10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)

Oklahoma Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety

1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection

2 Chapter 2: General Electrical Theory & Calculations

2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments

3 Chapter 3: General Installation Requirements (NEC Article 110)

3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable

4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)

4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)

5 Chapter 5: Services & Service Equipment (NEC Article 230)

5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)

6 Chapter 6: Electrical Load Calculations (NEC Article 220)

6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)

7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)

7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)

8 Chapter 8: Grounding and Bonding (NEC Article 250)

8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)

9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)

9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)

10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems

10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)

11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)

11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)

12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)

12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)

13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)

13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)

14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems

14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)

10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)

Key Takeaways Explain This Topic AI

NEC Chapter 9 Table 1 mandates conductor fill limits: 1 conductor = 53% max area, 2 conductors = 31% max area (due to twisting/jamming risk), and 3 or more conductors = 40% max area.

Under Chapter 9 Note 4 (the Nipple Rule), conduit nipples with a length not exceeding 24 inches (600 mm) between enclosures may be filled up to 60% of their cross-sectional area, and Table 310.15(C)(1) conductor bundling derating does not apply.

To calculate conduit fill for conductors of different sizes, sum the individual cross-sectional areas from Chapter 9 Table 5 (or Table 5A for compact aluminum) and match against the allowable area in Table 4 for the specific raceway type.

NEC 314.28(A)(1) Straight Pull Rule: The length of a pull box containing conductors #4 AWG or larger must not be less than 8 times the trade size of the largest conduit entering the enclosure.

NEC 314.28(A)(2) Angle/U-Pull Rule: The distance to the opposite wall must be at least 6 times the largest conduit diameter plus the sum of the diameters of all other raceway entries on the same wall; conduit entries of the same circuit must be separated by at least 6 times the conduit trade size.

Last updated: August 2026

Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)

Conduit fill calculations and pull box dimensioning are among the most heavily tested mathematical competencies on the Oklahoma Journeyman Electrician examination. Installing too many conductors in a raceway traps heat, degrades conductor insulation, causes severe physical jamming during pulling, and violates the National Electrical Code. Similarly, undersized pull and junction boxes subject heavy conductors (#4 AWG and larger) to sharp bend radiuses that crack thermoplastic and cross-linked polyethylene jackets. Mastering Chapter 9 Tables and NEC 314.28 ensures safe, code-compliant field installations.

1. Conductor Fill Percentages (NEC Chapter 9 Table 1)

NEC Chapter 9 Table 1 establishes the maximum percentage of raceway cross-sectional area that may be occupied by conductors based on the total number of conductors installed. +-----------------------------------------------------------------------------+

  • | NEC CHAPTER 9 TABLE 1 PERCENTAGE FILL |
  • | |
  • | Number of Conductors Maximum Permitted Cross-Sectional Fill|
  • | --------------------------------- ------------------------------------- |
  • | 1 Conductor 53% |
  • | 2 Conductors 31% (Prevents binding & jamming) |
  • | 3 or more Conductors 40% (Standard multi-conductor limit) |
  • | Conduit Nipples (≤ 24 inches) 60% (Chapter 9 Note 4) |
  • +-----------------------------------------------------------------------------+

Why is 2-Conductor Fill Limited to 31%?

When two conductors are pulled into a round raceway, they naturally align side-by-side. As they round conduit bends, they twist and wedge against the inner curvature of the pipe wall, creating an oval binding profile. The 31% fill limit ensures sufficient clearance so that the two conductors do not jam against each other and the raceway interior.

The 24-Inch Conduit Nipple Rule (Chapter 9 Note 4)

Where conduit or tubing nipples with a maximum length not exceeding 24 inches (600 mm) are installed between boxes, cabinets, meter centers, or panelboards:

The raceway may be filled to 60% of its total internal cross-sectional area .

Conductor Bundling Derating Does NOT Apply: The adjustment factors of NEC Table 310.15(C)(1) (e.g., 80% for 4–6 conductors, 70% for 7–9 conductors) are completely waived for conduit nipples ≤ 24 \le 24 ≤ 24 inches.

