11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62)
Oklahoma Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety
1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection
2 Chapter 2: General Electrical Theory & Calculations
2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments
3 Chapter 3: General Installation Requirements (NEC Article 110)
3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable
4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)
4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)
5 Chapter 5: Services & Service Equipment (NEC Article 230)
5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)
6 Chapter 6: Electrical Load Calculations (NEC Article 220)
6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)
7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)
7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)
8 Chapter 8: Grounding and Bonding (NEC Article 250)
8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)
9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)
9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)
10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems
10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)
11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)
11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)
12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)
12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)
13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)
13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)
14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems
14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)
11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62)
Key Takeaways Explain This Topic AI
Motor feeder conductors supplying two or more motors must have an allowable ampacity not less than 125% of the highest-rated motor full-load current (FLC) plus 100% of all other motor FLCs (NEC 430.24), multiplying only ONE motor by 125% if highest ratings are identical.
Where a feeder supplies both motor loads and non-motor loads (lighting, appliances, general receptacles), NEC 430.25 mandates that conductors are sized to carry 125% of the continuous non-motor load, 100% of non-continuous non-motor load, 125% of the highest motor FLC, plus 100% of all other motor FLCs.
Feeder short-circuit and ground-fault protection (NEC 430.62(A)) cannot exceed the largest calculated branch-circuit protective device rating for any single motor in the group PLUS the sum of the full-load currents (FLCs) of all other motors supplied by the feeder.
CRITICAL ROUNDING RULE: Under NEC 430.62(A), the calculated feeder overcurrent protective device rating must NEVER be rounded up to the next higher standard rating; it must be rounded DOWN to the next lower standard rating in NEC 240.6(A) if the calculated sum does not match a standard size.
Feeder overcurrent protective devices can be sized for future load expansion only if the feeder conductors are correspondingly increased in size to support the future capacity (NEC 430.62(B)).
Last updated: August 2026
Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (NEC 430.24 & 430.62)
In industrial and commercial electrical distribution systems, a single feeder commonly supplies an entire motor control center (MCC) or a group of discrete motor branch circuits. Sizing motor feeders requires careful application of two core principles: preventing cumulative conductor overheating from multiple running motors, and providing feeder overcurrent protection large enough to permit the largest motor to start while remaining small enough to protect against major short circuits. On the Oklahoma Journeyman Electrician exam, multi-motor feeder calculations are heavily tested.
1. Feeder Conductor Sizing for Multiple Motors (NEC 430.24)
Conductors supplying several motors must have an allowable ampacity not less than the sum of the full-load current (FLC) ratings of all the motors supplied, plus 25% of the highest-rated motor in the group: +-----------------------------------------------------------------------------+
- | NEC 430.24 MOTOR FEEDER SIZING FORMULA |
- | |
- | I_feeder >= (1.25 x I_FLC_highest) + Sum(I_FLC_all_other_motors) |
- | |
- | WHERE: |
- | - I_FLC_highest is the Table FLC of the single largest motor in group. |
- | - Sum(I_FLC_all_other_motors) is the sum of 100% of all other motor FLCs. |
- | - All FLC values MUST come from NEC Tables 430.248 or 430.250! |
- +-----------------------------------------------------------------------------+
- Identical Largest Motors Rule
Where two or more motors in the group have the identical highest full-load current rating , only one motor is considered the highest rated and multiplied by 125%. The other identical motor(s) are added at 100% of their Table FLC.
Mixed Loads: Motors Plus Other Loads (NEC 430.25)
Where a feeder supplies both motors and other electrical loads (such as continuous lighting, heaters, and general convenience receptacles), the minimum feeder ampacity is calculated as: I feeder = ( 1.25 × I FLC, largest motor ) + ∑ ( I FLC, other motors ) + ( 1.25 × I continuous loads ) + ( 1.00 × I non-continuous loads ) I_{\text{feeder}} = (1.25 \times I_{\text{FLC, largest motor}}) + \sum(I_{\text{FLC, other motors}}) + (1.25 \times I_{\text{continuous loads}}) + (1.00 \times I_{\text{non-continuous loads}}) I feeder = ( 1.25 × I FLC, largest motor ) + ∑ ( I FLC, other motors ) + ( 1.25 × I continuous loads ) + ( 1.00 × I non-continuous loads )
