Study guide

11.3 Biological Nutrient Removal: Nitrification, Denitrification & Phosphorus Removal

Oregon Water and Wastewater Operator Certification Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Oregon Operator Programs and DEQ Wastewater Certification

1.1 Dual-Agency Structure: DEQ Wastewater and OHA Drinking Water Programs 1.2 DEQ Wastewater System Classification and Supervision Rules 1.3 DEQ Certificates: Qualifications, OIT, Provisional Path, Exams and Fees

2 Chapter 2: OHA Drinking Water Certification and Certificate Renewal

2.1 OHA System Classification, Direct Responsible Charge and the Filtration Endorsement 2.2 OHA Certificates: Experience Tables, OIT, Exams, Fees and Small Water System Certification 2.3 Renewal, CEUs, Reinstatement, Reciprocity and Discipline for DEQ and OHA Certificates

3 Chapter 3: Federal Rules, Oregon Water Quality Standards and Cyanotoxins

3.1 Clean Water Act, Safe Drinking Water Act & NPDES Permitting 3.2 Willamette Basin TMDL and Oregon Water Quality Standards 3.3 Harmful Algal Blooms (HABs) & Oregon Cyanotoxin Rules (OAR 333-061-0510)

4 Chapter 4: Source Water, Intakes and Wells

4.1 Raw Water Sources, Intake Structures & Pretreatment 4.2 Groundwater Sources and Wells: Hydraulics, Construction and Protection

5 Chapter 5: Coagulation, Clarification and Filtration

5.1 Coagulation, Flocculation & Jar Testing Dynamics 5.2 Sedimentation, Clarification & Media Filtration Systems 5.3 Slow Sand, Diatomaceous Earth, Cartridge and Membrane Filtration

6 Chapter 6: Drinking Water Disinfection

6.1 Disinfection Chemistry, Chlorination Dynamics & CT Calculations 6.2 UV, Ozone, Chlorine Dioxide, Chloramines and Disinfection Byproduct Control

7 Chapter 7: Specialty Water Treatment and Residuals

7.1 Iron and Manganese Removal, Softening, and Taste and Odor Control 7.2 Corrosion Control, Lead and Copper, and Fluoridation 7.3 Water Treatment Residuals: Sludge, Backwash Water and Membrane Concentrate

8 Chapter 8: Distribution System Infrastructure

8.1 Distribution System Hydraulics, Piping Materials & Storage Facilities 8.2 Valves, Fire Hydrants & Water Main Installation / Disinfection 8.3 Service Connections, Meters, Water Loss Control and Utility Locating

9 Chapter 9: Distribution Operations, Cross-Connection Control and Water Quality

9.1 Storage Tank and Booster Pump Station Operation, Inspection and Disinfection 9.2 Cross-Connection Control & Backflow Prevention Assemblies (OAR 333-061-0070) 9.3 Water Quality in Distribution: Water Age, Nitrification & Flushing Programs

10 Chapter 10: Wastewater Preliminary and Primary Treatment and Lagoons

10.1 Preliminary Treatment: Screening, Grit Removal & Flow Measurement 10.2 Primary Clarification & Sedimentation Hydraulics 10.3 Stabilization Ponds and Aerated Lagoons

11 Chapter 11: Biological Wastewater Treatment

11.1 Secondary Treatment: Activated Sludge Process Control & Variations 11.2 Fixed-Film Treatment: Trickling Filters, RBCs, MBBR and IFAS 11.3 Biological Nutrient Removal: Nitrification, Denitrification & Phosphorus Removal

12 Chapter 12: Tertiary Treatment, Disinfection, Recycled Water and Small Systems

12.1 Tertiary Filtration, Membrane Bioreactors and Oregon Recycled Water Classes 12.2 Wastewater Disinfection and Dechlorination 12.3 Small Wastewater Systems, Septage Handling and Odor Control

13 Chapter 13: Solids Handling and Biosolids

13.1 Sludge Thickening, Conditioning & Dewatering Technologies 13.2 Anaerobic and Aerobic Digestion Operations & Control 13.3 Biosolids Quality, Land Application Rules & OAR 340-050 / 40 CFR 503

