14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760)

Oklahoma Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety

1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection

2 Chapter 2: General Electrical Theory & Calculations

2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments

3 Chapter 3: General Installation Requirements (NEC Article 110)

3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable

4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)

4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)

5 Chapter 5: Services & Service Equipment (NEC Article 230)

5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)

6 Chapter 6: Electrical Load Calculations (NEC Article 220)

6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)

7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)

7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)

8 Chapter 8: Grounding and Bonding (NEC Article 250)

8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)

9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)

9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)

10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems

10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)

11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)

11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)

12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)

12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)

13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)

13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)

14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems

14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)

14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760)

Key Takeaways Explain This Topic AI

The 2023 NEC split the former Article 725: Class 1 power-limited circuits moved to Article 724, Article 725 now covers Class 2 and Class 3 power-limited circuits only, Article 722 consolidates power-limited cable listing, and Article 726 covers new Class 4 power systems.

Class 2 and Class 3 conductors must be separated by at least 2 inches from conductors of electric light, power, and Class 1 circuits unless one of the specific permitted separation methods in 725.136 is used.

A power-limited fire alarm control panel must be supplied by an individual dedicated branch circuit that is identified in red, marked "FIRE ALARM CIRCUIT," and provided with a breaker locking means.

Cable substitution runs one direction only: a plenum-rated cable may replace a riser or general-purpose cable of the same or lower class, but a general-purpose or limited-use cable may never replace a plenum or riser cable.

Conductive optical fiber cable metallic members are bonded at the point of entrance with a conductor not smaller than 14 AWG copper, never required to be larger than 6 AWG, landed on the intersystem bonding termination required by 250.94.

Last updated: August 2026

Class 1, 2 & 3 Circuits, Fire Alarms & Optical Fiber Systems (NEC Articles 725, 760, 770 & 800)

Low-voltage, remote-control, signaling, and communications circuits operate across a vast spectrum of voltages and power levels—from high-energy motor starter control loops to ultra-low-power fiber optic data links. Because these systems present vastly different shock and fire hazards compared to standard 120V/240V/480V power circuits, the National Electrical Code provides specialized rules in Article 725 (Class 1, 2, 3 Circuits) , Article 760 (Fire Alarms) , Article 770 (Optical Fiber Cables) , and Article 800 (Communications) .

1. Class 1, Class 2, and Class 3 Circuits — Renumbered for 2023

Warning

Article 725 no longer holds Class 1 circuits. The 2023 NEC split this material across four articles, and a candidate who opens Article 725 looking for a Class 1 rule will not find it:

Article 2023 scope

722 Listing requirements for power-limited cables, consolidated in one place (including the new Class 4 cables)

724 Class 1 power-limited circuits and Class 1 power-limited remote-control and signaling circuits — moved out of 725

  • 725 Class 2 and Class 3 power-limited circuits only; the article title was revised to say so
  • 726 Class 4 power systems (fault-managed power) — new for 2023

Class 1 circuits were separated because they are not power-limited in the sense the IT industry uses the term, and keeping them in 725 created redundancy. The technical requirements below are unchanged; the article number in front of them is what moved.

Articles 724 and 725 establish alternative wiring methods based on the power limitations of the electrical source. By restricting available electrical energy, the risk of electrical fire and fatal shock is engineered out of the circuit. +-----------------------------------------------------------------------------+

  • | NEC ARTICLE 725 CIRCUIT CLASSIFICATION MATRIX |
  • | |
  • | CIRCUIT TYPE VOLTAGE & POWER LIMITS MANDATORY WIRING METHODS |
  • | ----------------------------------------------------------------------- |
  • | - Class 1 Power- - Max 30 Volts - Chapter 3 Wiring Methods |
  • | Limited - Max 1000 Volt-Amperes (VA) (EMT, RMC, MC, standard wire)|
  • | (725.41(A)) - Min #18 AWG copper wire |
  • | - Class 1 Remote- - Operates up to 600 Volts - Chapter 3 Wiring Methods |
  • | Control / Sign. (Motor controls, safety) - Overcurrent per 725.43 |
  • | - Class 2 - Max 30V / 100 VA - Class 2 Listed Cables |
  • | (Power-Limited) - Inherently safe against (CL2P, CL2R, CL2, CL2X) |
  • | FIRE and SHOCK - Separation from power wire |
  • | - Class 3 - Max 100V / 100 VA - Class 3 Listed Cables |
  • | (Power-Limited) - Safe against FIRE; (CL3P, CL3R, CL3, CL3X) |
  • | Higher shock risk - Higher insulation than CL2 |
  • +-----------------------------------------------------------------------------+

