Study guide
1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know
Oklahoma Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety
1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection
2 Chapter 2: General Electrical Theory & Calculations
2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments
3 Chapter 3: General Installation Requirements (NEC Article 110)
3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable
4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)
4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)
5 Chapter 5: Services & Service Equipment (NEC Article 230)
5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)
6 Chapter 6: Electrical Load Calculations (NEC Article 220)
6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)
7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)
7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)
8 Chapter 8: Grounding and Bonding (NEC Article 250)
8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)
9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)
9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)
10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems
10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)
11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)
11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)
12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)
12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)
13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)
13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)
14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems
14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)
1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know
Key Takeaways Explain This Topic AI
The Oklahoma Uniform Building Code Commission adopted the 2023 NEC as the statewide minimum code for commercial electrical construction under 59 O.S. § 1000.23, effective September 14, 2024 (OAC Title 748, Chapter 20, Subchapter 10).
Oklahoma modified 210.8(F) to delete the expiration date on Exception No. 2, so listed HVAC equipment remains exempt from the outdoor dwelling GFCI requirement in Oklahoma rather than losing the exemption on a sunset date.
Oklahoma added 422.16(B)(5), permitting a gas-fired central furnace serving a dwelling unit to be cord-and-plug connected with an equipment grounding conductor, a grounding-type plug, adequate ampacity, protection from physical damage, and a cord no longer than 9 feet.
None of Informative Annexes A through K are adopted as part of the Oklahoma statewide minimum code (OAC 748:20-10-3), although the annual-permit provision of Annex H 80.19(D) was adopted with modifications.
The OUBCC did not pull, review, or incorporate NFPA errata or Tentative Interim Amendments to the 2023 NEC, so the printed 2023 NEC as amended by Subchapter 10 is the governing text.
Last updated: August 2026
1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know
The PSI Candidate Information Bulletin does not simply say "2023 NEC." It says NFPA 70 — National Electrical Code, 2023 Edition, as revised and adopted by the Oklahoma Uniform Building Code Commission. That qualifier matters, because Oklahoma changed two sections of the Code and declined to adopt several others. A candidate who studies a generic national journeyman course will study one of those two sections backwards.
- 1. The Adoption Chain +-----------------------------------------------------------------------------+
- | HOW THE CODE BECOMES LAW IN OKLAHOMA |
- | |
- | NFPA publishes NFPA 70 (NEC), 2023 Edition |
- | | |
- | v |
- | OUBCC adopts it under 59 O.S. Sec. 1000.23 as the STATEWIDE MINIMUM |
- | CODE for commercial electrical construction -> OAC Title 748, |
- | Chapter 20, Subchapter 10 (effective 9-14-2024) |
- | | |
- | v |
- | OAC 158:40-1-4 makes the OUBCC-adopted NEC (plus the electrical portion |
- | of the adopted IRC) the CIB "standard of installation" |
- | | |
- | v |
- | Municipal inspection departments enforce it in the field |
- | (59 O.S. Sec. 1693); local amendments must meet or exceed the minimum |
- +-----------------------------------------------------------------------------+
Three consequences follow from the phrase statewide minimum code for commercial electrical construction :
It is a floor, not a ceiling. Another jurisdiction inside Oklahoma may adopt more stringent local requirements; it may not adopt less.
One- and two-family dwellings are reached through the IRC. OAC 158:40-1-4 names both the NEC and the electrical portion of the International Residential Code as the standards of installation, each as adopted by the OUBCC.
Anything Subchapter 10 does not modify is adopted as published. OAC 748:20-10-4 states that all chapters and provisions not specifically addressed as modified, deleted, moved, or removed are adopted without modification.
