12.3 Appliances & Electric Water Heaters (NEC Article 422)
Oklahoma Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety
1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection
2 Chapter 2: General Electrical Theory & Calculations
2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments
3 Chapter 3: General Installation Requirements (NEC Article 110)
3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable
4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)
4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)
5 Chapter 5: Services & Service Equipment (NEC Article 230)
5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)
6 Chapter 6: Electrical Load Calculations (NEC Article 220)
6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)
7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)
7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)
8 Chapter 8: Grounding and Bonding (NEC Article 250)
8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)
9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)
9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)
10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems
10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)
11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)
11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)
12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)
12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)
13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)
13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)
14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems
14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)
12.3 Appliances & Electric Water Heaters (NEC Article 422)
Key Takeaways Explain This Topic AI
Under NEC 422.13, all electric storage-type water heaters having a capacity of 120 gallons (450 L) or less are classified as continuous loads, requiring branch circuit conductors and overcurrent protective devices (OCPD) to be sized at not less than 125% of the nameplate current rating.
A standard 240V, 4500W residential electric storage water heater draws 18.75A; applying the 125% continuous load multiplier yields 23.44A, which mandates a 30A circuit breaker and #10 AWG copper conductors.
Under NEC 422.30 and 422.31, each appliance must be provided with a disconnecting means; if not within sight of the appliance (visible and within 50 feet), the branch circuit breaker must be capable of being locked in the open position with a permanent locking provision remaining in place with or without the lock per NEC 110.25.
Flexible cord connections under NEC 422.16(B) are permitted for specific built-in appliances: kitchen waste disposers require cord lengths between 18 and 36 inches, while built-in dishwashers require cord lengths between 3.0 and 6.5 feet, with receptacles located in adjacent spaces.
Under NEC 210.23(A)(2) and 422.10(B), fastened-in-place appliances on a 15A or 20A multi-outlet branch circuit supplying lighting or portable loads cannot exceed 50% of the circuit rating (10A on a 20A circuit), while any portable cord-and-plug appliance cannot exceed 80% (16A on a 20A circuit).
Last updated: August 2026
Appliances & Electric Water Heaters (NEC Article 422)
NEC Article 422 governs the electrical installation, branch circuit sizing, overcurrent protection, and disconnecting means for electrical appliances used in residential, commercial, and industrial occupancies. Appliances range from small cord-and-plug kitchen devices to heavy fixed equipment like electric water heaters, commercial dishwashers, and trash compactors. Understanding the precise sizing calculations, continuous load mandates, and lockout disconnect rules is essential for the Oklahoma Journeyman Electrician examination.
1. Branch Circuit Sizing for Appliances (NEC 422.10)
Branch circuit conductors supplying appliances must have an allowable ampacity not less than the marked appliance rating or the calculated load under Article 220. +---------------------------------------------------------------------------------------------------+
- | APPLIANCE BRANCH CIRCUIT SIZING PROTOCOLS |
- | |
- | CIRCUIT TYPE CODE REFERENCE SIZING RULE & CONDUCTOR AMPACITY MANDATES |
- | --------------------- --------------- -------------------------------------------------------- |
- | Individual Branch NEC 422.10(A) Must not be less than the appliance marked nameplate |
- | Circuit rating. For continuous loads (>= 3 hours), branch circuit|
- | conductors & OCPD must be sized at >= 125% of load. |
- | |
- | Multi-Outlet Branch NEC 422.10(B) & - Fastened-in-place appliances: <= 50% of circuit rating |
- | Circuit NEC 210.23(A) when circuit also supplies lighting or portable loads. |
- | - Portable cord-and-plug loads: <= 80% of circuit rating.|
- +---------------------------------------------------------------------------------------------------+
- 2. Electric Storage-Type Water Heaters (NEC 422.13)
One of the most frequently tested sizing questions on the Journeyman exam involves electric water heaters. Storage water heaters continuously maintain water temperature around the clock, creating prolonged thermal stress on branch circuits.
