Study guide
11.1 Secondary Treatment: Activated Sludge Process Control & Variations
Oregon Water and Wastewater Operator Certification Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Oregon Operator Programs and DEQ Wastewater Certification
1.1 Dual-Agency Structure: DEQ Wastewater and OHA Drinking Water Programs 1.2 DEQ Wastewater System Classification and Supervision Rules 1.3 DEQ Certificates: Qualifications, OIT, Provisional Path, Exams and Fees
2 Chapter 2: OHA Drinking Water Certification and Certificate Renewal
2.1 OHA System Classification, Direct Responsible Charge and the Filtration Endorsement 2.2 OHA Certificates: Experience Tables, OIT, Exams, Fees and Small Water System Certification 2.3 Renewal, CEUs, Reinstatement, Reciprocity and Discipline for DEQ and OHA Certificates
3 Chapter 3: Federal Rules, Oregon Water Quality Standards and Cyanotoxins
3.1 Clean Water Act, Safe Drinking Water Act & NPDES Permitting 3.2 Willamette Basin TMDL and Oregon Water Quality Standards 3.3 Harmful Algal Blooms (HABs) & Oregon Cyanotoxin Rules (OAR 333-061-0510)
4 Chapter 4: Source Water, Intakes and Wells
4.1 Raw Water Sources, Intake Structures & Pretreatment 4.2 Groundwater Sources and Wells: Hydraulics, Construction and Protection
5 Chapter 5: Coagulation, Clarification and Filtration
5.1 Coagulation, Flocculation & Jar Testing Dynamics 5.2 Sedimentation, Clarification & Media Filtration Systems 5.3 Slow Sand, Diatomaceous Earth, Cartridge and Membrane Filtration
6 Chapter 6: Drinking Water Disinfection
6.1 Disinfection Chemistry, Chlorination Dynamics & CT Calculations 6.2 UV, Ozone, Chlorine Dioxide, Chloramines and Disinfection Byproduct Control
7 Chapter 7: Specialty Water Treatment and Residuals
7.1 Iron and Manganese Removal, Softening, and Taste and Odor Control 7.2 Corrosion Control, Lead and Copper, and Fluoridation 7.3 Water Treatment Residuals: Sludge, Backwash Water and Membrane Concentrate
8 Chapter 8: Distribution System Infrastructure
8.1 Distribution System Hydraulics, Piping Materials & Storage Facilities 8.2 Valves, Fire Hydrants & Water Main Installation / Disinfection 8.3 Service Connections, Meters, Water Loss Control and Utility Locating
9 Chapter 9: Distribution Operations, Cross-Connection Control and Water Quality
9.1 Storage Tank and Booster Pump Station Operation, Inspection and Disinfection 9.2 Cross-Connection Control & Backflow Prevention Assemblies (OAR 333-061-0070) 9.3 Water Quality in Distribution: Water Age, Nitrification & Flushing Programs
10 Chapter 10: Wastewater Preliminary and Primary Treatment and Lagoons
10.1 Preliminary Treatment: Screening, Grit Removal & Flow Measurement 10.2 Primary Clarification & Sedimentation Hydraulics 10.3 Stabilization Ponds and Aerated Lagoons
11 Chapter 11: Biological Wastewater Treatment
11.1 Secondary Treatment: Activated Sludge Process Control & Variations 11.2 Fixed-Film Treatment: Trickling Filters, RBCs, MBBR and IFAS 11.3 Biological Nutrient Removal: Nitrification, Denitrification & Phosphorus Removal
12 Chapter 12: Tertiary Treatment, Disinfection, Recycled Water and Small Systems
12.1 Tertiary Filtration, Membrane Bioreactors and Oregon Recycled Water Classes 12.2 Wastewater Disinfection and Dechlorination 12.3 Small Wastewater Systems, Septage Handling and Odor Control
13 Chapter 13: Solids Handling and Biosolids
13.1 Sludge Thickening, Conditioning & Dewatering Technologies 13.2 Anaerobic and Aerobic Digestion Operations & Control 13.3 Biosolids Quality, Land Application Rules & OAR 340-050 / 40 CFR 503
14 Chapter 14: Wastewater Collection Systems and Pumping
14.1 Gravity Sewer Design, Manholes & Inflow/Infiltration (I/I) Management 14.2 Lift Station Design, Wet Wells & Submersible / Centrifugal Pumps 14.3 Collection System Maintenance, Pipeline Inspection (CCTV) & Trench Safety