2. Amendment One — 210.8(F) Outdoor Outlets (Chapter 2)
The national 2023 text of 210.8(F) requires GFCI protection for outdoor outlets serving dwelling units, with an exception for listed HVAC equipment that carried an expiration date . Oklahoma deleted that expiration date. As adopted by OAC 748:20-10-8, the Oklahoma rule reads:
All outdoor outlets for dwellings, other than those covered in 210.8(A) Exception No. 1, supplied by single-phase branch circuits rated 150 volts or less to ground and 50 amperes or less, shall be provided with GFCI protection, including outlets installed in:
- Garages that have floors located at or below grade
- Accessory buildings
- Boathouses
If equipment supplied by an outlet covered by this section is replaced, the outlet shall be provided with GFCI protection.
Exception No. 1: GFCI protection shall not be required on lighting outlets other than those covered by 210.8(C). Exception No. 2: GFCI protection shall not be required for listed HVAC equipment.
Question on the exam Oklahoma answer
Does a listed outdoor condensing unit at a dwelling need GFCI protection? No — Exception No. 2 applies, and Oklahoma removed the sunset date that would otherwise have retired it.
Does an outdoor lighting outlet at a dwelling need GFCI protection? No , unless it falls under 210.8(C) (the crawl-space/lighting provisions referenced there).
A homeowner replaces an outdoor outlet-supplied appliance. Any new obligation? Yes — replacing the equipment supplied by such an outlet triggers GFCI protection for that outlet.
Does the rule reach a detached garage or a boathouse? Yes — garages with floors at or below grade, accessory buildings, and boathouses are named explicitly.
3. Amendment Two — 422.16(B)(5) Gas-Fired Central Furnaces (Chapter 4)
Oklahoma added a subsection to Article 422 that does not exist in the national Code. OAC 748:20-10-10 adopts Chapter 4 with this addition:
422.16(B)(5) Gas-fired central furnaces. Gas-fired furnaces supplying dwelling units shall be permitted to be connected by a flexible cord-and-plug. The flexible cord shall have an equipment grounding conductor and be terminated into a grounding-type attachment plug. The cord and attachment plug shall have sufficient ampacity for the load, and shall be routed or otherwise protected to prevent physical damage to the cord or attachment plug. The cord length shall not be greater than 9 feet.
The stated purpose is practical: a cord-and-plug furnace connection lets a homeowner move the furnace onto a portable generator for heat during an outage. Five conditions travel with the allowance, and an exam item will usually change exactly one of them:
The occupancy must be a dwelling unit .
The furnace must be gas-fired (this is not a blanket cord allowance for electric furnaces or air handlers).
The cord must contain an equipment grounding conductor and terminate in a grounding-type attachment plug.
The cord and plug must have sufficient ampacity for the load .
The cord must be routed or protected against physical damage and must not exceed 9 feet .
4. What Oklahoma Did Not Adopt
Informative Annexes A through K are not adopted (OAC 748:20-10-3). They remain printed in the codebook you carry into the test center — Annex C conduit-fill tables, Annex D calculation examples, Annex H administration — and PSI writes conduit-fill items to those tables, but they are not part of Oklahoma’s enforceable statewide minimum code. Other jurisdictions in Oklahoma may adopt any or all of the annexes under 59 O.S. § 1000.29.
One annex provision was pulled back in with modifications: the annual permit of Annex H 80.19(D), rewritten to require the permit holder to keep detailed alteration records and to have the building official collect the per-permit fees at the end of the annual term.
Errata and Tentative Interim Amendments were not incorporated. OAC 748:20-10-1(c) states plainly that the OUBCC has not pulled, reviewed, or incorporated any published errata or TIAs from the NFPA website. The governing text is the printed 2023 NEC as amended by Subchapter 10.
Article 90 was adopted for continuity only , and only to the extent its provisions do not conflict with Oklahoma law or with the lawful exercise of code administration and enforcement jurisdiction.
Warning
Chapter 1, Chapter 5, Chapter 6, Chapter 7, and Chapter 8 modifications from earlier Oklahoma adoptions were revoked in the 2024 rulemaking. "Revoked" in this document does not delete the corresponding NEC chapter — it means the earlier Oklahoma modification is gone and the language reverts to the published 2023 NEC without amendment. Do not study an old Oklahoma amendment list.