Equipment Grounding & Bare Conductors (Chapter 9 Note 3)

Equipment grounding conductors (bare or insulated) and bonding conductors must always be included in conduit fill calculations. For bare conductors, cross-sectional dimensions must be obtained from NEC Chapter 9 Table 8 (Conductor Properties) .

2. Multi-Wire & Different Size Conduit Fill Calculations

When a conduit contains conductors of different wire gauges (e.g., three 3/0 AWG phase conductors, one 1/0 AWG neutral, and one #4 AWG bare copper equipment grounding conductor), the maximum number cannot be found in Annex C. You must calculate total conductor cross-sectional area using Chapter 9 Table 5 and compare it against Chapter 9 Table 4 . +-----------------------------------------------------------------------------+

  • | 4-STEP CONDUIT FILL CALCULATION PROCEDURE |
  • | |
  • | Step 1: Look up individual conductor cross-sectional areas in Table 5 |
  • | (Dimensions of Insulated Conductors and Fixture Wires) |
  • | Step 2: Multiply each area by quantity of wires and sum the total area |
  • | Step 3: Determine the required fill column from Table 1 (40% or 60%) |
  • | Step 4: Look up the raceway type in Table 4 and select the minimum trade |
  • | size whose permitted area is GREATER than or EQUAL to total area |
  • +-----------------------------------------------------------------------------+
  • Reference Data Extract: Conductor Areas (NEC Chapter 9 Table 5 - THHN/THWN-2)
  • Conductor Size (AWG/kcmil) Approximate Diameter (in.) Cross-Sectional Area ( i n . 2 in.^2 in . 2 )
  • #14 AWG THHN 0.111 0.0097
  • #12 AWG THHN 0.130 0.0133
  • #10 AWG THHN 0.164 0.0211
  • #8 AWG THHN 0.216 0.0366
  • #6 AWG THHN 0.254 0.0507
  • #4 AWG THHN 0.324 0.0824
  • #2 AWG THHN 0.384 0.1158
  • #1 AWG THHN 0.446 0.1562
  • 1/0 AWG THHN 0.486 0.1855
  • 2/0 AWG THHN 0.532 0.2223
  • 3/0 AWG THHN 0.584 0.2679
  • 4/0 AWG THHN 0.642 0.3237
  • 250 kcmil THHN 0.711 0.3970
  • 350 kcmil THHN 0.816 0.5229
  • 500 kcmil THHN 0.949 0.7073
  • Reference Data Extract: Raceway Allowable Areas (NEC Chapter 9 Table 4 - EMT)

Trade Size Total Area ( i n . 2 in.^2 in . 2 ) 1 Wire: 53% ( i n . 2 in.^2 in . 2 ) 2 Wires: 31% ( i n . 2 in.^2 in . 2 ) 3+ Wires: 40% ( i n . 2 in.^2 in . 2 ) Nipple: 60% ( i n . 2 in.^2 in . 2 )

  • 1/2 in. 0.304 0.161 0.094 0.122 0.182
  • 3/4 in. 0.533 0.283 0.165 0.213 0.320
  • 1 in. 0.864 0.458 0.268 0.346 0.518
  • 1-1/4 in. 1.496 0.793 0.464 0.598 0.898
  • 1-1/2 in. 2.036 1.079 0.631 0.814 1.221
  • 2 in. 3.356 1.778 1.040 1.342 2.013
  • 2-1/2 in. 5.858 3.105 1.816 2.343 3.515
  • 3 in. 8.846 4.688 2.742 3.538 5.307
  • 3-1/2 in. 11.545 6.119 3.579 4.618 6.927
  • 4 in. 14.754 7.820 4.574 5.902 8.852
  • Worked Example: Commercial Feeder Sizing

Question: What minimum trade size Electrical Metallic Tubing (EMT) is required to contain three 4/0 AWG THHN copper phase conductors, one 2/0 AWG THHN copper neutral, and one #4 AWG bare copper equipment grounding conductor?

