Study guide
12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)
Oklahoma Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Oklahoma Licensing Laws, Board Rules & Safety
1.1 Oklahoma Electrical License Act & CIB Regulations 1.2 OK Journeyman Exam Format, PSI Logistics & Codebook Navigation 1.3 OSHA Electrical Safety Standards (29 CFR 1926/1910) 1.4 NFPA 70E Electrical Safety in the Workplace & Arc Flash 1.5 Permits, Inspections, Structural Integrity & Job Estimating 1.6 Oklahoma's Adopted 2023 NEC: OUBCC Amendments You Must Know 1.7 OSHA 29 CFR 1926 Job-Site Safety: Sanitation, Signage, Ladders, Scaffolds & Fall Protection
2 Chapter 2: General Electrical Theory & Calculations
2.1 Ohm's Law, Watt's Law & DC Series/Parallel Circuits 2.2 AC Theory, Reactance, Impedance & Power Factor 2.3 Three-Phase Power Systems (Delta & Wye Configurations) 2.4 Electrical Units, Formulas & Conversions 2.5 Cost of Power in a Circuit, Efficiency & Troubleshooting/Test Instruments
3 Chapter 3: General Installation Requirements (NEC Article 110)
3.1 Examination, Identification, Installation & Use of Equipment (110.3) 3.2 Electrical Connections, Terminations & Torque Requirements (110.14) 3.3 Working Space, Clearances & Guarding of Live Parts (110.26 & 110.27) 3.4 Enclosure Types, Markings & Available Fault Current (110.24 & 110.28) 3.5 Installations Over 600 Volts: Article 110 Part III, Article 490 & Medium-Voltage Cable
4 Chapter 4: Branch Circuits & Feeders (NEC Articles 210, 215 & 225)
4.1 Branch Circuit Ratings, Multiwire Branch Circuits & Identification (210.3–210.10) 4.2 Ground-Fault Circuit-Interrupter (GFCI) Protection (210.8) 4.3 Arc-Fault Circuit-Interrupter (AFCI) Protection & Receptacle Outlets (210.12 & 210.52) 4.4 Outside Branch Circuits and Feeders (Article 225) & Feeder Sizing (Article 215)
5 Chapter 5: Services & Service Equipment (NEC Article 230)
5.1 Service Clearances, Overhead & Underground Service-Drop Requirements (230.9, 230.24 & 230.30) 5.2 Service-Entrance Conductors, Sizing & Installation (230.40–230.54) 5.3 Service Equipment Disconnecting Means, Overcurrent Protection & Emergency Disconnects (230.70–230.95)
6 Chapter 6: Electrical Load Calculations (NEC Article 220)
6.1 General Lighting, Small Appliance & Laundry Loads (NEC 220.41, 220.42, 220.45 & 220.52) 6.2 Standard Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part III) 6.3 Optional Dwelling Unit Feeder & Service Calculations (NEC Article 220 Part IV) 6.4 Commercial & Multi-Family Load Calculations (Cooktops, Dryers, HVAC & Stores)
7 Chapter 7: Overcurrent Protection & Tap Rules (NEC Article 240)
7.1 Overcurrent Protection Fundamentals & Standard Ampere Ratings (240.4 & 240.6) 7.2 Feeder & Branch Circuit Tap Rules (NEC 240.21) 7.3 Ground-Fault Protection of Equipment & Selective Coordination (NEC 240.13, 240.86 & Article 245)
8 Chapter 8: Grounding and Bonding (NEC Article 250)
8.1 General Grounding Principles, System Grounding & Grounded Conductors (NEC 250.4, 250.20 & 250.24) 8.2 Grounding Electrode System & Grounding Electrode Conductor (GEC) Sizing (NEC 250.50, 250.52 & 250.66) 8.3 Equipment Grounding Conductors (EGC) Sizing & Installation (NEC 250.118, 250.120 & 250.122) 8.4 Bonding Requirements, Main/System Bonding Jumpers & Separately Derived Systems (NEC 250.28, 250.30 & 250.102)