14 Chapter 14: Wastewater Collection Systems and Pumping

14.1 Gravity Sewer Design, Manholes & Inflow/Infiltration (I/I) Management 14.2 Lift Station Design, Wet Wells & Submersible / Centrifugal Pumps 14.3 Collection System Maintenance, Pipeline Inspection (CCTV) & Trench Safety

15 Chapter 15: Collection System Rehabilitation and Overflow Control

15.1 Sewer Rehabilitation, Trenchless Renewal and New-Pipe Acceptance Testing 15.2 Overflow Response, Bypass Pumping, CMOM Programs and Sewer Sulfide Control

16 Chapter 16: Laboratory Procedures and Water Quality Testing

16.1 Drinking Water Microbiological Testing: Coliform, E. coli & RTCR 16.2 Wastewater Lab Analysis: BOD5, TSS, COD & Volatile Solids 16.3 Wastewater Lab: Nutrients, Alkalinity, Bacteria, Toxicity Testing and Lab Accreditation 16.4 Process Monitoring: pH, Turbidity, Dissolved Oxygen & Chlorine Residuals 16.5 Sampling Protocols, Quality Assurance / Chain of Custody & Reporting

17 Chapter 17: Equipment, Electrical Systems and Maintenance

17.1 Pumps, Blowers and Mechanical Maintenance Programs 17.2 Electrical Systems, Motors, Generators, Instrumentation and SCADA

18 Chapter 18: Applied Water and Wastewater Mathematics

18.1 Dimensional Analysis, Flow Conversions & Detention Time 18.2 Chemical Feed, Dosage Calculations & the Pounds Formula 18.3 Treatment Plant Hydraulics, Loading Rates (SOR, WOR) & Pumping Horsepower

19 Chapter 19: Utility Safety

19.1 OSHA Standards, Confined Space Entry & Hazardous Chemical Safety 19.2 Field Safety: Electrical Hazards, Fall Protection, Work Zones, PPE and Oregon OSHA Rules

20 Chapter 20: Emergency Preparedness, Security and Utility Management

20.1 Cascadia Subduction Zone (CSZ) Seismic Preparedness & Infrastructure Hardening 20.2 Wildfire Impacts on Watersheds, Post-Fire Water Quality & Emergency Operations 20.3 Security, Cybersecurity, Emergency Response Planning and Utility Management

11.3 Biological Nutrient Removal: Nitrification, Denitrification & Phosphorus Removal

Key Takeaways Explain This Topic AI

Biological nitrification is an obligate aerobic, autotrophic process where Nitrosomonas and Nitrobacter convert ammonia (NH4+) to nitrate (NO3-), consuming 4.57 lbs of O2 and 7.14 lbs of alkalinity as CaCO3 per lb of NH3-N oxidized.

Biological denitrification is a facultative heterotrophic anoxic process that reduces nitrate to inert nitrogen gas (N2), recovering 3.57 lbs of alkalinity and saving 2.86 lbs of O2 equivalent per lb of NO3-N reduced.

The Modified Ludzack-Ettinger (MLE) process uses an internal nitrate recycle stream (200–400% of influent flow) from the aerobic zone to a pre-anoxic basin, utilizing raw wastewater BOD as the electron donor.

Enhanced Biological Phosphorus Removal (EBPR) relies on Phosphorus Accumulating Organisms (PAOs) cycled through an anaerobic selector (VFA uptake and orthophosphate release) into an aerobic zone (luxury polyphosphate uptake), with permanent removal via Waste Activated Sludge (WAS).

Chemical phosphorus removal uses metal salts (alum or ferric chloride) to precipitate insoluble metal phosphates, producing an additional 4–5 lbs of chemical sludge per lb of phosphorus removed while consuming alkalinity.

Last updated: October 2026

4.4 Biological Nutrient Removal: Nitrification, Denitrification & Phosphorus Removal

Note

Excess discharges of nitrogen and phosphorus drive cultural eutrophication in receiving surface waters, stimulating harmful algal blooms, nocturnal dissolved oxygen crashes, and fish kills. In Oregon, strict Total Maximum Daily Loads (TMDLs)—such as those governing the Willamette River, Tualatin River, and Klamath River basins—require municipal utilities to master both biological and chemical nutrient removal mechanisms.