15 Chapter 15: Collection System Rehabilitation and Overflow Control
15.1 Sewer Rehabilitation, Trenchless Renewal and New-Pipe Acceptance Testing 15.2 Overflow Response, Bypass Pumping, CMOM Programs and Sewer Sulfide Control
16 Chapter 16: Laboratory Procedures and Water Quality Testing
16.1 Drinking Water Microbiological Testing: Coliform, E. coli & RTCR 16.2 Wastewater Lab Analysis: BOD5, TSS, COD & Volatile Solids 16.3 Wastewater Lab: Nutrients, Alkalinity, Bacteria, Toxicity Testing and Lab Accreditation 16.4 Process Monitoring: pH, Turbidity, Dissolved Oxygen & Chlorine Residuals 16.5 Sampling Protocols, Quality Assurance / Chain of Custody & Reporting
17 Chapter 17: Equipment, Electrical Systems and Maintenance
17.1 Pumps, Blowers and Mechanical Maintenance Programs 17.2 Electrical Systems, Motors, Generators, Instrumentation and SCADA
18 Chapter 18: Applied Water and Wastewater Mathematics
18.1 Dimensional Analysis, Flow Conversions & Detention Time 18.2 Chemical Feed, Dosage Calculations & the Pounds Formula 18.3 Treatment Plant Hydraulics, Loading Rates (SOR, WOR) & Pumping Horsepower
19 Chapter 19: Utility Safety
19.1 OSHA Standards, Confined Space Entry & Hazardous Chemical Safety 19.2 Field Safety: Electrical Hazards, Fall Protection, Work Zones, PPE and Oregon OSHA Rules
20 Chapter 20: Emergency Preparedness, Security and Utility Management
20.1 Cascadia Subduction Zone (CSZ) Seismic Preparedness & Infrastructure Hardening 20.2 Wildfire Impacts on Watersheds, Post-Fire Water Quality & Emergency Operations 20.3 Security, Cybersecurity, Emergency Response Planning and Utility Management
11.1 Secondary Treatment: Activated Sludge Process Control & Variations
Key Takeaways Explain This Topic AI
The activated sludge process utilizes a suspension of aerobic heterotrophic microorganisms (mixed liquor) to biologically oxidize soluble and colloidal organic pollutants (BOD5) into cell mass, carbon dioxide, and water.
Microscopic examination of protozoan and metazoan bio-indicators provides real-time diagnostic evaluation of sludge health: flagellates and amoebas denote young sludge and high F/M, stalked ciliates dominate healthy mature systems, and rotifers or nematodes indicate old sludge and high MCRT.
Core operational control metrics include the Food-to-Microorganism ratio (F/M = 0.2–0.5 lb BOD/lb MLVSS·d), Mean Cell Residence Time (MCRT = 5–15 days conventional), and Sludge Volume Index (SVI = 80–150 mL/g ideal settleability).
Rising sludge in secondary clarifiers is caused by biological denitrification in deep sludge blankets where N2 gas bubbles lift settled sludge sheets; this requires increasing RAS rates and lowering blanket depths, contrasting with filamentous bulking which requires dissolved oxygen adjustment or targeted RAS chlorination.
Last updated: October 2026
4.3 Secondary Treatment: Activated Sludge Process Control & Variations
Note
The activated sludge process is an engineered biological suspension system wherein a concentrated mass of aerobic microorganisms (floc) continuously oxidizes, adsorbs, and assimilates dissolved and colloidal organic compounds. Understanding the complex interactions between aeration basin hydraulics, solids wasting rates, microbial ecology, and secondary clarification is the cornerstone of advanced wastewater treatment operations.
Biological Principles & Microbial Ecology
In the activated sludge reactor, aerobic heterotrophic bacteria serve as the primary biochemical workhorses. They synthesize extracellular polymeric substances (EPS)—primarily polysaccharides, proteins, and lipids—that form the structural glue binding bacteria, colloidal particles, and non-settleable solids into dense, settleable biological flocs .
