7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21)

Oklahoma Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety

1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection

2 Chapter 2: General Electrical Theory & Calculations

2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments

3 Chapter 3: General Installation Requirements (NEC Article 110)

3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable

4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)

4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)

5 Chapter 5: Services & Service Equipment (NEC Article 230)

5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)

6 Chapter 6: Electrical Load Calculations (NEC Article 220)

6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)

7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)

7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)

8 Chapter 8: Grounding and Bonding (NEC Article 250)

8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)

9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)

9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)

10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems

10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)

11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)

11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)

12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)

12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)

13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)

13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)

14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems

14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)

7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21)

Key Takeaways Explain This Topic AI

The Point of Supply Rule (NEC 240.21) requires overcurrent protection at conductor origins, with tap rules (240.2) serving as strict exceptions where overcurrent protection ahead of the tap exceeds normal conductor limits.

The 10-Foot Feeder Tap Rule (NEC 240.21(B)(1)) requires: length max 10 ft; ampacity not less than computed load and not less than rating of device supplied / termination OCPD; enclosed in raceway; does not extend beyond equipment.

The 25-Foot Feeder Tap Rule (NEC 240.21(B)(2)) requires: length max 25 ft; ampacity not less than 1/3 of upstream feeder OCPD rating; protected from physical damage; terminates in a single circuit breaker or set of fuses limiting load to tap ampacity.

Outside feeder taps of unlimited length (NEC 240.21(B)(5)) are permitted outdoors if protected from physical damage and terminated in a single disconnect with overcurrent protection at the building entrance.

Transformer secondary taps (NEC 240.21(C)) cannot rely on primary overcurrent protection and must satisfy the 10-ft (1/10th ratio) or 25-ft (1/3rd ratio) primary-to-secondary voltage ratio formulas.

Last updated: August 2026

Feeder & Branch Circuit Tap Rules (NEC 240.21)

In standard electrical distribution, every conductor must be protected at the exact point where it receives its supply. However, running full-sized conductors throughout a large industrial plant or commercial building to feed small subpanels, motor controllers, or disconnects is economically prohibitive and physically impractical. NEC 240.21 provides specific Tap Rules that permit conductors to be tapped from larger feeders without an overcurrent protective device at the tap point, provided rigorous physical protection, length, and termination criteria are met.

  • 1. The Fundamental Principle & Tap Conductor Definition
  • The Point of Supply Rule (NEC 240.21)

NEC 240.21 General Rule: Overcurrent protection shall be provided in each ungrounded circuit conductor at the point where the conductor receives its supply, except as specifically permitted in 240.21(A) through (H).

Definition of a Tap Conductor (NEC 240.2)

A Tap Conductor is defined as a conductor, other than a service conductor, that has overcurrent protection ahead of its point of supply exceeding the value permitted for similar conductors that are protected as described in NEC 240.4. +-----------------------------------------------------------------------------+

  • | ANATOMY OF A FEEDER TAP INSTALLATION |
  • | |
  • | [ 400A Main Feeder Breaker ] |
  • | | |
  • | ============== 500 kcmil Copper Feeder (Ampacity = 380A) ============= |
  • | | |
  • | +--- [ TAP POINT (No OCPD here!) ] |
  • | | |
  • | | <-- Tap Conductor (Length <= 10 ft or 25 ft) |
  • | | (Enclosed in approved raceway / protected) |
  • | v |
  • | [ Subpanel Main OCPD (Terminating Breaker / Fuses) ] |
  • | (Limits current to the allowable ampacity of the tap conductor) |
  • +-----------------------------------------------------------------------------+

The Golden Rule of Tap Sizing: NO Round-Up Permitted!

The Next Higher Standard Rating Rule (NEC 240.4(B)) NEVER applies to tap conductors . The overcurrent protective device at the termination of a tap conductor must have a rating that is less than or equal to the allowable ampacity of the tap conductor.

2. The 10-Foot Feeder Tap Rule (NEC 240.21(B)(1))

Feeder conductors are permitted to be tapped, without overcurrent protection at the tap point, for runs not exceeding 10 feet (3.0 m) if ALL of the following conditions are met:

Length Limitation: The total length of the tap conductors does not exceed 10 feet (3.0 m) .

Ampacity Requirements: The ampacity of the tap conductors is:

Not less than the combined computed loads on the circuits supplied by the tap conductors, AND

Not less than the rating of the equipment containing an overcurrent protective device supplied by the tap conductors, OR not less than the rating of the overcurrent protective device at the termination of the tap conductors.

