8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122)

Oklahoma Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety

1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection

2 Chapter 2: General Electrical Theory & Calculations

2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments

3 Chapter 3: General Installation Requirements (NEC Article 110)

3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable

4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)

4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)

5 Chapter 5: Services & Service Equipment (NEC Article 230)

5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)

6 Chapter 6: Electrical Load Calculations (NEC Article 220)

6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)

7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)

7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)

8 Chapter 8: Grounding and Bonding (NEC Article 250)

8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)

9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)

9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)

10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems

10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)

11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)

11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)

12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)

12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)

13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)

13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)

14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems

14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)

8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122)

Key Takeaways Explain This Topic AI

NEC 250.118 recognizes specific permitted types of equipment grounding conductors (EGCs), including copper/aluminum wire conductors, Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC), Electrical Metallic Tubing (EMT), listed Type AC armor, and limited lengths of Flexible Metal Conduit (FMC/LFMC).

Flexible Metal Conduit (FMC) is permitted as the sole EGC under NEC 250.118(5) only if terminated in listed fittings, protected by an OCPD rated 20A or less, total ground path length does not exceed 6 feet (1.8 m), and flexibility is not required after installation.

Under NEC Table 250.122, wire-type EGCs are sized strictly based on the rating or setting of the upstream automatic overcurrent protective device (fuse or circuit breaker) protecting the circuit.

NEC 250.122(B) mandates that if ungrounded circuit conductors are increased in size from the minimum required ampacity (such as for voltage drop compensation), wire-type EGCs MUST be increased in size proportionally according to the circular mil area of the ungrounded conductors.

In parallel raceway or multiconductor cable installations under NEC 250.122(F), a full-sized EGC based on the full rating of the circuit OCPD must be installed in EACH parallel conduit or raceway; dividing the EGC into smaller sizes across parallel conduits is strictly prohibited.

Last updated: August 2026

Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122)

The Equipment Grounding Conductor (EGC) is the unsung hero of electrical safety. Unlike the Grounding Electrode Conductor (which connects to the earth), the EGC runs alongside circuit conductors directly to utilization equipment, ensuring that any short circuit or ground fault to a metallic chassis finds an immediate, ultra-low-impedance metallic path back to the supply source to instantly trip the circuit breaker. On the Oklahoma Journeyman examination, sizing EGCs from NEC Table 250.122 , calculating proportional increases for voltage drop under 250.122(B) , and installing EGCs in parallel raceways under 250.122(F) are among the most heavily tested mathematical problems.

1. Permitted Types of Equipment Grounding Conductors (NEC 250.118)

NEC 250.118 defines the specific materials and wiring methods permitted to serve as equipment grounding conductors: +---------------------------------------------------------------------------------------------------+

  • | PERMITTED EQUIPMENT GROUNDING CONDUCTORS (NEC 250.118) |
  • | |
  • | METALLIC RACEWAYS & CABLES (Inherent EGC) WIRE-TYPE CONDUCTORS |
  • | ----------------------------------------- -------------------------------------------- |
  • | 1. Rigid Metal Conduit (RMC) 1. Copper, Aluminum, or Copper-Clad Aluminum |
  • | 2. Intermediate Metal Conduit (IMC) 2. Bare, Covered, or Insulated Wire |
  • | 3. Electrical Metallic Tubing (EMT) |
  • | 4. Armor of Type AC (BX) Cable with internal RESTRICTED RACEWAYS (Conditional EGC) |
  • | bonding strip -------------------------------------------- |
  • | 5. Listed Type MC Cable marked MCI-A 1. Flexible Metal Conduit (FMC) |
  • | 6. Copper sheath of Mineral-Insulated (MI) Cable 2. Liquidtight Flexible Metal Conduit (LFMC) |
  • +---------------------------------------------------------------------------------------------------+

Limitations on Flexible Raceways as EGCs (NEC 250.118(5) & (6)):

Raceway Type Maximum OCPD Rating Maximum Length in Ground Path Listing & Fitting Rules Flexibility After Install

Flexible Metal Conduit (FMC) 20 Amperes 6 feet (1.8 m) Must use listed fittings Prohibited if flexibility required