Protozoan & Metazoan Succession as Sludge Age Indicators
While bacteria perform the bulk of organic oxidation, microscopic examination of higher-order protozoa and metazoa provides operators with an immediate, visual diagnosis of biological health, sludge age, and effluent quality: +-----------------------------------------------------------------------------+
- | ACTIVATED SLUDGE MICROBIAL SUCCESSION |
- +-----------------------------------------------------------------------------+
- | YOUNG SLUDGE / HIGH F/M TRANSITIONAL PHASE OLD SLUDGE / LOW F/M |
- | - Low MCRT (< 3 days) - MCRT: 4 - 8 days - High MCRT (> 15 days) |
- | - Dispersed Bacteria - Free-Swimming - Stalked Ciliates |
- | - Flagellates dominate Ciliates dominate & Suctorians |
- | - Amoebas present - Floc forming - Rotifers abundant |
- | - High Effluent Turbidity - Moderate Turbidity - Nematodes present |
- | - Pin Floc / Ashing |
- | =========================> TIME / SLUDGE AGE ===========================> |
- +-----------------------------------------------------------------------------+
Organism Class Dominant Species Examples Sludge Age / F/M State Operational & Diagnostic Significance
Amoebas Arcella , Chaos Very Young Sludge; F / M > 0.6 F/M > 0.6 F / M > 0.6 ; Startup Single-celled; sluggish pseudopod movement. Signifies severe organic overloading, recovering from toxic shock, or excessive solids wasting. Turbid effluent.
Flagellates Bodo , Monas , Euglena Young Sludge; F / M = 0.5 − 0.8 F/M = 0.5 - 0.8 F / M = 0.5 − 0.8 ; Low MCRT Propelled by 1–2 whip-like flagella. Feed on dispersed single bacteria. Indicate poorly flocculated mixed liquor and high soluble BOD in effluent.
Free-Swimming Ciliates Paramecium , Colpidium Intermediate Sludge; F / M = 0.3 − 0.5 F/M = 0.3 - 0.5 F / M = 0.3 − 0.5 Covered in coordinated cilia. Graze heavily on dispersed bacteria, clearing the supernatant liquor. Sign of improving bio-flocculation.
Stalked Ciliates Vorticella , Carchesium , Epistylis Mature Sludge; F / M = 0.2 − 0.4 F/M = 0.2 - 0.4 F / M = 0.2 − 0.4 ; Ideal MCRT Attached to floc matrices by contractile stalks. Indicate high process stability, low effluent turbidity, and complete bio-sorption.
Rotifers & Nematodes Philodina , Nematoda worms Old Sludge; F / M < 0.15 F/M < 0.15 F / M < 0.15 ; Extended Aeration Complex multicellular metazoa. Capable of consuming large floc fragments. Indicate very high MCRT ( > 15 − 20 days > 15-20 \text{ days} > 15 − 20 days ), complete nitrification, and potential for pin floc formation.
Aeration Basin Operation & Dissolved Oxygen (DO)
Aerobic heterotrophs and autotrophic nitrifiers require continuous molecular oxygen to sustain metabolic respiration and cell synthesis:
Target Dissolved Oxygen Range: 1.5 to 2.5 mg/L 1.5 \text{ to } 2.5 \text{ mg/L} 1.5 to 2.5 mg/L ( 2.0 mg/L 2.0 \text{ mg/L} 2.0 mg/L optimal setpoint throughout the aeration basin).
Consequences of Low DO ( < 1.0 mg/L < 1.0 \text{ mg/L} < 1.0 mg/L ): Low oxygen environments favor the proliferation of filamentous bacteria (such as Sphaerotilus natans and Type 021N ), which possess higher surface-area-to-volume ratios and outcompete floc-forming bacteria for limited oxygen. This triggers severe filamentous sludge bulking . Incomplete BOD oxidation occurs, and autotrophic nitrification ceases entirely.
Consequences of Excessive DO ( > 4.0 mg/L > 4.0 \text{ mg/L} > 4.0 mg/L ): Over-aeration wastes substantial electrical blower power. High shear forces from aggressive bubbling physically tear fragile flocs apart into non-settleable micro-flocs ( pin floc ), increasing effluent turbidity. Furthermore, high dissolved oxygen carried into anoxic zones via return streams suppresses biological denitrification.