Environmental & Regulatory Drivers in Oregon

Ammonia Toxicity to Salmonids: Total ammonia exists in aqueous equilibrium between un-ionized ammonia ( NH 3 \text{NH}_3 NH 3 ​ ) and ammonium ions ( NH 4 + \text{NH}_4^+ NH 4 + ​ ):

NH 4 + + OH − ⇌ NH 3 + H 2 O \text{NH}_4^+ + \text{OH}^- \rightleftharpoons \text{NH}_3 + \text{H}_2\text{O} NH 4 + ​ + OH − ⇌ NH 3 ​ + H 2 ​ O

Un-ionized ammonia ( NH 3 \text{NH}_3 NH 3 ​ ) is an uncharged lipid-soluble gas that easily penetrates gill membranes of migrating Pacific salmon and steelhead, causing severe neurotoxicity, gill tissue damage, and mortality. As water temperature and pH rise, the equilibrium shifts dramatically toward toxic NH 3 \text{NH}_3 NH 3 ​ . Consequently, Oregon DEQ NPDES permits enforce stringent seasonal ammonia limits (often < 1.0 − 2.0 mg/L < 1.0-2.0 \text{ mg/L} < 1.0 − 2.0 mg/L as N during low-flow summer months).

Eutrophication & Hypoxia: Bioavailable nitrogen and phosphorus stimulate explosive blooms of algae and macrophytes. When these algal mats die, bacterial decay exerts an immense oxygen demand, driving dissolved oxygen below Oregon's criteria (for example 8.0 mg/L for cold-water aquatic life and 11.0 mg/L during salmonid spawning).

Biological Nitrification: Biochemistry & Stoichiometry

Nitrification is a two-step biological oxidation performed by obligate aerobic, chemolithoautotrophic bacteria that utilize inorganic carbon (carbon dioxide and bicarbonate) for cellular synthesis: +-----------------------------------------------------------------------------+

  • | TWO-STEP BIOLOGICAL NITRIFICATION |
  • +-----------------------------------------------------------------------------+
  • | AMMONIUM (NH4+) |
  • | | |
  • | | Nitrosomonas bacteria (Ammonia-Oxidizing Bacteria - AOB) |
  • | | Consumes 3.43 lbs O2 / lb NH3-N |
  • | v Releases H+ ions (consumes alkalinity) |
  • | NITRITE (NO2-) |
  • | | |
  • | | Nitrobacter bacteria (Nitrite-Oxidizing Bacteria - NOB) |
  • | | Consumes 1.14 lbs O2 / lb NH3-N |
  • | v |
  • | NITRATE (NO3-) |
  • +-----------------------------------------------------------------------------+
  • 1. Biochemical Reactions

Step 1: Ammonia Oxidation to Nitrite (by Nitrosomonas ):

2 NH 4 + + 3 O 2 → 2 NO 2 − + 4 H + + 2 H 2 O + Energy 2\text{NH}_4^+ + 3\text{O}_2 \rightarrow 2\text{NO}_2^- + 4\text{H}^+ + 2\text{H}_2\text{O} + \text{Energy} 2 NH 4 + ​ + 3 O 2 ​ → 2 NO 2 − ​ + 4 H + + 2 H 2 ​ O + Energy

Step 2: Nitrite Oxidation to Nitrate (by Nitrobacter ):

2 NO 2 − + O 2 → 2 NO 3 − + Energy 2\text{NO}_2^- + \text{O}_2 \rightarrow 2\text{NO}_3^- + \text{Energy} 2 NO 2 − ​ + O 2 ​ → 2 NO 3 − ​ + Energy

Overall Combined Nitrification Reaction:

NH 4 + + 2 O 2 → NO 3 − + 2 H + + H 2 O \text{NH}_4^+ + 2\text{O}_2 \rightarrow \text{NO}_3^- + 2\text{H}^+ + \text{H}_2\text{O} NH 4 + ​ + 2 O 2 ​ → NO 3 − ​ + 2 H + + H 2 ​ O

2. Foundational Stoichiometric Constants

Every wastewater operator must know these theoretical constants for exam calculations and plant control:

Oxygen Demand: 4.57 lbs O 2 4.57 \text{ lbs } \text{O}_2 4.57 lbs O 2 ​ are consumed per pound of ammonia nitrogen ( NH 3 -N \text{NH}_3\text{-N} NH 3 ​ -N ) oxidized to nitrate ( 3.43 lbs O 2 3.43 \text{ lbs } \text{O}_2 3.43 lbs O 2 ​ by Nitrosomonas and 1.14 lbs O 2 1.14 \text{ lbs } \text{O}_2 1.14 lbs O 2 ​ by Nitrobacter ). Including cellular biomass synthesis, actual field demand ranges from 4.2 to 4.6 lbs O 2 / lb NH 3 -N 4.2 \text{ to } 4.6 \text{ lbs } \text{O}_2 / \text{lb } \text{NH}_3\text{-N} 4.2 to 4.6 lbs O 2 ​ / lb NH 3 ​ -N .

Alkalinity Destruction: 7.14 lbs of alkalinity as CaCO 3 7.14 \text{ lbs of alkalinity as } \text{CaCO}_3 7.14 lbs of alkalinity as CaCO 3 ​ are destroyed per pound of NH 3 -N \text{NH}_3\text{-N} NH 3 ​ -N oxidized. This occurs because the reaction produces two moles of hydrogen ions ( 2 H + 2\text{H}^+ 2 H + ) for every mole of ammonium oxidized, neutralizing bicarbonate alkalinity ( HCO 3 − \text{HCO}_3^- HCO 3 − ​ ):

H + + HCO 3 − → H 2 O + CO 2 ↑ \text{H}^+ + \text{HCO}_3^- \rightarrow \text{H}_2\text{O} + \text{CO}_2\uparrow H + + HCO 3 − ​ → H 2 ​ O + CO 2 ​ ↑

3. Critical Environmental & Kinetic Parameters

Dissolved Oxygen (DO): Nitrifiers have a much lower oxygen affinity than heterotrophs. Aeration basin DO must be maintained at ≥ 2.0 mg/L \ge 2.0 \text{ mg/L} ≥ 2.0 mg/L ( 2.0 to 3.0 mg/L 2.0 \text{ to } 3.0 \text{ mg/L} 2.0 to 3.0 mg/L ). If DO drops below 1.0 mg/L 1.0 \text{ mg/L} 1.0 mg/L , nitrification slows significantly; below 0.5 mg/L 0.5 \text{ mg/L} 0.5 mg/L , it ceases.

pH Range: Optimum nitrification occurs between pH 7.5 and 8.5 7.5 \text{ and } 8.5 7.5 and 8.5 . Nitrification kinetics decline steeply below pH 7.0 7.0 7.0 ; at pH < 6.5 < 6.5 < 6.5 , rates drop by 75 % 75\% 75% ; below pH 6.0 6.0 6.0 , nitrification halts completely. In Pacific Northwest surface-water-fed collection systems with naturally low raw alkalinity ( 20 − 50 mg/L 20-50 \text{ mg/L} 20 − 50 mg/L ), utilities must feed supplemental alkalinity (caustic soda NaOH \text{NaOH} NaOH , soda ash Na 2 CO 3 \text{Na}_2\text{CO}_3 Na 2 ​ CO 3 ​ , or lime Ca(OH) 2 \text{Ca(OH)}_2 Ca(OH) 2 ​ ) to maintain a residual aeration alkalinity > 50 − 80 mg/L as CaCO 3 > 50-80 \text{ mg/L as } \text{CaCO}_3 > 50 − 80 mg/L as CaCO 3 ​ .

Temperature Sensitivity ( Q 10 Q_{10} Q 10 ​ Effect): Nitrifiers reproduce very slowly. Their growth rate is highly sensitive to water temperature. When temperature drops from 20 ∘ C 20^\circ\text{C} 2 0 ∘ C to 10 ∘ C 10^\circ\text{C} 1 0 ∘ C , the minimum MCRT required to prevent nitrifier washout doubles or triples (e.g., from 5 days 5 \text{ days} 5 days in summer to 12 − 18 days 12-18 \text{ days} 12 − 18 days in Pacific Northwest winters).

Biological Denitrification: Anoxic Reduction

Biological denitrification is the biological conversion of oxidized nitrogen (nitrate NO 3 − \text{NO}_3^- NO 3 − ​ and nitrite NO 2 − \text{NO}_2^- NO 2 − ​ ) into inert dinitrogen gas ( N 2 \text{N}_2 N 2 ​ ), which safely vents to the atmosphere.