Find Individual Areas from Table 5 & Table 8:

Three 4/0 AWG THHN: 3 × 0.3237 in. 2 = 0.9711 in. 2 3 \times 0.3237\text{ in.}^2 = 0.9711\text{ in.}^2 3 × 0.3237 in. 2 = 0.9711 in. 2

One 2/0 AWG THHN: 1 × 0.2223 in. 2 = 0.2223 in. 2 1 \times 0.2223\text{ in.}^2 = 0.2223\text{ in.}^2 1 × 0.2223 in. 2 = 0.2223 in. 2

One #4 AWG Bare Copper (Table 8): 1 × 0.0484 in. 2 = 0.0484 in. 2 1 \times 0.0484\text{ in.}^2 = 0.0484\text{ in.}^2 1 × 0.0484 in. 2 = 0.0484 in. 2

Sum Total Conductor Area: Total Area = 0.9711 + 0.2223 + 0.0484 = 1.2418 in. 2 \text{Total Area} = 0.9711 + 0.2223 + 0.0484 = 1.2418\text{ in.}^2 Total Area = 0.9711 + 0.2223 + 0.0484 = 1.2418 in. 2

Determine Allowable Percentage Fill: Total number of conductors is 3 + 1 + 1 = 5 3 + 1 + 1 = 5 3 + 1 + 1 = 5 conductors → \rightarrow → 40% Fill Column .

Select Conduit from Table 4 (EMT, 40% Column):

1-1/2 in. EMT allowable 40% area = 0.814 in. 2 0.814\text{ in.}^2 0.814 in. 2 ( 0.814 < 1.2418 0.814 < 1.2418 0.814 < 1.2418 — TOO SMALL)

2 in. EMT allowable 40% area = 1.342 in. 2 1.342\text{ in.}^2 1.342 in. 2 ( 1.342 ≥ 1.2418 1.342 \ge 1.2418 1.342 ≥ 1.2418 — COMPLIANT )

Answer: 2-inch EMT is the minimum compliant trade size.

3. Pull and Junction Box Sizing for Conductors #4 AWG and Larger (NEC 314.28)

When raceways contain conductors of size #4 AWG or larger , standard trade box dimensions (e.g., 4-inch square boxes) cannot be used. The pull box, junction box, or conduit body dimensions must be mathematically calculated per NEC 314.28(A) to provide sufficient bend radius and pulling space. +-----------------------------------------------------------------------------+

  • | PULL BOX SIZING RULES (NEC 314.28(A)) |
  • | |
  • | [1. Straight Pulls (314.28(A)(1))] |
  • | - Length of box ≥ 8 x (Trade Size of Largest Conduit) |
  • | |
  • | [2. Angle Pulls, U-Pulls & Splices (314.28(A)(2))] |
  • | - Distance to Opposite Wall ≥ [6 x (Largest Conduit)] + [Sum of all other |
  • | conduits entering the SAME wall] |
  • | |
  • | [3. Conduit Separation Distance (314.28(A)(2))] |
  • | - Distance between conduit entry and exit of the SAME circuit run |
  • | ≥ 6 x (Conduit Trade Size), measured center-to-center |
  • +-----------------------------------------------------------------------------+
  • Straight Pull Rule (NEC 314.28(A)(1))

In straight pulls (where conductors enter one side of the box and exit through the directly opposite wall in a straight line): Length of Box ≥ 8 × D largest \text{Length of Box} \ge 8 \times D_{\text{largest}} Length of Box ≥ 8 × D largest ​

Where D largest D_{\text{largest}} D largest ​ is the trade diameter of the largest raceway entering the enclosure.