Aeration Technologies:
Fine-Bubble Diffusers: Submerged flexible EPDM membranes or porous ceramic domes. High Standard Oxygen Transfer Efficiency ( SOTE = 25 % to 35 % \text{SOTE} = 25\% \text{ to } 35\% SOTE = 25% to 35% in clean water). Deliver tiny bubbles ( 1 − 3 mm 1-3 \text{ mm} 1 − 3 mm ) with high contact surface area.
Mechanical Surface Aerators: Rotating impellers or brush rotors splashing at the liquid surface. Low capital cost and resilient against clogging, but lower transfer efficiency ( SOTE = 8 % to 12 % \text{SOTE} = 8\% \text{ to } 12\% SOTE = 8% to 12% ) and vulnerable to aerosol dispersion and freezing in cold climates.
Mixed Liquor Suspended Solids: MLSS vs. MLVSS
Mixed Liquor Suspended Solids (MLSS): The total concentration of all filterable solids suspended within the aeration basin, comprising active biomass, dead microbial debris, inert mineral grit, and non-biodegradable suspended solids. Measured in mg/L \text{mg/L} mg/L . Typical conventional range: 1500 to 3500 mg/L 1500 \text{ to } 3500 \text{ mg/L} 1500 to 3500 mg/L .
Mixed Liquor Volatile Suspended Solids (MLVSS): The organic, combustible fraction of MLSS determined by igniting the dried sample filter in a muffle furnace at 550 ∘ C 550^\circ\text{C} 55 0 ∘ C . Only the volatile fraction represents active, living biological biomass:
Volatile Fraction = MLVSS (mg/L) MLSS (mg/L) ≈ 0.70 − 0.80 ( 70 % to 80 % in healthy plants ) \text{Volatile Fraction } = \frac{\text{MLVSS (mg/L)}}{\text{MLSS (mg/L)}} \approx 0.70 - 0.80 \quad (70\% \text{ to } 80\% \text{ in healthy plants}) Volatile Fraction = MLSS (mg/L) MLVSS (mg/L) ≈ 0.70 − 0.80 ( 70% to 80% in healthy plants )
If the volatile fraction drops below 65 % 65\% 65% , it indicates excessive inert mineral silt, sand, or chemical precipitate accumulation in the biological system.
Process Control Metrics & Formulas
Operators maintain biological process equilibrium through four foundational mathematical tools: F / M F/M F / M ratio, MCRT, SVI, and solids mass balances.
1. Food-to-Microorganism ( F / M F/M F / M ) Ratio
The F / M F/M F / M ratio quantifies the organic loading applied per unit mass of active biological solids per day:
F / M = lbs BOD 5 added per day lbs MLVSS present under aeration F/M = \frac{\text{lbs } \text{BOD}_5 \text{ added per day}}{\text{lbs MLVSS present under aeration}} F / M = lbs MLVSS present under aeration lbs BOD 5 added per day
F / M = Q ( MGD ) × Influent BOD 5 ( mg/L ) × 8.34 lbs/gal V aer ( MG ) × MLVSS ( mg/L ) × 8.34 lbs/gal F/M = \frac{Q (\text{MGD}) \times \text{Influent BOD}_5 (\text{mg/L}) \times 8.34 \text{ lbs/gal}}{V_{\text{aer}} (\text{MG}) \times \text{MLVSS} (\text{mg/L}) \times 8.34 \text{ lbs/gal}} F / M = V aer ( MG ) × MLVSS ( mg/L ) × 8.34 lbs/gal Q ( MGD ) × Influent BOD 5 ( mg/L ) × 8.34 lbs/gal
Operational Ranges:
Conventional Plug-Flow / Complete Mix: 0.2 to 0.5 lb BOD 5 / lb MLVSS ⋅ day 0.2 \text{ to } 0.5 \text{ lb BOD}_5 / \text{lb MLVSS}\cdot\text{day} 0.2 to 0.5 lb BOD 5 / lb MLVSS ⋅ day
Extended Aeration / Oxidation Ditch: 0.05 to 0.15 lb BOD 5 / lb MLVSS ⋅ day 0.05 \text{ to } 0.15 \text{ lb BOD}_5 / \text{lb MLVSS}\cdot\text{day} 0.05 to 0.15 lb BOD 5 / lb MLVSS ⋅ day
2. Mean Cell Residence Time (MCRT) / Solids Retention Time (SRT) / Sludge Age
MCRT represents the average duration, in days, that a biological cell remains within the treatment system before being removed via wasting or effluent loss:
MCRT ( days ) = Total lbs MLSS in the aeration basin (or system) lbs WAS TSS wasted/day + lbs Effluent TSS lost/day \text{MCRT } (\text{days}) = \frac{\text{Total lbs MLSS in the aeration basin (or system)}}{\text{lbs WAS TSS wasted/day} + \text{lbs Effluent TSS lost/day}} MCRT ( days ) = lbs WAS TSS wasted/day + lbs Effluent TSS lost/day Total lbs MLSS in the aeration basin (or system)
MCRT = V aer ( MG ) × MLSS ( mg/L ) × 8.34 ( Q WAS ( MGD ) × WAS TSS ( mg/L ) × 8.34 ) + ( Q eff ( MGD ) × Eff TSS ( mg/L ) × 8.34 ) \text{MCRT} = \frac{V_{\text{aer}} (\text{MG}) \times \text{MLSS} (\text{mg/L}) \times 8.34}{(Q_{\text{WAS}} (\text{MGD}) \times \text{WAS}_{\text{TSS}} (\text{mg/L}) \times 8.34) + (Q_{\text{eff}} (\text{MGD}) \times \text{Eff}_{\text{TSS}} (\text{mg/L}) \times 8.34)} MCRT = ( Q WAS ( MGD ) × WAS TSS ( mg/L ) × 8.34 ) + ( Q eff ( MGD ) × Eff TSS ( mg/L ) × 8.34 ) V aer ( MG ) × MLSS ( mg/L ) × 8.34
Operational Ranges:
- Conventional Activated Sludge: 5 to 15 days 5 \text{ to } 15 \text{ days} 5 to 15 days
- Extended Aeration Systems: 20 to 30 + days 20 \text{ to } 30+ \text{ days} 20 to 30 + days
- 3. Sludge Volume Index (SVI)
SVI is an empirical settling parameter that reflects the compaction and settling characteristics of mixed liquor in a secondary clarifier. It is determined by conducting a 30-minute settled sludge volume test ( SV 30 \text{SV}_{30} SV 30 ) in a 1000 mL 1000 \text{ mL} 1000 mL graduated cylinder or wide-mouth Settlometer:
SVI ( mL/g ) = Settled Sludge Volume after 30 min ( SV 30 , mL/L ) × 1000 Aeration Basin MLSS ( mg/L ) \text{SVI } (\text{mL/g}) = \frac{\text{Settled Sludge Volume after 30 min } (\text{SV}_{30}, \text{ mL/L}) \times 1000}{\text{Aeration Basin MLSS } (\text{mg/L})} SVI ( mL/g ) = Aeration Basin MLSS ( mg/L ) Settled Sludge Volume after 30 min ( SV 30 , mL/L ) × 1000 +-----------------------------------------------------------------------------+
- | SVI OPERATIONAL INTERPRETATION |
- +-----------------------------------------------------------------------------+
- | SVI < 80 mL/g | Dense, granular, old sludge; rapid settling; leaves |
- | | tiny pin flocs in supernatant (turbid effluent). |
- |-----------------------+-----------------------------------------------------|
- | SVI = 80 - 150 mL/g | IDEAL SETTLEABILITY: Rapid, uniform sludge blanket |
- | | descent with crystal clear supernatant liquor. |
- |-----------------------+-----------------------------------------------------|
- | SVI > 150 - 200 mL/g | BULKING SLUDGE: Slow, fluffy settling; high blanket |
- | | in clarifier; severe danger of solids carryover. |
- +-----------------------------------------------------------------------------+
- 4. Return Activated Sludge (RAS) & Waste Activated Sludge (WAS) Control
Return Activated Sludge (RAS): Concentrated settled biological solids recycled from the bottom of secondary clarifiers back to the aeration basin inlet to maintain target MLSS inventory. Flow rate typically ranges from 25 % to 100 % 25\% \text{ to } 100\% 25% to 100% of plant influent flow. Mass balance equation:
Q RAS = Q × MLSS RAS TSS − MLSS Q_{\text{RAS}} = \frac{Q \times \text{MLSS}}{\text{RAS}_{\text{TSS}} - \text{MLSS}} Q RAS = RAS TSS − MLSS Q × MLSS
Waste Activated Sludge (WAS): The mass of excess biomass purged daily from the system to maintain a constant target MCRT and F / M F/M F / M ratio. WAS wasting is the primary process control handle operated by wastewater technicians.