9 Chapter 9: Wiring Methods & Materials (NEC Articles 300–314)
9.1 General Requirements for Wiring Methods, Underground Clearances & Firestopping (NEC Article 300) 9.2 Conductor Ampacity Ratings, Temperature Correction & Bundling Adjustments (Article 310 & Table 310.16) 9.3 Nonmetallic-Sheathed Cable (Type NM), Metal-Clad Cable (Type MC) & Armored Cable (Type AC) 9.4 Outlet, Device, Pull & Junction Boxes Sizing and Box Fill Calculations (NEC Article 314) 9.5 Temporary Installations (Article 590), Cranes & Hoists (Article 610), Elevators & Escalators (Article 620)
10 Chapter 10: Raceways, Tubing, Conduit Fill & Underground Systems
10.1 Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC) & Electrical Metallic Tubing (EMT) 10.2 Nonmetallic Raceways (PVC, RTRC, Liquidtight) & Cable Trays (NEC Articles 352, 356, 392) 10.3 Conduit Fill Calculations (Chapter 9 Tables 1, 4 & 5, Annex C) & Pull Box Sizing (NEC 314.28)
11 Chapter 11: Motors, Controllers & Air Conditioning (NEC Articles 430 & 440)
11.1 Motor Full-Load Current (FLC), Branch Circuit Conductor Sizing & Disconnects (430.6, 430.22 & 430.102) 11.2 Motor Overload Protection & Motor Branch Circuit Short-Circuit/Ground-Fault Protection (430.32 & 430.52) 11.3 Motor Feeder Conductor Sizing & Feeder Overcurrent Protection (430.24 & 430.62) 11.4 Air Conditioning & Refrigeration Equipment (NEC Article 440: MCA, MOCP & Disconnects)
12 Chapter 12: Transformers & Equipment (NEC Articles 450, 410, 422 & 424)
12.1 Transformer Sizing, Protection & Voltage Calculations (NEC Article 450 & Table 450.3(B)) 12.2 Luminaires, Lampholders & Lamps Installation (NEC Article 410) 12.3 Appliances & Electric Water Heaters (NEC Article 422) 12.4 Fixed Electric Space-Heating Equipment (NEC Article 424) 12.5 Snow-Melting & De-Icing Equipment (Article 426) and Pipeline & Vessel Heating (Article 427) 12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)
13 Chapter 13: Special Occupancies & Hazardous Locations (NEC Articles 500–517)
13.1 Hazardous (Classified) Locations: Class I, II, and III (Articles 500, 501, 502 & 503) 13.2 Commercial Garages, Repair Facilities & Fuel Dispensing Facilities (Articles 511 & 514) 13.3 Health Care Facilities: Patient Care Spaces & Wiring Methods (Article 517) 13.4 Agricultural Buildings & Manufactured/Mobile Homes (Articles 547 & 550) 13.5 Bulk Storage Plants (Article 515) and Spray Application, Dipping & Coating (Article 516)
14 Chapter 14: Special Equipment, Swimming Pools & Low-Voltage Systems
14.1 Swimming Pools, Spas, Hot Tubs & Hydromassage Bathtubs (Article 680) 14.2 Emergency Systems, Legally Required & Optional Standby Systems (Articles 700, 701 & 702) 14.3 Class 1, 2, 3 & Class 4 Power-Limited Circuits (NEC Articles 722, 724, 725 & 726) and Fire Alarms (NEC Article 760) 14.4 RV Parks (Article 551), Floating Buildings (Article 553) & Marinas/Docking Facilities (Article 555)
12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)
Key Takeaways Explain This Topic AI
NEC 600.5(A) requires at least one sign or outline lighting outlet at each entrance to each tenant space in a commercial building or occupancy accessible to pedestrians, supplied by a branch circuit rated at least 20 amperes that supplies no other load.