1. Microbial Ecology & Anoxic Conditions

Denitrification is carried out by facultative heterotrophic bacteria ( Pseudomonas , Paracoccus , Alcaligenes ). These organisms are ordinary heterotrophs that utilize organic carbon for energy and growth. In an anoxic environment —defined as a zone where dissolved oxygen is absent ( D O < 0.2 mg/L DO < 0.2 \text{ mg/L} D O < 0.2 mg/L ) but chemically bound oxygen in the form of nitrate ( NO 3 − \text{NO}_3^- NO 3 − ​ ) is present—these bacteria substitute nitrate for molecular oxygen as their terminal respiratory electron acceptor:

NO 3 − → NO 2 − → NO ↑ → N 2 O ↑ → N 2 ↑ \text{NO}_3^- \rightarrow \text{NO}_2^- \rightarrow \text{NO}\uparrow \rightarrow \text{N}_2\text{O}\uparrow \rightarrow \text{N}_2\uparrow NO 3 − ​ → NO 2 − ​ → NO ↑→ N 2 ​ O ↑→ N 2 ​ ↑

Important

If dissolved oxygen is introduced into an anoxic zone (via excessive mixed liquor recycle or high surface turbulence), the bacteria will preferentially utilize the dissolved oxygen rather than nitrate, shutting down the denitrification pathway.

2. Carbon Source Requirements

Denitrifiers require an electron donor (biodegradable organic carbon) to reduce nitrate:

Raw Wastewater BOD (Pre-Anoxic): Readily biodegradable soluble COD (rbCOD) present in raw influent wastewater. Highly economical as it requires no purchased chemical carbon.

External Carbon Feed (Post-Anoxic): When an anoxic tank is situated downstream of the aerobic zone (where influent BOD has already been consumed), an external carbon source must be injected. Common electron donors include methanol ( CH 3 OH \text{CH}_3\text{OH} CH 3 ​ OH ) , sodium acetate , or micro-blended glycerin :

6 NO 3 − + 5 CH 3 OH → 3 N 2 ↑ + 5 CO 2 + 7 H 2 O + 6 OH − 6\text{NO}_3^- + 5\text{CH}_3\text{OH} \rightarrow 3\text{N}_2\uparrow + 5\text{CO}_2 + 7\text{H}_2\text{O} + 6\text{OH}^- 6 NO 3 − ​ + 5 CH 3 ​ OH → 3 N 2 ​ ↑ + 5 CO 2 ​ + 7 H 2 ​ O + 6 OH −

3. Stoichiometric Credits of Denitrification

Denitrification partially offsets the intense resource demands of nitrification:

Alkalinity Recovery: Recovers 3.57 lbs of alkalinity as CaCO 3 3.57 \text{ lbs of alkalinity as } \text{CaCO}_3 3.57 lbs of alkalinity as CaCO 3 ​ per pound of nitrate nitrogen ( NO 3 -N \text{NO}_3\text{-N} NO 3 ​ -N ) reduced. This represents exactly 50 % 50\% 50% of the alkalinity destroyed during nitrification.

Oxygen Credit (Energy Savings): Heterotrophs utilize the chemically bound oxygen in nitrate to oxidize organic carbon, crediting/saving 2.86 lbs of O 2 2.86 \text{ lbs of } \text{O}_2 2.86 lbs of O 2 ​ equivalent per pound of NO 3 -N \text{NO}_3\text{-N} NO 3 ​ -N reduced. This reduces mechanical blower electrical power requirements by 15 − 25 % 15-25\% 15 − 25% .

Nitrogen Removal Process Configurations +-----------------------------------------------------------------------------+

  • | MODIFIED LUDZACK-ETTINGER (MLE) PROCESS |
  • +-----------------------------------------------------------------------------+
  • | Internal Nitrate Recycle (MLR) |
  • | +---------------------------------------+ |
  • | | (200% - 400% Q) | |
  • | v | |
  • | Raw Influent -->[ Anoxic ]----->[ Aerobic ]------+--> Secondary |
  • | Wastewater [ Zone ] [ Nitrification ] Clarifier |
  • | [ DO<0.2 ] [ DO > 2.0 ] | |
  • | ^ | |
  • | | RAS | |
  • | +--------------------------------------------+ |
  • +-----------------------------------------------------------------------------+
  • 1. Modified Ludzack-Ettinger (MLE) Process

The MLE process is the industry standard for biological nitrogen removal:

Basin Layout: A pre-anoxic tank is placed directly upstream of the aerobic nitrification tank .

