5. Total Three-Phase Power Formulas & Calculations
Regardless of whether an installation is wired in Wye or Delta, total three-phase power is calculated using standard Line-to-Line Voltage ( V L V_L V L ) and Line Current ( I L I_L I L ) values. +-----------------------------------------------------------------------------------------+
- | THREE-PHASE POWER EQUATIONS |
- | |
- | 1. Apparent Power (S): S = √3 × V_Line × I_Line [Units: VA or kVA] |
- | 2. True Power (P): P = √3 × V_Line × I_Line × PF [Units: W or kW] |
- | 3. Reactive Power (Q): Q = √3 × V_Line × I_Line × sin θ [Units: VAR or kVAR] |
- | 4. Full-Load Line Current: I_Line = P / ( √3 × V_Line × PF ) [Units: Amperes] |
- | |
- | Where: √3 ≈ 1.73205 |
- +-----------------------------------------------------------------------------------------+
Comprehensive Worked Journeyman Calculation Scenarios:
Scenario A: Sizing a 3-Phase Commercial Transformer Bank
A commercial kitchen requires a 480 V 480\text{V} 480 V to 208 Y / 120 V 208\text{Y}/120\text{V} 208 Y /120 V , 3-phase dry-type step-down transformer rated at 75 kVA 75\text{ kVA} 75 kVA .
Primary Full-Load Current ( 480 V 480\text{V} 480 V Line-to-Line): I Primary = S 3 × V Line = 75 , 000 VA 1.73205 × 480 V = 75 , 000 831.38 = 90.21 A I_{\text{Primary}} = \frac{S}{\sqrt{3} \times V_{\text{Line}}} = \frac{75,000\text{ VA}}{1.73205 \times 480\text{V}} = \frac{75,000}{831.38} = 90.21\text{ A} I Primary = 3 × V Line S = 1.73205 × 480 V 75 , 000 VA = 831.38 75 , 000 = 90.21 A
Secondary Full-Load Current ( 208 V 208\text{V} 208 V Line-to-Line): I Secondary = S 3 × V Line = 75 , 000 VA 1.73205 × 208 V = 75 , 000 360.27 = 208.18 A I_{\text{Secondary}} = \frac{S}{\sqrt{3} \times V_{\text{Line}}} = \frac{75,000\text{ VA}}{1.73205 \times 208\text{V}} = \frac{75,000}{360.27} = 208.18\text{ A} I Secondary = 3 × V Line S = 1.73205 × 208 V 75 , 000 VA = 360.27 75 , 000 = 208.18 A
Scenario B: Industrial Motor Full-Load Current Calculation
A 50 HP 50\text{ HP} 50 HP , 480 V 480\text{V} 480 V , 3-phase industrial pump motor operates with an efficiency ( η \eta η ) of 90 % 90\% 90% and a power factor of 0.85 0.85 0.85 .
Convert Horsepower to Output Mechanical Watts: P out = 50 HP × 746 W/HP = 37 , 300 W P_{\text{out}} = 50\text{ HP} \times 746\text{ W/HP} = 37,300\text{ W} P out = 50 HP × 746 W/HP = 37 , 300 W
Calculate Total Electrical Input Power ( P in P_{\text{in}} P in ): P in = P out η = 37 , 300 W 0.90 = 41 , 444.44 W = 41.44 kW P_{\text{in}} = \frac{P_{\text{out}}}{\eta} = \frac{37,300\text{ W}}{0.90} = 41,444.44\text{ W} = 41.44\text{ kW} P in = η P out = 0.90 37 , 300 W = 41 , 444.44 W = 41.44 kW
Calculate Required Input Line Current ( I Line I_{\text{Line}} I Line ): I Line = P in 3 × V Line × PF = 41 , 444.44 W 1.73205 × 480 V × 0.85 = 41 , 444.44 706.68 = 58.65 A I_{\text{Line}} = \frac{P_{\text{in}}}{\sqrt{3} \times V_{\text{Line}} \times \text{PF}} = \frac{41,444.44\text{ W}}{1.73205 \times 480\text{V} \times 0.85} = \frac{41,444.44}{706.68} = 58.65\text{ A} I Line = 3 × V Line × PF P in = 1.73205 × 480 V × 0.85 41 , 444.44 W = 706.68 41 , 444.44 = 58.65 A