NEC 220.14(F) requires a minimum of 1200 volt-amperes to be included in the calculated load for each required sign or outline lighting branch circuit.
NEC 600.6 requires a disconnecting means that opens all ungrounded conductors of the sign or outline lighting system, located within sight of the sign or the controller, or capable of being locked in the open position.
NEC 600.32 limits neon secondary circuit conductors to 1000 volts and requires listed GTO cable installed in a listed raceway or the sign body, with the secondary circuit kept as short as practicable.
Article 411 lighting systems operating at 30 volts or less must be supplied from a branch circuit rated no more than 20 amperes, with the power supply output limited to 30 volts (42.4 volts peak) and 25 amperes maximum.
Last updated: August 2026
12.6 Electric Signs & Outline Lighting (Article 600) and Lighting Systems 30 Volts or Less (Article 411)
Lighting and Signs carries 10 scored items on the PSI outline — the same weight as Grounding and Bonding and more than Conductors and Cables. Section 12.2 covered luminaire installation under Article 410. Two of the eight listed sub-topics, lighting systems that operate at less than 30 volts and neon lighting and electric signs , live in entirely different articles that a general journeyman course usually skips.
- 1. Article 600 — Electric Signs and Outline Lighting
- The required sign outlet (600.5)
NEC 600.5(A) requires that each commercial building and each commercial occupancy accessible to pedestrians be provided with at least one outlet in an accessible location at each entrance to each tenant space for sign or outline lighting use.
- Requirement Value
- Minimum branch-circuit rating 20 amperes
Other loads permitted on that circuit None — except loads directly related to control of the sign, such as electronic or electromechanical controllers
Minimum calculated load per required branch circuit 1200 volt-amperes (NEC 220.14(F))
Where the outlet is not required Service hallways or corridors, which are not considered accessible to pedestrians
Load-calculation consequence. A strip center with eight tenant spaces has eight required sign outlets. That is 8 × 1200 VA = 9,600 VA that must appear in the service calculation whether or not a single tenant has hung a sign yet. Candidates who calculate a shell-building service and forget the sign load undersize the service.
Disconnecting means (600.6)
Each sign and outline lighting system, and each feeder circuit or branch circuit supplying a sign, must have a disconnecting means that opens all ungrounded conductors and is either within sight of the sign or outline lighting system it controls, or capable of being locked in the open position with the locking means remaining in place with or without the lock installed. Where the sign is operated by an electronic or electromechanical controller located externally, the disconnect is permitted to be within sight of the controller — with a field-applied permanent label on the sign identifying the disconnect location.
Grounding, bonding, and listing
Signs and outline lighting systems must be listed and installed per the installation instructions unless they are field-installed skeleton tubing or otherwise specifically addressed.
600.7 requires the metal parts of the sign to be grounded and bonded . The bonding conductor for sign sections and metal parts is a specified minimum copper size, and the bonding path must be continuous through metal raceways and across sign sections. Where a remote metal enclosure or a section of a sign is separated, an equipment bonding jumper is required.
600.21 requires that transformers, power supplies, ballasts, and drivers be accessible — an attic or suspended-ceiling location must have an access opening and adequate working space, and the equipment may not be permanently sealed behind finish.
600.24 covers Class 2 power sources used in signs, permitting Class 2 wiring methods for the low-energy portions of the system.
Portable and mobile signs (600.10)
A portable or mobile sign — the wheeled arrow board in a parking lot — must be listed , must be supplied through a flexible cord of limited length, and must be provided with ground-fault circuit-interrupter protection , either integral to the sign or in the attachment plug.