Key Engineering Differences:

Class 1 Circuits (NEC Part II):

Class 1 circuits represent significant energy levels capable of starting fires or delivering severe shocks. Therefore, they MUST use Chapter 3 wiring methods (metal conduit, MC cable, standard building wire). Conductor sizing: minimum #18 AWG (7A overcurrent protection) or #16 AWG (10A overcurrent protection) per NEC 725.49.

Class 2 Circuits (NEC Part III):

Sourced from listed Class 2 power supplies, transformers, or LED drivers. Because both voltage (≤30V) and power (≤100 VA) are inherently limited, a human touching exposed conductors will not experience dangerous ventricular fibrillation, and an accidental short circuit will not generate enough heat to ignite building insulation.

Class 3 Circuits (NEC Part III):

Sourced from power supplies operating from 30V up to 100V (max 100 VA). While power is limited to prevent fire, the higher voltage introduces an electric shock hazard; therefore, Class 3 cables require thicker, higher-dielectric insulation ratings (300V rated).

2. Separation of Class 2/3 from Power Conductors (NEC 725.136)

Because Class 2 and Class 3 cables feature lighter insulation ratings (often not rated for 600V), physical contact between a 120V/277V/480V conductor and a Class 2 conductor would dangerously energize low-voltage equipment and create immediate electrocution and fire hazards. +-----------------------------------------------------------------------------+

  • | CLASS 2/3 SEPARATION MANDATE (NEC 725.136) |
  • | |
  • | [LIGHT / POWER / CLASS 1 CABLE] [CLASS 2 / CLASS 3 CABLE] |
  • | (120V / 277V / 480V) (Thermostat / Sound / Control)|
  • | | | |
  • | |<----------- MINIMUM 2 INCHES ------------>| |
  • | | (50 mm Separation) | |
  • | |
  • | INSIDE JUNCTION BOXES / ENCLOSURES (NEC 725.136(B)-(D)): |
  • | - Permitted only where separated by a continuous, listed PHYSICAL BARRIER |
  • | (such as a steel or nonmetallic partition plate). |
  • | - Exception: Power leads entering SOLELY to supply the Class 2 transformer|
  • | maintaining minimum 0.25 in. (6 mm) clearance. |
  • +-----------------------------------------------------------------------------+

Open Runs / Cable Trays: A minimum physical separation of not less than 2 inches (50 mm) must be maintained at all times between Class 2 or Class 3 conductors and electric light, power, or Class 1 conductors, unless either circuit is installed in a Chapter 3 raceway, metal-sheathed cable, or armored cable.

Enclosures and Boxes: Class 2/3 conductors cannot occupy the same enclosure or junction box with light/power wiring unless separated by a permanent, listed metal or nonmetallic barrier .

3. Cable Markings, Environmental Ratings & Hierarchy (NEC 725.154 & 725.179) +-----------------------------------------------------------------------------+

  • | CLASS 2 & 3 CABLE HIERARCHY & SUBSTITUTIONS |
  • | |
  • | [CL3P / CL2P] (Plenum Rated - NEC 300.22(C) Air Plenums) |
  • | | |
  • | v |
  • | [CL3R / CL2R] (Riser Rated - Floor-to-Floor Vertical Shafts) |
  • | | |
  • | v |
  • | [CL3 / CL2] (General Purpose - Commercial & Residential Walls) |
  • | | |
  • | v |
  • | [CL3X / CL2X] (Limited Use - Residential / In Conduit Only) |
  • | |
  • | CRITICAL SUBSTITUTION RULES (NEC Table 725.154): |
  • | - Class 3 cables CAN substitute for Class 2 cables. |
  • | - Class 2 cables CANNOT substitute for Class 3 cables! |
  • | - Communications cables (CMP, CMR, CM) can substitute for Class 2 & 3. |
  • | - Plenum (P) can replace Riser (R), General, and Limited Use (X). |
  • +-----------------------------------------------------------------------------+
  • 4. Fire Alarm Systems (NEC Article 760)

Fire alarm systems provide audible and visual notification and interface with building safety controls (elevator recall, smoke dampers, door releases). +-----------------------------------------------------------------------------+