Example: If the largest raceway is a 4-inch conduit, the box length must be at least 8 × 4 in. = 32 inches 8 \times 4\text{ in.} = 32\text{ inches} 8 × 4 in. = 32 inches . +-----------------------------------------------------------------------------+

  • | STRAIGHT PULL BOX LAYOUT |
  • | |
  • | <---------------- 8 x D (32") -----------------> |
  • | +----------------------------------------------+ |
  • | [ 4" Conduit]|==============================================|[ 4" Conduit]|
  • | [ 2" Conduit]|==============================================|[ 2" Conduit]|
  • | +----------------------------------------------+ |
  • +-----------------------------------------------------------------------------+
  • Angle Pulls, U-Pulls, and Splices (NEC 314.28(A)(2))

Where conductors make a 90-degree turn (Angle Pull), enter and exit the same wall (U-Pull), or are spliced inside the enclosure: Distance to Opposite Wall ≥ ( 6 × D largest ) + ∑ D other conduits on same wall \text{Distance to Opposite Wall} \ge (6 \times D_{\text{largest}}) + \sum D_{\text{other conduits on same wall}} Distance to Opposite Wall ≥ ( 6 × D largest ​ ) + ∑ D other conduits on same wall ​ +-----------------------------------------------------------------------------+

  • | ANGLE PULL BOX LAYOUT |
  • | |
  • | Width = (6 x 3") + 2" + 2" = 22" |
  • | +----------------------[ 3" ]---[ 2" ]---[ 2" ]+ |
  • | | | | | | |
  • | | | | | | |
  • | Height = | | | | | |
  • | (6 x 3") | | | | | |
  • | + 2" + 2" | | | | | |
  • | = 22" | | | | | |
  • | |[ 3" ]------------------+ | | | |
  • | |[ 2" ]---------------------------+ | | |
  • | |[ 2" ]------------------------------------+ | |
  • | +----------------------------------------------+ |
  • | |
  • | - Required Box Dimensions: 22 inches x 22 inches |
  • | - Conduit Separation between 3" entry and 3" exit: 6 x 3" = 18 inches min |
  • +-----------------------------------------------------------------------------+
  • Worked Example: Multi-Conduit Angle Pull Box Sizing

Question: A pull box has one 3-inch conduit and two 2-inch conduits entering the bottom wall and exiting through the right-hand wall. The box contains 4/0 AWG conductors. What are the minimum internal dimensions of the box, and what is the minimum required distance between the 3-inch raceway entries?

Calculate Distance from Bottom Wall to Top Wall (Height): Height = ( 6 × 3 in. ) + 2 in. + 2 in. = 18 + 2 + 2 = 22 inches \text{Height} = (6 \times 3\text{ in.}) + 2\text{ in.} + 2\text{ in.} = 18 + 2 + 2 = 22\text{ inches} Height = ( 6 × 3 in. ) + 2 in. + 2 in. = 18 + 2 + 2 = 22 inches

Calculate Distance from Right Wall to Left Wall (Width): Width = ( 6 × 3 in. ) + 2 in. + 2 in. = 18 + 2 + 2 = 22 inches \text{Width} = (6 \times 3\text{ in.}) + 2\text{ in.} + 2\text{ in.} = 18 + 2 + 2 = 22\text{ inches} Width = ( 6 × 3 in. ) + 2 in. + 2 in. = 18 + 2 + 2 = 22 inches

Calculate Minimum Separation Distance Between Raceway Entries (314.28(A)(2)): Separation = 6 × 3 in. = 18 inches (center-to-center) \text{Separation} = 6 \times 3\text{ in.} = 18\text{ inches (center-to-center)} Separation = 6 × 3 in. = 18 inches (center-to-center)

Result: The pull box must be at least 22 inches wide by 22 inches high with at least 18 inches of separation between the corresponding 3-inch entries.

Combination Straight and Angle Pulls

Where a single junction box contains both a straight pull and an angle pull, calculate the dimensions required for each pull independently along each axis; the box must satisfy the largest dimension calculated for each wall.

Loading diagram... Conduit Fill & Pull Box Sizing Calculation Workflow (NEC Ch. 9 & NEC 314.28)