Internal Nitrate Recycle (MLR / NRCY): High-capacity axial flow pumps recycle nitrate-rich mixed liquor from the discharge end of the aerobic basin back to the pre-anoxic tank at 200 % to 400 % 200\% \text{ to } 400\% 200% to 400% of influent flow ( 2 Q to 4 Q 2Q \text{ to } 4Q 2 Q to 4 Q ) .

Operational Advantage: The incoming raw wastewater BOD provides the free organic carbon needed for denitrification in the pre-anoxic zone, eliminating external carbon chemical costs while recovering 50 % 50\% 50% of lost alkalinity before the water reaches the aerobic zone.

2. 4-Stage Bardenpho Process

Designed to achieve ultra-low Total Nitrogen ( < 3.0 mg/L < 3.0 \text{ mg/L} < 3.0 mg/L ):

Primary Anoxic Zone: Receives raw influent and internal recycle ( 200 − 400 % Q 200-400\% Q 200 − 400% Q ); achieves 70 − 80 % 70-80\% 70 − 80% nitrate removal using influent carbon.

Primary Aerobic Zone: Completes BOD oxidation and nitrifies ammonia to nitrate.

Secondary (Post) Anoxic Zone: Denitrifies residual nitrate escaping the first stage via endogenous microbial respiration or supplemental external carbon feed (methanol/acetate).

Re-Aeration Zone: A short ( 15 − 30 minute 15-30 \text{ minute} 15 − 30 minute ) aerobic stage that strips entrained nitrogen gas, adds dissolved oxygen (commonly to about 2 mg/L) and prevents septic or rising sludge in the secondary clarifier.

Phosphorus Removal Mechanisms

Phosphorus exists in wastewater as orthophosphate ( PO 4 3 − \text{PO}_4^{3-} PO 4 3 − ​ ), polyphosphates, and organically bound phosphorus. It cannot be converted into an inert gas; it can only be removed from wastewater by physically incorporating it into a solid phase and wasting it out in the sludge.

1. Enhanced Biological Phosphorus Removal (EBPR)

EBPR employs specialized bacteria known as Phosphorus Accumulating Organisms (PAOs) , such as Candidatus Accumulibacter phosphatis, cycled through alternating anaerobic and aerobic zones: +-----------------------------------------------------------------------------+

  • | EBPR BIOCHEMICAL CYCLE |
  • +-------------------------------------+---------------------------------------+
  • | ANAEROBIC SELECTOR | AEROBIC ZONE |
  • | - ZERO Dissolved Oxygen | - Dissolved Oxygen > 2.0 mg/L |
  • | - ZERO Nitrate (NO3-) | - PAOs oxidize stored PHAs |
  • | - PAOs take up VFAs (Acetate) | - "LUXURY PHOSPHATE UPTAKE" |
  • | - Store VFAs as intracellular PHA | - Intracellular Poly-P storage |
  • | - Polyphosphate bonds cleaved | - Soluble ortho-P drops < 0.1 mg/L |
  • | - "ORTHOPHOSPHATE RELEASE" | - Permanent P removal via WAS wasting|
  • +-------------------------------------+---------------------------------------+

Anaerobic Selector Zone (True Anaerobic: No DO, No NO 3 − \text{NO}_3^- NO 3 − ​ ):

Under fermentation conditions, non-PAO heterotrophs convert raw BOD into Volatile Fatty Acids (VFAs) , predominantly acetic acid and propionic acid.

PAOs absorb these VFAs and store them internally as carbon reserves called polyhydroxyalkanoates (PHAs) .

To power this rapid VFA transport and storage without oxygen, PAOs break the high-energy bonds of their internal polyphosphate chains, discharging free orthophosphate into the bulk liquid ( orthophosphate release ). Liquid phosphorus concentrations in this zone can spike to 20 − 40 mg/L 20-40 \text{ mg/L} 20 − 40 mg/L .

Aerobic Zone:

Entering the aerated basin, PAOs oxidize their stored internal PHAs for cellular energy and growth.