  • | FIRE ALARM SYSTEM CLASSIFICATIONS (NEC 760) |
  • | |
  • | SYSTEM TYPE VOLTAGE / POWER WIRING METHOD |
  • | ----------------------------------------------------------------------- |
  • | - Non-Power-Limited Fire Up to 600 Volts - Chapter 3 Methods |
  • | Alarm (NPLFA) (High-energy circuits) - Min #18 AWG Copper |
  • | (Part II / 760.41) - Overcurrent Protected |
  • | - Power-Limited Fire Supplied by listed - Listed Fire Alarm |
  • | Alarm (PLFA) power-limited supply Cables: FPLP, FPLR, |
  • | (Part III / 760.121) FPL (NEC 760.179) |
  • +-----------------------------------------------------------------------------+
  • Dedicated Branch Circuit & Red Marking Rules (NEC 760.41 & 760.121)

Dedicated Branch Circuit: The power source for both NPLFA and PLFA systems must be supplied by an individual, dedicated branch circuit .

No Other Loads: No other lighting, convenience outlets, or appliance loads are permitted on the fire alarm branch circuit.

Red Circuit Identification: The branch circuit overcurrent protective device (circuit breaker) and its enclosure/cover must be clearly marked in RED and permanently labeled "FIRE ALARM CIRCUIT" .

Permanent Breaker Lockout: The branch-circuit breaker handle must be equipped with a permanent, listed mechanical lockout device (breaker clip/lockout) preventing inadvertent manual switching or disconnection by unauthorized personnel.

Fire Alarm Cable Types & Separation (NEC 760.136 & 760.179)

FPLP (Plenum): Listed for use in ducts, plenums, and other air-handling spaces.

FPLR (Riser): Listed for use in vertical runs in a shaft or floor-to-floor penetrations.

FPL (General Purpose): Listed for general-purpose fire alarm use.

Separation (NEC 760.136): PLFA conductors must maintain a 2-inch (50 mm) separation from light, power, and Class 1 conductors in open runs, or be separated by a continuous barrier in enclosures.

5. Optical Fiber Cables (Article 770) & Communications (Article 800) +-----------------------------------------------------------------------------+

  • | OPTICAL FIBER & COMMUNICATIONS GROUNDING RULES |
  • | |
  • | CABLE TYPE METALLIC CONTENT GROUNDING REQUIREMENT |
  • | ----------------------------------------------------------------------- |
  • | - Nonconductive Optical NO METAL (Glass fiber, No grounding required. |
  • | Fiber (OFNP, OFNR) dielectric jacket) Can share raceways with |
  • | Class 2/3 & comms. |
  • | - Conductive Optical CONTAINS METAL (Armor, MUST be grounded at |
  • | Fiber (OFCP, OFCR) strength wire, shield) point of entrance with |
  • | min #6 Cu (770.93/100). |
  • | - Communications Metallic conductors Primary protector and |
  • | (CMP, CMR, CM) (Twisted-pair copper) grounding to IBT with |
  • | min #6 Cu (NEC 800.100).|
  • +-----------------------------------------------------------------------------+
  • Intersystem Bonding Termination (IBT) & Grounding Conductor (NEC 250.94 & 800.100)

Communications, CATV, network, and conductive optical fiber cables entering a building must connect their primary protectors and metal sheaths to the building's Intersystem Bonding Termination (IBT) .

Bonding Conductor Sizing (NEC 800.100(A)(3)): copper or other corrosion-resistant conductive material, insulated, covered, or bare, not smaller than 14 AWG , with a current-carrying capacity not less than the grounded metallic members of the cable — and it is not required to be larger than 6 AWG . The 6 AWG figure is a ceiling on what the Code can make you install , not a floor; a candidate who answers "minimum 6 AWG" has the rule inverted.

Routing (NEC 800.100(A)(4) and (A)(5)): run in as straight a line as practicable . In one- and two-family dwellings the conductor must be as short as practicable and not exceed 20 feet (6.0 m) ; where that length cannot be met in a one- or two-family dwelling, a separate grounding electrode is driven and bonded to the power grounding electrode system with a conductor not smaller than 6 AWG . Outside of one- and two-family dwellings there is no 20-foot cap.

Loading diagram... Class 1, 2, 3 and Fire Alarm Circuit Segregation & Cable Hierarchy (NEC 725, 760, 770)