3.2 Electrical Connections, Terminations & Torque Requirements (110.14)

Oklahoma Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety

1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection

2 Chapter 2: General Electrical Theory & Calculations

2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments

3 Chapter 3: General Installation Requirements (NEC Article 110)

3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable

4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)

4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)

5 Chapter 5: Services & Service Equipment (NEC Article 230)

5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)

6 Chapter 6: Electrical Load Calculations (NEC Article 220)

6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)

7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)

7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)

8 Chapter 8: Grounding and Bonding (NEC Article 250)

8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)

9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)

9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)

10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems

10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)

11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)

11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)

12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)

12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)

13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)

13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)

14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems

14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)

3.2 Electrical Connections, Terminations & Torque Requirements (110.14)

Key Takeaways Explain This Topic AI

NEC 110.14(C) establishes termination temperature defaults: 60°C for circuits rated 100A or less (or conductors #14 through #1 AWG) unless marked for 75°C; 75°C for circuits over 100A (or conductors larger than #1 AWG).

When using 90°C rated conductors (such as THHN/THWN-2), the 90°C ampacity column in Table 310.16 is used for ambient temperature correction and raceway fill adjustment, but the final derated ampacity must never exceed the lowest terminal temperature rating in the circuit.

Dissimilar metals (copper and aluminum) in direct contact cause galvanic corrosion; terminations must use listed connectors marked 'AL7CU' (75°C) or 'AL9CU' (90°C), with antioxidant inhibitor compound applied per manufacturer instructions.

Splicing methods under NEC 110.14(B) require listed wire nuts, split-bolt connectors, compression sleeves, or exothermic welding, with insulation equal to the conductor or approved listed heat-shrink/insulating tape.

NEC 110.14(D) strictly mandates the use of calibrated torque tools (torque screwdrivers/wrenches) to tighten all electrical connections to manufacturer-specified values or Informative Annex I tables.

Last updated: August 2026

Electrical Connections, Terminations & Torque Requirements (NEC 110.14)

Electrical connections represent the most vulnerable points in any power distribution system. Loose terminations, improper temperature ratings, galvanic corrosion between dissimilar metals, and uncalibrated torquing are the leading causes of electrical fires, equipment burnouts, and arc flash incidents. NEC 110.14 sets forth rigorous rules governing terminal temperature ratings, splicing integrity, dissimilar metals, and mandatory tightening torque.

1. Terminal Temperature Ratings & Coordination (NEC 110.14(C))

Conductors are terminated on circuit breakers, disconnects, panelboard busbars, and motor terminals. Even if a conductor has an insulation rating of 90°C (such as THHN, THWN-2, or XHHW-2), the circuit cannot operate at a temperature higher than the lowest-rated terminal or component in the circuit. +-----------------------------------------------------------------------------+

  • | TERMINAL TEMPERATURE RULES (NEC 110.14(C)) |
  • | |
  • | CIRCUITS RATED 100A OR LESS CIRCUITS RATED OVER 100A |
  • | (Conductors #14 through #1 AWG) (Conductors larger than #1 AWG) |
  • | |
  • | - Default: 60°C Ampacity - Default: 75°C Ampacity |
  • | - Exception: 75°C permitted if ALL - 75°C column of Table 310.16 |
  • | equipment & terminals are listed is the standard baseline |
  • | and marked for 75°C - 90°C permitted only if all |
  • | terminations are rated 90°C |
  • +-----------------------------------------------------------------------------+

The 60°C vs. 75°C Baseline Rules:

Circuits Rated 100 Amperes or Less (Conductors #14 to #1 AWG):

Sizing conductors must be based on the 60°C temperature column of NEC Table 310.16.

Exception: Conductors with higher temperature insulation ratings (e.g., 75°C or 90°C) may be used at the 75°C column ampacity IF the equipment terminals, circuit breakers, and all connected devices are listed and marked for 75°C (commonly marked "75°C" or "60/75°C").

Circuits Rated Over 100 Amperes (Conductors Larger than #1 AWG):

Sizing conductors is based on the 75°C temperature column of NEC Table 310.16.

Conductors with 90°C insulation are permitted to be used at 75°C ampacity.

Separate Connector Ratings (Design Letter Form):

Terminals on equipment are often marked with dual ratings. For example, a modern molded-case circuit breaker rated 50A is typically marked "AL9CU 60/75°C", allowing the use of the 75°C conductor ampacity table.

The 90°C Ampacity Derating Principle

Most modern commercial building wire is rated 90°C (e.g., THHN / THWN-2). How do electricians apply 90°C conductors when terminals are rated 75°C?

Step 1: Use the 90°C column of Table 310.16 as the starting ampacity value for adjustment factors (more than 3 current-carrying conductors in raceway per Table 310.15(C)(1)) and correction factors (elevated ambient temperature per Table 310.15(B)(1) or (2)).

Step 2: Calculate the derated ampacity.

