Study guide

14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)

Oklahoma Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety

1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection

2 Chapter 2: General Electrical Theory & Calculations

2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments

3 Chapter 3: General Installation Requirements (NEC Article 110)

3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable

4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)

4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)

5 Chapter 5: Services & Service Equipment (NEC Article 230)

5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)

6 Chapter 6: Electrical Load Calculations (NEC Article 220)

6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)

7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)

7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)

8 Chapter 8: Grounding and Bonding (NEC Article 250)

8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)

9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)

9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)

10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems

10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)

11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)

11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)

12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)

12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)

13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)

13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)

14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems

14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)

14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)

Key Takeaways Explain This Topic AI

NEC 551.71 requires every RV site with electrical supply to have at least one 20-ampere, 125-volt receptacle, with a minimum of 20 percent of sites equipped with a 50-ampere, 125/250-volt receptacle and a minimum of 70 percent equipped with a 30-ampere, 125-volt receptacle.

RV park service and feeder loads are calculated at 9600 volt-amperes per 50-ampere site, 3600 volt-amperes per 30-ampere site, and 2400 volt-amperes per 20-ampere site, before the demand factors of Table 551.73(A) are applied.

NEC 553.4 requires the service equipment for a floating building to be located adjacent to, but not in or on, the building or any floating structure.

NEC 555.35 requires feeders on docking facilities to have listed ground-fault protection of equipment rated not more than 100 milliamperes, and shore power receptacles to be protected by GFPE set at not more than 30 milliamperes.

The electrical datum plane for floating piers is 30 inches above the water level and at least 12 inches above the deck, and in land areas subject to tidal fluctuation it is 2 feet above the highest high tide for the area.

Last updated: August 2026

14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)

Section 13.4 covered agricultural buildings (Article 547) and manufactured and mobile homes (Article 550). The Special Occupancies subject area also lists mobile home parks, RVs and RV parks and, separately, floating buildings . Those are Articles 551, 553, and — because a floating building is almost always at a docking facility — 555.

1. Article 551 Part VI — Recreational Vehicle Parks

Article 551 has two halves. Parts I through V cover the vehicle itself — its low-voltage system, its generator, its power-supply assembly, and its factory wiring. Part VI is the part a journeyman installs: the park .

The receptacle mix (551.71)

  • Requirement Value
  • Every RV site with electrical supply At least one 20-ampere, 125-volt receptacle
  • Minimum share of sites with a 50-ampere, 125/250-volt receptacle 20 percent
  • Minimum share of sites with a 30-ampere, 125-volt receptacle 70 percent
  • Remaining sites One or more of the receptacle configurations conforming to 551.81

GFCI 125-volt, 15- and 20-ampere receptacles at RV sites require GFCI protection ; the 30- and 50-ampere RV supply receptacles do not

The percentages overlap deliberately — a single premium site may carry a 50-ampere, a 30-ampere, and a 20-ampere receptacle. An informational note in the Code observes that the 20 percent figure for 50-ampere sites can be inadequate for seasonal parks serving a high proportion of large coaches, so designers routinely exceed it.

Calculated load (551.73)

Each site type is assigned a volt-ampere value before demand factors:

  • Site equipment Calculated load per site
  • 50-ampere, 125/250-volt 9,600 VA
  • 30-ampere, 125-volt 3,600 VA
  • 20-ampere, 125-volt 2,400 VA

The total is then reduced by the demand factors of Table 551.73(A) , which fall steeply as the site count rises because RVs do not all run air conditioning, water heaters, and converters at the same instant. Park distribution is normally a 120/240-volt, three-wire system (551.72).

Site supply equipment (551.77)

Site supply equipment is located on the left (road) side of the parked RV , positioned at or near the rear of the stand, so that a coach parked in the normal orientation has its inlet within reach of the pedestal.

The disconnecting means must be readily accessible and mounted within a defined height band above grade — not less than 2 feet and not more than about 6½ feet.