NEC 422.13 Rule: "All fixed electric storage-type water heaters having a capacity of 120 gallons (450 L) or less shall be considered a continuous load for the purpose of sizing branch circuits." +-----------------------------------------------------------------------------+
- | WATER HEATER CALCULATION WORKFLOW (NEC 422.13) |
- | |
- | STEP 1: Calculate Full-Load Nameplate Current |
- | I_nameplate = Power (Watts) / Voltage (Volts) |
- | |
- | STEP 2: Apply 125% Continuous Load Multiplier (NEC 422.13 / 210.19(A)(1)) |
- | Minimum Conductor & OCPD Ampacity = I_nameplate × 1.25 |
- | |
- | STEP 3: Select Standard Overcurrent Device (NEC 240.6) |
- | Choose standard breaker/fuse >= calculated minimum ampacity. |
- | |
- | STEP 4: Size Copper Conductors (NEC Table 310.16 & 240.4(D)) |
- | Select conductor with ampacity matching circuit rating. |
- +-----------------------------------------------------------------------------+
- Comprehensive Calculation: Standard 4,500W Residential Water Heater
A single-family residence has a 50-gallon , 4,500-Watt , 240-Volt electric storage water heater:
Full-Load Current: I = 4500 Watts 240 Volts = 18.75 Amperes I = \frac{4500\text{ Watts}}{240\text{ Volts}} = \mathbf{18.75\text{ Amperes}} I = 240 Volts 4500 Watts = 18.75 Amperes
Minimum Circuit Ampacity (125% continuous rule): Minimum Ampacity = 18.75 A × 1.25 = 23.44 Amperes \text{Minimum Ampacity} = 18.75\text{ A} \times 1.25 = \mathbf{23.44\text{ Amperes}} Minimum Ampacity = 18.75 A × 1.25 = 23.44 Amperes
Overcurrent Protective Device Selection:
Under NEC 240.6(A), the next standard protective device size above 23.44A is 30 Amperes (a 25A breaker could protect 23.44A, but water heater circuits traditionally standardize on 30A).
Conductor Sizing:
Under NEC Table 310.16 and Small Conductor Rules (NEC 240.4(D)), #10 AWG copper (rated 30A at 75°C/60°C) is required.
Water Heater Sizing Comparison Table:
- Water Heater Rating Voltage Full-Load Current Min. Ampacity (125%) Min. OCPD Rating Min. Conductor Size (Cu)
- 3,000 Watts 240V 12.50 A 15.63 A 20 Amperes #12 AWG Cu
- 3,800 Watts 240V 15.83 A 19.79 A 20 Amperes #12 AWG Cu
- 4,500 Watts 240V 18.75 A 23.44 A 30 Amperes #10 AWG Cu
- 5,500 Watts 240V 22.92 A 28.65 A 30 Amperes #10 AWG Cu
- 12,000 Watts (3Ø) 208V 33.31 A 41.64 A 50 Amperes #8 AWG Cu
- 3. Disconnecting Means for Appliances (NEC 422.30–422.35)
A disconnecting means is mandatory for each appliance to ensure service technicians can safely de-energize equipment without risking accidental re-energization. +---------------------------------------------------------------------------------------------------+
- | APPLIANCE DISCONNECT RULES (NEC 422.31) |
- | |
- | APPLIANCE RATING DISCONNECT LOCATION PERMITTED DISCONNECTING MEANS |
- | --------------------- -------------------------------- --------------------------------------- |
- | <= 300 VA or <= 1/8 hp Branch circuit switch or breaker Branch circuit breaker or switch. |
- | (422.31(A)) Need not be within sight or lockable. |
- | |
- | > 300 VA or > 1/8 hp Within Sight OR Lockable Circuit 1. Disconnect switch within sight |
- | (Without Motor) Breaker (NEC 422.31(B)) (within 50 ft & visible), OR |
- | 2. Branch breaker with permanent lockout|
- | provision complying with NEC 110.25. |
- | |
- | Motor-Driven Within Sight of Motor Controller 1. Disconnect within sight of motor |
- | > 1/8 hp (NEC 422.31(C)) controller, OR |
- | 2. Lockable breaker complying with 110.25|
- +---------------------------------------------------------------------------------------------------+
Lockout/Tagout Compliance Under NEC 110.25:
When a branch circuit breaker serves as the disconnecting means for an appliance located out of sight (e.g., an electric water heater in a basement while the electrical panel is in the garage), the locking provision must be installed on or at the switch or circuit breaker and must remain in place with or without the lock installed .