Activated Sludge Process Variations
Process Variation Flow Pattern & Hydraulic Regime Typical MLSS Range Key Operational Features & Tradeoffs
Plug-Flow Long, narrow serpentine basins ( L : W ≥ 10 : 1 L:W \ge 10:1 L : W ≥ 10 : 1 ) 1500 − 3000 mg/L 1500 - 3000 \text{ mg/L} 1500 − 3000 mg/L High F / M F/M F / M and high oxygen demand at inlet; tapering air profile required; susceptible to shock loads.
Complete Mix Square or round basins with rapid uniform dispersion 2500 − 4500 mg/L 2500 - 4500 \text{ mg/L} 2500 − 4500 mg/L Completely dampens toxic shock and peak hydraulic surges; uniform oxygen demand throughout tank.
Step Feed Plug-flow basin with influent split into multiple inlet ports 2000 − 4000 mg/L 2000 - 4000 \text{ mg/L} 2000 − 4000 mg/L High biomass inventory in front passes while decreasing solids loading rate on secondary clarifiers.
Contact Stabilization Two separate tanks: short contact (30–60 min) and stabilization (3–6 hrs) Contact: 1500 − 2500 1500 - 2500 1500 − 2500 mg/L; Stab: 4000 − 8000 4000 - 8000 4000 − 8000 mg/L Rapid biosorption of soluble BOD; reduces total required tank volume by 40 − 50 % 40-50\% 40 − 50% ; complex solids balancing.
Oxidation Ditch Closed-loop oval racetrack channel with mechanical brush rotors 3000 − 5000 mg/L 3000 - 5000 \text{ mg/L} 3000 − 5000 mg/L Extended aeration regime (MCRT > 20 days > 20 \text{ days} > 20 days ); robust nitrification; exceptional resistance to shock loads.
Sequencing Batch Reactor (SBR) Single-tank cyclical batch operation: Fill, React, Settle, Decant, Idle 2500 − 5000 mg/L 2500 - 5000 \text{ mg/L} 2500 − 5000 mg/L Eliminates secondary clarifiers and RAS pumps; flexible cycle timing allows targeted nutrient removal.
Membrane Bioreactor (MBR) Aeration basin integrated with 0.04 − 0.1 μ m 0.04 - 0.1 \ \mu\text{m} 0.04 − 0.1 μ m microfiltration cassettes 8000 − 12 , 000 mg/L 8000 - 12,000 \text{ mg/L} 8000 − 12 , 000 mg/L Eliminates secondary clarifiers entirely; small footprint; crystal clear effluent ( < 0.1 NTU < 0.1 \text{ NTU} < 0.1 NTU ); high membrane aeration power.
Operational Troubleshooting: Bulking, Foaming & Rising Sludge
Distinguishing between different clarifier and biological upsets is essential for choosing the proper corrective action. +-----------------------------------------------------------------------------+
- | DIAGNOSTIC MATRIX: SECONDARY CLARIFIER UPSETS |
- +-----------------------+-----------------------------+-----------------------+
- | FILAMENTOUS BULKING | RISING SLUDGE | PIN FLOC |
- | - High SVI (> 150) | - Normal SVI (80 - 120) | - Low SVI (< 80) |
- | - Settles very slowly | - Settles well in cylinder, | - Settles rapidly |
- | - Blanket floats | floats later with gas | - Turbid supernatant |
- | - Interlocking fibers | - N2 gas bubbles present | - Microscopic spheres |
- | - Cause: Low DO/F:M | - Cause: Denitrification | - Cause: Over-aerated |
- +-----------------------+-----------------------------+-----------------------+
- 1. Filamentous Bulking
Mechanism: Excessive proliferation of filamentous bacteria ( Microthrix parvicella , Sphaerotilus natans , Type 021N , Nostocoida limicola ) that extend outward from the biological floc, physically preventing floc particles from consolidating and compacting.
