3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27)
Oklahoma Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety
1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection
2 Chapter 2: General Electrical Theory & Calculations
2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments
3 Chapter 3: General Installation Requirements (NEC Article 110)
3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable
4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)
4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)
5 Chapter 5: Services & Service Equipment (NEC Article 230)
5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)
6 Chapter 6: Electrical Load Calculations (NEC Article 220)
6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)
7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)
7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)
8 Chapter 8: Grounding and Bonding (NEC Article 250)
8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)
9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)
9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)
10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems
10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)
11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)
11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)
12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)
12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)
13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)
13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)
14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems
14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)
3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27)
Key Takeaways Explain This Topic AI
Working space depth for electrical equipment operating at 0–600V nominal to ground is governed by NEC Table 110.26(A)(1) across three conditions: Condition 1 (3 ft / 3 ft), Condition 2 (3 ft / 3.5 ft), and Condition 3 (3 ft / 4 ft).
Working space width must be at least 30 inches or equipment width (doors opening ≥90 degrees), with minimum headroom of 6.5 feet (78 in.) or equipment height under NEC 110.26(A)(2)-(3).
Dedicated Electrical Space (NEC 110.26(E)) protects indoor equipment from floor to 6 feet above equipment or the structural ceiling from foreign piping, ductwork, or systems; foreign systems in the zone above 6 ft must have leak protection.
Large equipment rated 1,200A or more and over 6 feet wide requires two personnel entry/exit doors (min 24 in wide x 6.5 ft high) equipped with listed panic hardware opening outward in the direction of egress (NEC 110.26(C)).
Live parts operating at 50V or more must be guarded against accidental contact by approved enclosures, elevation of 8 feet or more, or robust partitions (NEC 110.27).
Last updated: August 2026
Working Space, Clearances & Guarding of Live Parts (NEC 110.26 & 110.27)
Electrical equipment operating at 50 volts or more requires adequate physical space for personnel to examine, adjust, service, and maintain energized parts safely. Cramped electrical rooms, equipment blocked by storage, low ceilings, and foreign plumbing pipes running over switchboards are serious safety hazards that violate the NEC. On the Oklahoma Journeyman Electrician exam, mastering NEC 110.26 dimensions, Table 110.26(A)(1) conditions, dedicated space boundaries, and egress door hardware rules is essential.
1. Working Space Dimensions (NEC 110.26(A))
Working space must be provided and maintained around all electrical equipment likely to require examination, adjustment, servicing, or maintenance while energized (such as switchboards, panelboards, motor control centers, and safety disconnect switches). +-----------------------------------------------------------------------------+
- | THREE-DIMENSIONAL WORKING SPACE ENVELOPE |
- | |
- | 1. WIDTH (NEC 110.26(A)(2)): |
- | - Minimum 30 inches (762 mm) OR the width of equipment (greater). |
- | - Equipment can be offset within width space. |
- | - Enclosure doors/hinged panels must open at least 90 DEGREES. |
- | |
- | 2. HEIGHT / HEADROOM (NEC 110.26(A)(3)): |
- | - Minimum 6.5 feet (2.0 m / 78 inches) OR height of equipment (greater)|
- | - Exception: Service equipment/panelboards in existing dwellings ≤ 200A|
- | |
- | 3. DEPTH (NEC 110.26(A)(1) & Table 110.26(A)(1)): |
- | - Measured from exposed live parts or enclosure front. |
- | - Varies from 3.0 ft to 4.0 ft based on Voltage and Conditions 1, 2, 3.|
- | |
- | [STORAGE STRICTLY PROHIBITED (NEC 110.26(B))] |
- | - Working space shall NEVER be used for storage (boxes, brooms, pallets). |
- +-----------------------------------------------------------------------------+
- 2. Working Depth Clearances (NEC Table 110.26(A)(1))
The clear working depth in front of electrical equipment operating at 0 to 600 volts nominal to ground is determined by three specific environmental conditions:
Definitions of the Three Conditions:
Condition 1 (Insulated / Non-Conductive Opposite Side): Exposed live parts on one side of the working space and no live or grounded parts on the other side of the working space. (Example: An open panel facing a finished wood-stud or drywall partition with no grounded metal pipes or outlets).
Condition 2 (Grounded Surface Opposite Side): Exposed live parts on one side of the working space and grounded parts on the other side of the working space. Note: Concrete walls, brick, masonry, tile, grounded metal conduit, structural steel, and wet surfaces are legally considered grounded surfaces .
Condition 3 (Exposed Live Parts on Both Sides): Exposed live parts on both sides of the working space with the operator standing between them. (Example: Switchgear assemblies or panelboards installed directly opposite each other across an aisle where both can be serviced simultaneously).