Physical Protection: The tap conductors are enclosed in an approved raceway, cable, or within the enclosure of an enclosed switchboard, switchgear, panelboard, or control devices.

No Extension: The tap conductors do not extend beyond the switchboard, switchgear, panelboard, disconnecting means, or control devices they supply. +-----------------------------------------------------------------------------+

  • | 10-FOOT FEEDER TAP RULE (NEC 240.21(B)(1)) |
  • | |
  • | MAXIMUM LENGTH: 10 Feet (3.0 meters) |
  • | MINIMUM AMPACITY: 1. >= Combined computed load |
  • | 2. >= Rating of terminating OCPD or panelboard bus |
  • | ENCLOSURE: Must be in raceway, cable, or equipment enclosure |
  • | TERMINATION: Must terminate directly in panel/switchboard/device |
  • | RATIO RULE: No 1/10th ratio required for FEEDER taps |
  • | (Contrast with Transformer Secondary Taps!) |
  • +-----------------------------------------------------------------------------+

Worked Example (10-Foot Tap):

A 600A main feeder in a wireway is tapped to supply a 100A subpanel located 6 feet away. The calculated load on the subpanel is 78 amperes, and the subpanel contains a 100A main circuit breaker.

Length = 6 ft ≤ 10 ft \le 10\text{ ft} ≤ 10 ft (Compliant).

Enclosed in rigid metallic conduit (Compliant).

Minimum conductor ampacity required = 100 Amperes (must equal terminating OCPD).

Minimum copper conductor: #3 AWG THHN Cu (rated 100A at 75°C).

Exam Trap: An apprentice selects #4 AWG Cu (rated 85A at 75°C) arguing that 85A exceeds the 78A computed load and rounds up to 100A under 240.4(B). This is a code violation: tap conductors cannot round up; ampacity must be ≥ 100 A \ge 100\text{A} ≥ 100 A .

3. The 25-Foot Feeder Tap Rule (NEC 240.21(B)(2))

Feeder conductors are permitted to be tapped for runs not exceeding 25 feet (7.5 m) if ALL of the following conditions are met:

Length Limitation: The total length of the tap conductors does not exceed 25 feet (7.5 m) .

The One-Third (1/3) Ampacity Rule: The ampacity of the tap conductors is not less than one-third (1/3) of the rating of the overcurrent protective device protecting the feeder conductors from which they are supplied: I tap ≥ I feeder_OCPD 3 I_{\text{tap}} \ge \frac{I_{\text{feeder\_OCPD}}}{3} I tap ​ ≥ 3 I feeder_OCPD ​ ​

Physical Protection: The tap conductors are protected from physical damage by being enclosed in an approved raceway, cable tray, or other approved cable method.

Single OCPD Termination: The tap conductors terminate in a single circuit breaker or a single set of fuses that limits the load to the allowable ampacity of the tap conductors. +-----------------------------------------------------------------------------+

  • | 25-FOOT FEEDER TAP RULE (NEC 240.21(B)(2)) |
  • | |
  • | MAXIMUM LENGTH: 25 Feet (7.5 meters) |
  • | MINIMUM AMPACITY: At least 1/3 of the upstream feeder OCPD rating |
  • | PHYSICAL PROTECTION: Enclosed in raceway, cable tray, or cable armor |
  • | TERMINATION: MUST terminate in a SINGLE circuit breaker or fuse set|
  • | sized <= tap conductor allowable ampacity |
  • +-----------------------------------------------------------------------------+

Worked Example (25-Foot Tap Calculation):

A 400-Ampere feeder protected by a 400A circuit breaker supplies a tap running 22 feet in EMT to a subpanel. What is the minimum conductor size (75°C copper) and maximum terminating circuit breaker permitted?

Calculate Minimum Tap Ampacity: I tap_min = 400 A 3 = 133.33 Amperes I_{\text{tap\_min}} = \frac{400\text{ A}}{3} = \mathbf{133.33\text{ Amperes}} I tap_min ​ = 3 400 A ​ = 133.33 Amperes

Select Conductor from NEC Table 310.16 (75°C Copper):

  • #1 AWG Cu = 130 Amperes (Insufficient: 130 A < 133.33 A 130\text{ A} < 133.33\text{ A} 130 A < 133.33 A )
  • 1/0 AWG Cu = 150 Amperes (Compliant: 150 A ≥ 133.33 A 150\text{ A} \ge 133.33\text{ A} 150 A ≥ 133.33 A )

Determine Maximum Terminating OCPD:

The terminating breaker cannot exceed the conductor ampacity ( 150 A 150\text{ A} 150 A ).