Portable clip-on or snap-on lockout hasps carried in a tool bag do not satisfy NEC 110.25!
Other Permitted Disconnecting Means:
Unit Switches (NEC 422.34): A unit switch with a marked "OFF" position that disconnects all ungrounded conductors is permitted as the disconnect if other disconnecting means (e.g., service switch, panel breaker) exist in the building.
Cord-and-Plug Connections (NEC 422.33): For cord-and-plug connected appliances, an accessible separable connector or attachment plug and receptacle is an approved disconnecting means.
4. Flexible Cord Connections for Built-in Appliances (NEC 422.16(B))
Important
Oklahoma adds a fifth item to this list. OAC 748:20-10-10 adopts NEC Chapter 4 with an added 422.16(B)(5) , permitting a gas-fired central furnace supplying a dwelling unit to be cord-and-plug connected so the homeowner can move it onto a portable generator. The cord must contain an equipment grounding conductor and terminate in a grounding-type attachment plug, must have sufficient ampacity for the load, must be routed or protected against physical damage, and must not exceed 9 feet . See Section 1.6.
Specific built-in household appliances are permitted to be cord-and-plug connected rather than hardwired, provided strict dimensional and safety rules are satisfied: +---------------------------------------------------------------------------------------------------+
- | CORD-AND-PLUG APPLIANCE SPECIFICATIONS (NEC 422.16(B)) |
- | |
- | APPLIANCE CORD LENGTH RECEPTACLE LOCATION & SPECIAL MANDATES |
- | -------------------- ------------------------- ----------------------------------------------- |
- | Kitchen Waste 18 in. to 36 in. - Receptacle located in under-sink space. |
- | Disposer (450 mm to 900 mm) - Grounding-type attachment plug required. |
- | (422.16(B)(1)) - Cord protected from physical damage. |
- | |
- | Built-in 3.0 ft to 6.5 ft - Receptacle in space adjacent to dishwasher |
- | Dishwasher (0.9 m to 2.0 m) (e.g., under adjacent sink cabinet). |
- | (422.16(B)(2)) - Opening in partition must have smooth edges. |
- | - Receptacle must be accessible. |
- | |
- | Trash 3.0 ft to 4.0 ft - Receptacle in space adjacent to compactor. |
- | Compactor (0.9 m to 1.2 m) - Grounding-type attachment plug required. |
- | (422.16(B)(2)) |
- | |
- | Wall-Mounted Ovens / Manufacturer-specified - Cord must terminate in grounding attachment |
- | Counter Cooktops flexible cord assembly plug; receptacle accessible. |
- +---------------------------------------------------------------------------------------------------+
- 5. Appliance Overcurrent Protection (NEC 422.11)
Appliances must be protected against overcurrent in accordance with their nameplate ratings:
Marked Rating: If a protective device rating is marked on the appliance nameplate (e.g., "Max Fuse or HACR Breaker: 25A"), the branch circuit OCPD rating shall not exceed the marked value .
Non-Motor Appliances (NEC 422.11(E)): If not marked and the appliance is rated at 13.3 A 13.3\text{A} 13.3 A or less, the OCPD shall not exceed 20 A 20\text{A} 20 A . If rated over 13.3 A 13.3\text{A} 13.3 A , the OCPD shall not exceed 150% of the appliance rating , rounded up to the next standard rating if 150% does not correspond to a standard size.