Diagnostic Signs: Extremely high SVI ( > 150 − 250 mL/g > 150-250 \text{ mL/g} > 150 − 250 mL/g ); slow, uniform sludge blanket settling; clear supernatant in settlometer test; secondary clarifier blanket expands upward until overflowing weirs.
Root Causes: Basin DO < 1.5 mg/L < 1.5 \text{ mg/L} < 1.5 mg/L ; very low F / M F/M F / M ; septic influent high in sulfides ( H 2 S \text{H}_2\text{S} H 2 S ); or nutrient deficiency (ratio of BOD 5 : N : P \text{BOD}_5 : \text{N} : \text{P} BOD 5 : N : P below 100 : 5 : 1 100 : 5 : 1 100 : 5 : 1 ).
Emergency Control: Carefully dosed chlorination of the RAS stream at 2 to 3 lbs Cl 2 / 1000 lbs MLSS ⋅ day 2 \text{ to } 3 \text{ lbs } \text{Cl}_2 / 1000 \text{ lbs MLSS}\cdot\text{day} 2 to 3 lbs Cl 2 /1000 lbs MLSS ⋅ day . Chlorine selectively attacks the extended filamentous sheaths protruding into the bulk liquid while sparing the protected bacteria inside the dense floc core.
2. Rising Sludge (Clarifier Denitrification)
Mechanism: Biological denitrification occurring in the secondary clarifier sludge blanket. When mixed liquor containing elevated nitrate ( NO 3 − \text{NO}_3^- NO 3 − ) is held under anoxic conditions in a deep sludge blanket ( > 2 − 4 hours > 2-4 \text{ hours} > 2 − 4 hours ), facultative heterotrophs strip oxygen from nitrate, releasing nitrogen gas ( N 2 \text{N}_2 N 2 ) :
2 NO 3 − + 10 e − + 12 H + → N 2 ↑ + 6 H 2 O 2\text{NO}_3^- + 10e^- + 12\text{H}^+ \rightarrow \text{N}_2\uparrow + 6\text{H}_2\text{O} 2 NO 3 − + 10 e − + 12 H + → N 2 ↑ + 6 H 2 O
The insoluble N 2 \text{N}_2 N 2 gas bubbles attach to settled sludge flocs, floating large, consolidated sheets or clods of sludge to the surface.
Crucial Diagnostic Distinction: The SVI test reveals normal, rapid settling ( 80 to 120 mL/g 80 \text{ to } 120 \text{ mL/g} 80 to 120 mL/g ) and clear supernatant during the first 15–20 minutes. However, after 30 to 60 minutes of sitting in the cylinder, the entire settled sludge mass floats to the top buoyed by gas bubbles.
Remedy: Increase the Return Activated Sludge (RAS) pumping rate to lower the clarifier blanket depth and reduce solids retention time in the clarifier; reduce aeration basin SRT if nitrification is not permit-mandated.
3. Biological Foaming Types
Viscous Brown Nocardia Foam: Thick, greasy, chocolate-brown foam accumulating on aeration basins and secondary clarifier surfaces. Caused by actinomycetes ( Nocardia , Gordonia ) and Microthrix parvicella , which possess hydrophobic mycolic acid cell walls that trap air bubbles. Triggered by high MCRT ( > 10 − 15 days > 10-15 \text{ days} > 10 − 15 days ), warm water temperatures, and elevated influent Fats, Oils, and Grease (FOG). Controlled by aggressively lowering MCRT (increasing WAS wasting), spraying cationic polymer/chlorine sprays on the surface, and never returning skimmed foam to the plant headworks.
White Frothy Foam: Billowy, white, soapy foam covering aeration basins. Caused by very young sludge (low MCRT, very high F / M > 0.6 F/M > 0.6 F / M > 0.6 ) or synthetic non-biodegradable surfactants. Controlled by decreasing WAS wasting to build mixed liquor solids inventory.