Liquidtight FMC (LFMC) (3/8" to 1/2") 20 Amperes 6 feet (1.8 m) Must use listed fittings Prohibited if flexibility required

Liquidtight FMC (LFMC) (3/4" to 1-1/4") 60 Amperes 6 feet (1.8 m) Must use listed fittings Prohibited if flexibility required

Critical Journeyman Exam Rule: If Flexible Metal Conduit (FMC) or LFMC exceeds 6 feet in length, or is protected by a breaker larger than 20A (or >60A for 3/4"+ LFMC), or supplies vibrating equipment where flexibility is required after installation (e.g., motors, transformers, rooftop HVAC units), a separate wire-type EGC must be pulled inside or outside the conduit (NEC 250.118(5)(d)).

2. Sizing Equipment Grounding Conductors (NEC Table 250.122)

Wire-type EGCs are sized strictly based on the rating or setting of the upstream automatic overcurrent protective device (OCPD) protecting the circuit conductors: +---------------------------------------------------------------------------------------------------+

  • | NEC TABLE 250.122: MINIMUM SIZE EQUIPMENT GROUNDING CONDUCTORS |
  • | |
  • | RATING OR SETTING OF UPSTREAM MINIMUM SIZE OF EGC |
  • | OVERCURRENT DEVICE (AMPERES) ----------------------------------------------- |
  • | COPPER (AWG/kcmil) ALUMINUM (AWG/kcmil) |
  • | -------------------------------------------- ----------------------- ---------------------- |
  • | 15 14 AWG 12 AWG |
  • | 20 12 AWG 10 AWG |
  • | 30 10 AWG 8 AWG |
  • | 40 or 60 10 AWG 8 AWG |
  • | 100 8 AWG 6 AWG |
  • | 200 6 AWG 4 AWG |
  • | 300 4 AWG 2 AWG |
  • | 400 3 AWG 1 AWG |
  • | 500 2 AWG 1/0 AWG |
  • | 600 1 AWG 2/0 AWG |
  • | 800 1/0 AWG 3/0 AWG |
  • | 1000 2/0 AWG 4/0 AWG |
  • | 1200 3/0 AWG 250 kcmil |
  • | 1600 4/0 AWG 350 kcmil |
  • | 2000 250 kcmil 400 kcmil |
  • +---------------------------------------------------------------------------------------------------+
  • 3. Proportional Adjustment for Conductor Upsizing / Voltage Drop (NEC 250.122(B))

When ungrounded phase conductors are increased in size from the minimum size required for the load (most commonly to prevent excessive voltage drop on long circuit runs), the wire-type EGC must be increased in size proportionally according to the circular mil area of the ungrounded conductors. +---------------------------------------------------------------------------------------------------+

  • | NEC 250.122(B) PROPORTIONAL EGC SIZING FORMULA & LOGIC |
  • | |
  • | Area_new_EGC = Area_orig_EGC × ( Area_upsized_phase / Area_orig_phase ) |
  • | |
  • | Why is this mandatory? |
  • | On a long conductor run, if phase conductors are upsized to reduce resistance and voltage drop, |
  • | leaving the EGC at standard size leaves the ground-fault loop impedance high. In a fault, |
  • | the voltage drop across the undersized EGC would elevate chassis touch potential to lethal levels|
  • | and delay the instantaneous trip of the circuit breaker! |
  • +---------------------------------------------------------------------------------------------------+

Step-by-Step Worked Voltage Drop / Proportional Upsizing Problem:

Scenario: A 50-Ampere, 240V branch circuit supplies an outdoor water pumping station located 350 feet from the panelboard. The minimum conductor size required for a 50A circuit is #8 AWG THHN Copper (rated 50A at 75°C). To limit voltage drop to under 3%, the ungrounded phase conductors are upsized to #4 AWG Copper .

Calculation Steps:

Find Circular Mil Area of Original Minimum Phase Conductor:

From NEC Chapter 9, Table 8: #8 AWG = 16 , 510 cmil 16,510\text{ cmil} 16 , 510 cmil .

Find Circular Mil Area of Upsized Phase Conductor:

From NEC Chapter 9, Table 8: #4 AWG = 41 , 740 cmil 41,740\text{ cmil} 41 , 740 cmil .