Step 3 (The Terminal Check): Compare the derated ampacity to the 75°C column ampacity. The maximum allowable continuous current cannot exceed the 75°C column value (or the 60°C column value if terminals are 60°C). +-----------------------------------------------------------------------------+

  • | WORKED DERATING & TERMINATION EXAMPLE |
  • | |
  • | - Circuit: 80A 3-phase feeder in 40°C (104°F) ambient |
  • | - Conductor: #4 AWG Copper THHN (90°C insulation) |
  • | - Raceways: 4 current-carrying conductors in EMT |
  • | - Terminals: Circuit breaker rated 75°C |
  • | |
  • | 1. Base 90°C Ampacity (#4 AWG Cu) = 95 Amperes |
  • | 2. Ambient Temp Correction (40°C from Table 310.15(B)(1)) = 0.91 |
  • | 3. Raceway Fill Adjustment (4 conductors from Table 310.15(C)(1)) = 0.80 |
  • | 4. Derated Ampacity = 95 A x 0.91 x 0.80 = 69.16 Amperes |
  • | 5. Terminal Check: 75°C Table 310.16 value for #4 AWG Cu = 85 Amperes |
  • | 6. Final Allowable Ampacity = 69.16 Amperes (governed by derating). |
  • | (If derated value had been 90A, it would be capped at 85A for 75°C lug)|
  • +-----------------------------------------------------------------------------+
  • 2. Conductor Dissimilar Metals & Corrosion (NEC 110.14)

Terminals and splicing devices must be identified for the specific conductor material (copper, aluminum, or copper-clad aluminum).

Galvanic Action & Thermal Expansion

Direct contact between dissimilar metals (e.g., copper touching aluminum) in the presence of moisture creates an electrochemical galvanic cell , rapidly oxidizing and eroding the aluminum.

Aluminum expands and contracts at a significantly higher rate than copper when heated under electrical load. When tightened into standard copper-only mechanical lugs, aluminum can "creep" or flow under pressure, becoming loose over repeated thermal cycles and generating intense localized heat.

Terminal Lug Markings:

CU: Listed for Copper conductors only.

AL: Listed for Aluminum conductors only.

CU/AL or AL/CU: Listed for both copper and aluminum (legacy 60°C rating).

AL7CU: Listed for aluminum or copper conductors at 75°C .

AL9CU: Listed for aluminum or copper conductors at 90°C .

Antioxidant Compounds (Oxide Inhibitors): Aluminum forms an invisible, high-resistance oxide film upon contact with air. When terminating stranded aluminum conductors, electricians must wire-brush the bare strands and apply a listed antioxidant compound (e.g., Noalox, Penetrox) unless the connector instructions state otherwise.

3. Splicing and Wire Connectors (NEC 110.14(B))

Conductors must be spliced or joined by approved splicing devices or by brazing, welding, or soldering with a fusible metal or alloy. Soldered splices must first be joined mechanically and electrically secure without solder before soldering. +-----------------------------------------------------------------------------+

  • | APPROVED SPLICING METHODS (110.14(B)) |
  • | |
  • | [Twist-On Wire Nuts] [Split-Bolt Connectors] [Compression Sleeves] |
  • | - Pressure spring - Dual-rated brass/bronze - Hydraulic/manual crimp |
  • | - Listed wire range - Requires listed spacer - Cold flow bond |
  • | - Dry indoor locations for Cu-to-Al splices - Solid/stranded joints |
  • | |
  • | [Insulation Restoration Mandate] |
  • | - Splices must be covered with insulation EQUAL to the original conductor |
  • | - Direct burial/submersible splices must be listed (UL 486D standard) |
  • +-----------------------------------------------------------------------------+

Splicing Rules & Requirements:

Insulation Equivalence: All splices and free ends of conductors must be covered with an insulation equivalent to that of the conductors or with an identified insulating device (such as listed heat-shrink tubing or rated electrical tape wrapped to equal or greater dielectric thickness).

Underground / Submersible Splices: Splicing conductors in wet locations, handholes, or direct burial underground requires splicing kits listed under UL 486D (sealed wire connector systems) with waterproof resin, gel-filled enclosures, or thick-wall adhesive-lined heat shrink.

4. Mandatory Tightening Torque Requirements (NEC 110.14(D))

Historically, field electricians tightened terminal screws and lugs "by feel." National fire investigation data proved that improper torque is a leading root cause of terminal overheating and electrical failures. NEC 110.14(D) makes calibrated torque tool use mandatory .

"Where a tightening torque is indicated as a numeric value on equipment or in the installation instructions provided by the manufacturer, a calibrated torque tool shall be used to achieve the indicated torque value, unless the equipment manufacturer has provided installation instructions for an alternative method of achieving the required torque."

Technical Realities of Torquing:

Under-Torquing: Creates insufficient contact surface pressure, resulting in high micro-contact resistance ( P = I 2 R P = I^2 R P = I 2 R ), localized heating, progressive oxidation, thermal runaway, and arcing.

Over-Torquing: Crushes and severs conductor strands, strips screw threads, cracks cast aluminum/copper lugs, and causes mechanical stress fracturing.

Calibrated Tools Required: Electricians must carry and use calibrated torque screwdrivers (inch-pounds) and torque wrenches (foot-pounds).

Informative Annex I (Table 110.14(D)): Where manufacturer torque values are missing or lost from older equipment, the default torque tables in Informative Annex I provide standardized values based on screw slot type, hex head size, and conductor gauge.

Loading diagram... Conductor Sizing & Terminal Temperature Coordination Workflow (NEC 110.14(C))