Using this energy, PAOs absorb dissolved orthophosphate from the water column in massive excess of normal biological nutritional requirements—a phenomenon known as luxury uptake .

PAOs re-synthesize intracellular polyphosphate granules, driving soluble orthophosphate in the bulk liquid down to < 0.1 − 0.5 mg/L < 0.1-0.5 \text{ mg/L} < 0.1 − 0.5 mg/L .

Sludge Wasting (WAS):

Phosphorus is permanently purged from the system solely by wasting PAO-rich Waste Activated Sludge (WAS) .

Operational Warning: If P-rich WAS is allowed to sit in an anaerobic gravity thickener or non-aerated holding tank, the PAOs will experience anaerobic stress and re-release all stored orthophosphate back into the liquid phase, returning concentrated phosphorus to the plant headworks in the decant stream.

2. Common Biological Phosphorus Removal Process Configurations

A/O (Anaerobic / Oxic): Mainstream anaerobic selector followed by aerobic basin. Used strictly for phosphorus removal where nitrification is not required.

A2O (Anaerobic / Anoxic / Oxic): Incorporates an anoxic zone between the anaerobic and aerobic basins with internal nitrate recycle. Protects the anaerobic zone from nitrate contamination while achieving simultaneous nitrogen and phosphorus removal.

University of Cape Town (UCT) Process: In high-nitrate systems, RAS contains substantial nitrate that would destroy anaerobic conditions if returned directly to the anaerobic selector. The UCT process routes RAS to the anoxic zone first to reduce nitrate, then recycles anoxic mixed liquor to the anaerobic selector.

3. Chemical Phosphorus Precipitation

When wastewater lacks sufficient influent VFAs for EBPR, or when permit limits require effluent Total Phosphorus < 0.05 − 0.10 mg/L < 0.05-0.10 \text{ mg/L} < 0.05 − 0.10 mg/L , chemical precipitation using trivalent metal salts is required:

Precipitation Reactions:

Aluminum Sulfate (Alum):

Al 2 ( SO 4 ) 3 ⋅ 14 H 2 O + 2 PO 4 3 − → 2 AlPO 4 ↓ + 3 SO 4 2 − + 14 H 2 O \text{Al}_2(\text{SO}_4)_3 \cdot 14\text{H}_2\text{O} + 2\text{PO}_4^{3-} \rightarrow 2\text{AlPO}_4\downarrow + 3\text{SO}_4^{2-} + 14\text{H}_2\text{O} Al 2 ​ ( SO 4 ​ ) 3 ​ ⋅ 14 H 2 ​ O + 2 PO 4 3 − ​ → 2 AlPO 4 ​ ↓ + 3 SO 4 2 − ​ + 14 H 2 ​ O

Ferric Chloride:

FeCl 3 + PO 4 3 − → FePO 4 ↓ + 3 Cl − \text{FeCl}_3 + \text{PO}_4^{3-} \rightarrow \text{FePO}_4\downarrow + 3\text{Cl}^- FeCl 3 ​ + PO 4 3 − ​ → FePO 4 ​ ↓ + 3 Cl −

Molar Dosing Requirements: Stoichiometrically, one mole of aluminum or iron precipitates one mole of orthophosphate ( 1 : 1 molar ratio 1:1 \text{ molar ratio} 1 : 1 molar ratio ). However, because hydroxide ions ( OH − \text{OH}^- OH − ) compete aggressively for metal cations to form metal hydroxides ( Al(OH) 3 \text{Al(OH)}_3 Al(OH) 3 ​ or Fe(OH) 3 \text{Fe(OH)}_3 Fe(OH) 3 ​ ), actual plant dosage requires a molar ratio of 1.5 : 1 to 2.5 : 1 metal-to-phosphorus 1.5:1 \text{ to } 2.5:1 \text{ metal-to-phosphorus} 1.5 : 1 to 2.5 : 1 metal-to-phosphorus .

Chemical Sludge Production: Coagulant addition generates substantial chemical precipitate, adding 4.0 to 5.0 lbs of dry chemical sludge 4.0 \text{ to } 5.0 \text{ lbs of dry chemical sludge} 4.0 to 5.0 lbs of dry chemical sludge for every pound of phosphorus removed. It also consumes alkalinity and depresses basin pH.