Neon: field-installed skeleton tubing (Part II)
- Rule Requirement
- Secondary voltage limit (600.32) 1000 volts maximum for neon secondary circuit conductors
Secondary conductor type Listed GTO cable , rated for the voltage, installed in a listed raceway or in the sign body/metal enclosure
Length Secondary conductors kept as short as practicable ; the longer the high-voltage run, the greater the capacitive loss and the fire risk
Spacing Secondary conductors must be spaced from each other and from grounded metal per the article; the raceway must be sized so the high-voltage insulation is not compressed
Transformer/power supply Must be listed, marked with the secondary voltage and current, and provided with secondary-circuit ground-fault protection
Electrode connections Made inside a listed receptacle or enclosure; bare electrode terminals may not be accessible to unqualified persons
A journeyman is not usually the person bending the tubing, but is the person who lands the primary circuit, mounts and grounds the transformer enclosure, and gets the disconnect right.
2. Article 411 — Lighting Systems Operating at 30 Volts or Less
Article 411 governs the low-voltage lighting systems used for landscape lighting, display lighting, cove lighting, and cable/rail systems: a listed assembly of an isolating power supply, the low-voltage luminaires, and the connecting wiring.
- Rule Requirement
- Supply branch circuit Rated not more than 20 amperes
- Secondary output 30 volts maximum (42.4 volts peak), 25 amperes maximum under all load conditions
Listing The lighting system must be listed as a complete system, or assembled from listed components identified for the use
Bare conductors Permitted only as part of a listed system, installed so that accidental contact and short circuits between conductors are prevented
Concealed or extended wiring Where the secondary wiring is concealed or extended through a building wall, it must use a Chapter 3 wiring method
Pools, spas, and fountains Article 411 systems may not be installed within 10 feet (3.0 m) of pools, spas, fountains, and similar locations except as permitted by Article 680
Warning
"Low voltage" is not "low energy." A 300-watt landscape transformer at 12 volts sources 25 amperes into a bare conductor pair. That is more than enough to melt a wedding ring, ignite dry mulch at a damaged splice, or set a landscape wire on fire under a mower cut. The 25-ampere output cap and the listing requirement in Article 411 exist precisely because the shock hazard is low and the thermal hazard is not.
3. Fluorescent, Recessed, and Closet Rules from Article 410
The remaining Lighting and Signs sub-topics — fixture construction requirements, fluorescent fixtures, and recessed fixtures — are Article 410 rules that produce exam items every cycle:
Recessed luminaire clearances (410.116). A non-IC-rated recessed luminaire must have at least ½ inch of clearance from combustible materials (except at the points of support), and thermal insulation must be kept at least 3 inches from the enclosure and wiring compartment and may not be installed above the luminaire so as to entrap heat. A luminaire identified for insulation contact (Type IC) may be in direct contact with insulation and covered by it.
Fluorescent ballast disconnect (410.130(G)). Fluorescent luminaires that use double-ended lamps and contain ballasts must have a disconnecting means in indoor locations, external to or accessible within the luminaire, so a maintenance worker can de-energize the ballast without pulling a branch-circuit breaker in another room. The disconnect must simultaneously break all supply conductors, including the grounded conductor.
Bathtub and shower zone (410.10(D)). No cord-connected luminaire, chain-, cable-, or cord-suspended luminaire, lighting track, pendant, or ceiling-suspended paddle fan may be located within a zone measured 3 feet horizontally and 8 feet vertically from the top of the bathtub rim or shower stall threshold. Luminaires in that zone must be listed for damp locations , or listed for wet locations where subject to shower spray.
Clothes closet clearances (410.16). Minimum clearance from the nearest point of a storage space : 12 inches for a surface-mounted incandescent or LED luminaire with a completely enclosed light source; 6 inches for a surface-mounted fluorescent luminaire; 6 inches for a recessed incandescent or LED luminaire with a completely enclosed light source; 6 inches for a recessed fluorescent luminaire. Surface-mounted fluorescent or LED luminaires are permitted within the storage space where identified for that use. Open-lamp incandescent luminaires and pendants are not permitted in clothes closets at all.