2. Feeder Short-Circuit & Ground-Fault Protection (NEC 430.62)
Feeder overcurrent protective devices (OCPDs) must be sized to allow the largest motor in the group to start without tripping the main feeder protective device, while all other motors are already running at full load. NEC 430.62(A) establishes the mandatory mathematical procedure: +-----------------------------------------------------------------------------+
- | NEC 430.62(A) FEEDER OCPD SIZING FORMULA |
- | |
- | Feeder OCPD Max = (Largest Branch OCPD) + Sum(I_FLC_all_other_motors) |
- | |
- | WHERE: |
- | - Largest Branch OCPD = The MAXIMUM permitted branch-circuit short- |
- | circuit protective device rating for the LARGEST motor under Table |
- | 430.52 (including the Round-Up rule under 430.52(C)(1) Ex 1). |
- | - Sum(I_FLC_all_other_motors) = The sum of 100% Table FLCs of all other |
- | motors in the group. |
- | |
- | *** THE GOLDEN RULE OF MOTOR FEEDERS: ROUND DOWN! *** |
- | If the calculated sum does NOT match a standard rating in NEC 240.6(A), |
- | you MUST select the NEXT LOWER standard ampere rating. |
- | Rounding UP is a SEVERE CODE VIOLATION under NEC 430.62(A)! |
+-----------------------------------------------------------------------------+ +-----------------------------------------------------------------------------+
- | CONTRASTING ROUNDING RULES: BRANCH OCPD VS. FEEDER OCPD |
- | |
- | BRANCH CIRCUIT OCPD (NEC 430.52(C)(1) Ex 1): |
- | - Round UP to the NEXT HIGHER standard rating in NEC 240.6(A). |
- | |
- | FEEDER OCPD (NEC 430.62(A)): |
- | - Round DOWN to the NEXT LOWER standard rating in NEC 240.6(A). |
- +-----------------------------------------------------------------------------+
- 3. Complete Step-by-Step Multi-Motor Feeder Calculation
Comprehensive Scenario: An industrial feeder supplies a motor control center (MCC) operating at 460 Volts, 3-Phase, 3-Wire . The MCC supplies three continuous-duty squirrel-cage induction motors:
- Motor 1: 30 HP, 460V, 3-phase
- Motor 2: 15 HP, 460V, 3-phase
- Motor 3: 10 HP, 460V, 3-phase
Inverse-time circuit breakers are used throughout for both branch-circuit and feeder protection. All conductors are 75°C THHN Copper. +-----------------------------------------------------------------------------+
- | WORKED CALCULATION ARCHITECTURE DIAGRAM |
- | |
- | [ 460V 3-Phase Main Distribution Panel ] |
- | | |
- | [ Feeder Breaker: ??? A ] |
- | | |
- | ===== Feeder Conductor (Ampacity >= 85A) =====> [ Motor Control Center ] |
- | | | | |
- | +---------------------------+ | +-----+ |
- | | | | |
- | [100A Breaker] [60A Breaker] [35A Breaker]|
- | | | | |
- | Motor 1 (30 HP) Motor 2 (15 HP) Motor 3 (10 HP)
- | FLC = 40.0 A FLC = 21.0 A FLC = 14.0 A
- +-----------------------------------------------------------------------------+
- Step 1: Look Up Table Full-Load Currents (NEC Table 430.250)
- Motor 1 (30 HP, 460V): FLC = 40.0 Amperes (Highest rated motor)
- Motor 2 (15 HP, 460V): FLC = 21.0 Amperes
- Motor 3 (10 HP, 460V): FLC = 14.0 Amperes
Step 2: Calculate Minimum Feeder Conductor Ampacity (NEC 430.24) I feeder = ( 1.25 × 40.0 A ) + 21.0 A + 14.0 A I_{\text{feeder}} = (1.25 \times 40.0\text{ A}) + 21.0\text{ A} + 14.0\text{ A} I feeder = ( 1.25 × 40.0 A ) + 21.0 A + 14.0 A I feeder = 50.0 A + 21.0 A + 14.0 A = 85.0 Amperes I_{\text{feeder}} = 50.0\text{ A} + 21.0\text{ A} + 14.0\text{ A} = 85.0\text{ Amperes} I feeder = 50.0 A + 21.0 A + 14.0 A = 85.0 Amperes
Conductor Selection (NEC Table 310.16, 75°C Cu):
#4 AWG THHN Cu has an allowable ampacity of 85 Amperes (exact match).
(If 90°C derating is needed, #3 AWG THHN Cu rated 100A at 75°C provides generous margin).
Step 3: Determine Individual Motor Branch Circuit Breakers (NEC Table 430.52)
Using inverse-time circuit breakers (250% multiplier):
Motor 1 (30 HP): 40.0 A × 2.50 = 100.0 A → 40.0\text{ A} \times 2.50 = 100.0\text{ A} \rightarrow 40.0 A × 2.50 = 100.0 A → 100A Breaker (Exact standard rating in 240.6(A)).
Motor 2 (15 HP): 21.0 A × 2.50 = 52.5 A → 21.0\text{ A} \times 2.50 = 52.5\text{ A} \rightarrow 21.0 A × 2.50 = 52.5 A → Round UP under 430.52(C)(1) Ex 1 to 60A Breaker .
Motor 3 (10 HP): 14.0 A × 2.50 = 35.0 A → 14.0\text{ A} \times 2.50 = 35.0\text{ A} \rightarrow 14.0 A × 2.50 = 35.0 A → 35A Breaker (Exact standard rating in 240.6(A)).
Step 4: Calculate Maximum Feeder Circuit Breaker Rating (NEC 430.62(A)) Feeder OCPD Max = ( Branch OCPD of Largest Motor ) + ∑ ( I FLC of other motors ) \text{Feeder OCPD Max} = (\text{Branch OCPD of Largest Motor}) + \sum(I_{\text{FLC of other motors}}) Feeder OCPD Max = ( Branch OCPD of Largest Motor ) + ∑ ( I FLC of other motors ) Feeder OCPD Max = 100.0 A + 21.0 A + 14.0 A = 135.0 Amperes \text{Feeder OCPD Max} = 100.0\text{ A} + 21.0\text{ A} + 14.0\text{ A} = 135.0\text{ Amperes} Feeder OCPD Max = 100.0 A + 21.0 A + 14.0 A = 135.0 Amperes
Select Standard Rating from NEC 240.6(A):
Standard ratings in this range are: 100A, 110A, 125A , 150A , 175A.
135 Amperes does not correspond to a standard rating.
Applying the Mandatory Round-Down Rule: We must select the NEXT LOWER standard rating = 125 Amperes .
Exam Warning: Selecting 150 Amperes is a classic licensing examination failure trap!