Find Standard EGC Size for a 50A OCPD:

From NEC Table 250.122: 50A OCPD requires #10 AWG Copper .

Area of #10 AWG Copper (Ch. 9, Table 8) = 10 , 380 cmil 10,380\text{ cmil} 10 , 380 cmil .

Apply the Proportional Adjustment Formula: Multiplier = 41 , 740 cmil 16 , 510 cmil = 2.52816 \text{Multiplier} = \frac{41,740\text{ cmil}}{16,510\text{ cmil}} = 2.52816 Multiplier = 16 , 510 cmil 41 , 740 cmil ​ = 2.52816 New Required EGC Area = 10 , 380 cmil × 2.52816 = 26 , 242.3 cmil \text{New Required EGC Area} = 10,380\text{ cmil} \times 2.52816 = 26,242.3\text{ cmil} New Required EGC Area = 10 , 380 cmil × 2.52816 = 26 , 242.3 cmil

Select Next Standard AWG Size from Chapter 9, Table 8:

#8 AWG = 16 , 510 cmil 16,510\text{ cmil} 16 , 510 cmil (Too small)

#6 AWG = 26 , 240 cmil 26,240\text{ cmil} 26 , 240 cmil (Standard industry round: 26 , 240 cmil ≈ 26 , 242 cmil 26,240\text{ cmil} \approx 26,242\text{ cmil} 26 , 240 cmil ≈ 26 , 242 cmil , #6 AWG is selected; if strict rounding applies, next size is #6 AWG).

Answer: The required equipment grounding conductor must be upsized to #6 AWG Copper .

4. EGCs in Parallel Raceways or Cables (NEC 250.122(F))

Where circuit conductors are run in parallel in two or more raceways or cables (e.g., an 800A feeder split across two parallel conduits), the rules for EGC installation are strictly enforced: +---------------------------------------------------------------------------------------------------+

  • | PARALLEL RACEWAY EGC INSTALLATION (NEC 250.122(F)(1)) |
  • | |
  • | 800A FEEDER OCPD |
  • | +-----------------------------------------------------------------------------------+ |
  • | | | |
  • | | Conduit 1: (3) 500 kcmil Phase + (1) 1/0 AWG Cu EGC <-- FULL SIZE EGC | |
  • | | | |
  • | | Conduit 2: (3) 500 kcmil Phase + (1) 1/0 AWG Cu EGC <-- FULL SIZE EGC | |
  • | +-----------------------------------------------------------------------------------+ |
  • | |
  • | CRITICAL CODE MANDATE: |
  • | Each parallel raceway must contain a FULL-SIZED equipment grounding conductor sized from |
  • | Table 250.122 based on the full 800A OCPD rating (1/0 AWG Cu in each pipe). |
  • | You CANNOT divide the 1/0 AWG EGC into two smaller conductors (such as two #4 AWG wires)! |
  • +---------------------------------------------------------------------------------------------------+

Why Must Each Parallel Conduit Contain a Full-Sized EGC?

If a ground fault occurs inside Conduit 1, the fault current flows almost entirely through the EGC inside Conduit 1 due to magnetic coupling and mutual inductance. If that EGC were undersized (half-sized), it would instantly vaporize under the 800A fault current before the upstream circuit breaker could clear the fault, resulting in conduit blowout and structural fire.

5. Cord-and-Plug Connected Equipment Grounding (NEC 250.114)

NEC 250.114 specifies which appliances and portable tools must have their exposed metal frames grounded via an equipment grounding conductor in the cord and attachment plug:

Residential Occupancies: Refrigerators, freezers, room air conditioners, clothes washing machines, clothes dryers, dishwashers, electrical aquarium equipment, sump pumps, and motor-operated tools (saws, drills, lawn mowers, snowblowers, hedge clippers).

Commercial & Industrial Occupancies: Hand-held motor-operated tools, cord-connected appliances, and all equipment operating at over 150 volts to ground.

Double-Insulated Exception (NEC 250.114 Exception): Listed tools and appliances protected by a system of double insulation (distinctively marked with the square-in-a-square symbol) are NOT required to be grounded.

Loading diagram... Equipment Grounding Conductor Sizing & Installation Decision Flowchart (NEC 250.122)