Where the pedestal serves more than one site, the working space and the identification of which receptacle serves which site must be maintained.

Overhead conductors crossing the park must maintain the clearances of 551.79 over the RV stands and the roadways.

2. Article 553 — Floating Buildings

A floating building is a building unit that floats on water, is moored in a permanent location, and has a premises wiring system served through connection by permanent wiring to an electricity supply on shore. That definition is what separates Article 553 from Article 555 (the docking facility) and from a boat (which is not covered by the NEC at all).

Rule Requirement

Service conductors and equipment (553.4) The service equipment must be located adjacent to, but not in or on , the floating building or any floating structure — the disconnect stays on land where a firefighter can reach it

Number of supplies Each floating building is served by a single set of feeder or service conductors, run from the shore service equipment out to the unit

Grounded conductor The grounded (neutral) conductor must be insulated and identified, and it may not be connected to the equipment grounding conductor or to metal parts on the load side of the service disconnecting means

Equipment grounding An insulated equipment grounding conductor must be run with the supply conductors from the shore service equipment to the floating building, and it — not the water, not the mooring hardware — is the fault-current return path

Bonding (553.11) Metal parts of the floating structure, metal piping, and non-current-carrying metal enclosures must be bonded to the equipment grounding conductor

Warning

Why the neutral-to-ground separation matters here more than anywhere else. On land, a neutral-ground bond downstream of the service creates parallel current paths through metal. On the water, those parallel paths are through the water itself , and the resulting voltage gradient produces electric shock drowning — a swimmer paralyzed by current well below what would trip an ordinary overcurrent device. Every rule in Articles 553 and 555 about insulated neutrals, insulated equipment grounding conductors, and low-threshold ground-fault protection exists for that one failure mode.

  • 3. Article 555 — Marinas, Boatyards, and Docking Facilities
  • The electrical datum plane

Article 555 begins with a reference plane rather than a rule: electrical equipment and connections must be above the electrical datum plane.

  • Situation Electrical datum plane
  • Floating piers 30 inches above the water level and not less than 12 inches above the deck
  • Land areas subject to tidal fluctuation 2 feet above the highest high tide for the area

Land areas not subject to tidal fluctuation Referenced to the highest water level for the area under normal circumstances

Ground-fault protection thresholds (555.35)

  • Circuit Required protection
  • Feeders installed on docking facilities Listed GFPE rated not more than 100 mA
  • Shore power receptacles (the boat supply outlets) GFPE set at not more than 30 mA
  • 15- and 20-ampere, 125-volt receptacles other than shore power GFCI protection for personnel (Class A, 4–6 mA)

The tiered thresholds reflect what each device protects: a Class A GFCI protects a person touching a tool on the dock, the 30 mA shore-power GFPE limits the leakage a boat can put into the water, and the 100 mA feeder GFPE catches a failing dock feeder without shutting down the entire marina every time a single boat leaks.

Leakage current measurement. The 2023 NEC requires docking facilities with multiple shore power receptacles to have a means of measuring leakage current so an individual leaking boat can be identified rather than the whole dock being de-energized. The listing requirement for the leakage current measurement device becomes effective January 1, 2026.

Equipment grounding conductors (555.37)

Equipment grounding conductors serving docking facilities must be insulated, wire-type conductors sized in accordance with 250.122 but not smaller than 12 AWG . The insulated requirement is deliberate: a bare or raceway-only grounding path in a saltwater environment corrodes to a high-resistance connection that will not clear a fault but will happily energize the water.

Other rules that produce exam items

Wiring methods on piers include rigid metal conduit, IMC, Type PVC, Type RTRC, and liquidtight flexible conduits, with portable power cables permitted for the flexible connections that a floating pier requires.

Disconnecting means for shore power connections must be readily accessible, located not more than 30 inches from the receptacle it controls, and must open all ungrounded conductors.

Signage warning of the shock hazard of swimming near a docking facility is required where electrical equipment is installed.

Overhead conductors are prohibited over the areas where boats are moored, launched, or moved by mast or boom.