- Nominal Voltage to Ground Condition 1 Clearance Condition 2 Clearance Condition 3 Clearance
- 0 – 150 Volts ; (e.g., 120/240V 1-ph, 120/208V 3-ph) 3.0 ft (914 mm) 3.0 ft (914 mm) 3.0 ft (914 mm)
151 – 600 Volts ; (e.g., 277/480V 3-ph, 480V Delta, 600V) 3.0 ft (914 mm) 3.5 ft (1.07 m / 42 in.) 4.0 ft (1.22 m / 48 in.)
Exam Key: Notice that for 0–150V nominal to ground (such as a 120/208V panel where voltage to ground is 120V), the working depth is 3.0 feet for all three conditions . For a 277/480V system (where voltage to ground is 277V), Condition 1 is 3.0 ft, Condition 2 is 3.5 ft, and Condition 3 is 4.0 ft.
3. Dedicated Electrical Space (NEC 110.26(E))
Indoor service equipment, switchboards, switchgear, panelboards, and motor control centers must be protected from physical damage and water leakage by establishing a Dedicated Electrical Space . +-----------------------------------------------------------------------------+
- | INDOOR DEDICATED ELECTRICAL SPACE (NEC 110.26(E)(1)) |
- | |
- | ================ STRUCTURAL CEILING / ROOF DECK ===================== |
- | |
- | -------------------- FOREIGN SYSTEM ZONE --------------------------- |
- | - Foreign piping (sprinklers, water, chilled water) allowed ONLY if |
- | equipped with leak protection shields or drip pans. |
- | |
- | ------------------- 6-FOOT DEDICATED CEILING ---------------------- |
- | ^ |
- | | DEDICATED EQUIPMENT SPACE (NO FOREIGN SYSTEMS PERMITTED) |
- | | - Extends from floor to 6 feet above equipment (or to structural |
- | 6 FT ceiling, whichever is lower). |
- | | - Footprint equal to width and depth of the electrical equipment. |
- | v - STRICTLY PROHIBITED: Plumbing, sewer, gas, chilled water, ducts. |
- | +-----------------------------------------------------------------+ |
- | | PANELBOARD / SWITCHBOARD | |
- | | (Electrical Equipment) | |
- | +-----------------------------------------------------------------+ |
- | ========================== FINISHED FLOOR =========================== |
- +-----------------------------------------------------------------------------+
Dedicated Space Rules Breakdown:
Dedicated Equipment Space (110.26(E)(1)(a)):
Spans the width and depth of the equipment, extending from the floor up to a height of 6.0 feet (1.8 m) above the equipment or to the structural ceiling (whichever is lower).
No foreign piping, ducts, leak protection apparatus, or foreign equipment shall be located in this zone.
Only electrical raceways, cables, and equipment associated with the electrical installation are permitted.
Foreign Systems Space (110.26(E)(1)(b)):
The space above the 6-foot dedicated zone up to the structural ceiling is permitted to contain foreign systems (e.g., fire sprinkler branch piping, HVAC ducts, chilled water supply) only if protection is provided (such as drip pans, protective covers, or shielding) to prevent condensation, leaks, or breaks from damaging the electrical equipment.
4. Large Equipment Access & Entrance Rules (NEC 110.26(C))
When high-amperage equipment experiences an internal arc flash or explosion, an electrician inside the workspace must be able to escape instantly without becoming trapped. +-----------------------------------------------------------------------------+
- | LARGE EQUIPMENT EGRESS RULES (NEC 110.26(C)) |
- | |
- | [CRITERIA: Rated 1,200A or More AND Over 6.0 Feet (1.8 m) Wide] |
- | |
- | 1. TWO ENTRANCE / EXIT DOORS: |
- | - One entrance/egress door at EACH END of the working space. |
- | - Minimum door dimensions: 24 inches wide by 6.5 feet high. |
- | |
- | 2. EXCEPTION (SINGLE DOOR PERMITTED IF): |
- | - Continuous unobstructed exit path where workspace depth is DOUBLED; |
- | OR continuous unobstructed travel path away from equipment. |
- | |
- | 3. PERSONNEL PANIC HARDWARE (NEC 110.26(C)(3)): |
- | - Doors within 25 FEET from nearest edge of working space must: |
- | a) Open in direction of egress (SWING OUTWARD). |
- | b) Be equipped with listed PANIC HARDWARE or fire exit push-bars. |
- +-----------------------------------------------------------------------------+
- 5. Guarding of Live Parts (NEC 110.27)
Live parts of electrical equipment operating at 50 volts or more must be guarded against accidental contact by approved enclosures or by any of the following methods:
Location in a Room or Enclosure: Accessible only to qualified persons (e.g., locked electrical vault or fenced enclosure).
Elevation: Located on a suitable balcony, gallery, or platform elevated at least 8.0 feet (2.4 m) above the floor or working surface.
Partitions or Screens: Substantial partitions arranged so that only qualified personnel have access.