Permitted standard breaker: 150 Amperes .

4. Outside Feeder Taps of Unlimited Length (NEC 240.21(B)(5))

Where feeder tap conductors are installed completely outdoors, length restrictions are lifted because the open-air environment significantly mitigates fire hazards to building structures: +-----------------------------------------------------------------------------+

  • | OUTSIDE FEEDER TAPS OF UNLIMITED LENGTH (240.21(B)(5)) |
  • | |
  • | LOCATION: Entirely outside buildings (except at entrance point)|
  • | LENGTH: UNLIMITED distance outdoors |
  • | PHYSICAL PROTECTION: Enclosed in approved raceway or cable |
  • | TERMINATION: Single circuit breaker or single set of fuses |
  • | DISCONNECT POINT: Located at a readily accessible location either |
  • | outside the building or inside nearest point of entry|
  • | OCPD SIZING: Limits load to the allowable ampacity of tap wire |
  • +-----------------------------------------------------------------------------+
  • 5. Transformer Secondary Taps (NEC 240.21(C))

Except for specific 2-wire single-phase and 3-wire Delta-Delta transformers meeting NEC 240.4(F), primary overcurrent protective devices DO NOT protect transformer secondary conductors . Transformer secondary conductors must be protected under the tap rules of NEC 240.21(C):

10-Foot Secondary Tap Rule (NEC 240.21(C)(2))

Secondary conductors not over 10 feet must satisfy:

Length ≤ 10 feet \le 10\text{ feet} ≤ 10 feet .

Ampacity ≥ \ge ≥ computed load and ≥ \ge ≥ rating of device supplied or termination OCPD.

Ampacity not less than one-tenth (1/10) of the primary OCPD rating multiplied by the primary-to-secondary voltage ratio: I sec_ampacity ≥ ( I pri_OCPD 10 ) × ( V primary V secondary ) I_{\text{sec\_ampacity}} \ge \left( \frac{I_{\text{pri\_OCPD}}}{10} \right) \times \left( \frac{V_{\text{primary}}}{V_{\text{secondary}}} \right) I sec_ampacity ​ ≥ ( 10 I pri_OCPD ​ ​ ) × ( V secondary ​ V primary ​ ​ )

Enclosed in an approved raceway.

25-Foot Secondary Tap Rule (NEC 240.21(C)(6))

Secondary conductors not over 25 feet must satisfy:

Length ≤ 25 feet \le 25\text{ feet} ≤ 25 feet .

Ampacity not less than one-third (1/3) of the primary OCPD rating multiplied by the primary-to-secondary voltage ratio: I sec_ampacity ≥ ( I pri_OCPD 3 ) × ( V primary V secondary ) I_{\text{sec\_ampacity}} \ge \left( \frac{I_{\text{pri\_OCPD}}}{3} \right) \times \left( \frac{V_{\text{primary}}}{V_{\text{secondary}}} \right) I sec_ampacity ​ ≥ ( 3 I pri_OCPD ​ ​ ) × ( V secondary ​ V primary ​ ​ )

Terminates in a single circuit breaker or set of fuses rated ≤ \le ≤ secondary conductor ampacity.

Protected from physical damage. +-----------------------------------------------------------------------------+

  • | SUMMARY OF TAP RULES COMPARISON TABLE |
  • | |
  • | TAP TYPE MAX LENGTH MINIMUM AMPACITY RATIO TERMINATION |
  • | ----------------------------------------------------------------------- |
  • | 10-Ft Feeder (B)(1) 10 Feet >= Terminating OCPD Panel / Switch |
  • | 25-Ft Feeder (B)(2) 25 Feet >= 1/3 Feeder OCPD Single OCPD |
  • | Outside Feeder (B)(5) Unlimited Sized to disconnect Single OCPD |
  • | 10-Ft Sec. (C)(2) 10 Feet >= 1/10 Pri OCPD x Ratio Device / OCPD |
  • | 25-Ft Sec. (C)(6) 25 Feet >= 1/3 Pri OCPD x Ratio Single OCPD |
  • +-----------------------------------------------------------------------------+

Loading diagram... NEC 240.21 Feeder & Transformer Tap Rule Selection Tree