9.1 Storage Tank and Booster Pump Station Operation, Inspection and Disinfection

Oregon Water and Wastewater Operator Certification Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Oregon Operator Programs and DEQ Wastewater Certification

1.1 Dual-Agency Structure: DEQ Wastewater and OHA Drinking Water Programs 1.2 DEQ Wastewater System Classification and Supervision Rules 1.3 DEQ Certificates: Qualifications, OIT, Provisional Path, Exams and Fees

2 Chapter 2: OHA Drinking Water Certification and Certificate Renewal

2.1 OHA System Classification, Direct Responsible Charge and the Filtration Endorsement 2.2 OHA Certificates: Experience Tables, OIT, Exams, Fees and Small Water System Certification 2.3 Renewal, CEUs, Reinstatement, Reciprocity and Discipline for DEQ and OHA Certificates

3 Chapter 3: Federal Rules, Oregon Water Quality Standards and Cyanotoxins

3.1 Clean Water Act, Safe Drinking Water Act & NPDES Permitting 3.2 Willamette Basin TMDL and Oregon Water Quality Standards 3.3 Harmful Algal Blooms (HABs) & Oregon Cyanotoxin Rules (OAR 333-061-0510)

4 Chapter 4: Source Water, Intakes and Wells

4.1 Raw Water Sources, Intake Structures & Pretreatment 4.2 Groundwater Sources and Wells: Hydraulics, Construction and Protection

5 Chapter 5: Coagulation, Clarification and Filtration

5.1 Coagulation, Flocculation & Jar Testing Dynamics 5.2 Sedimentation, Clarification & Media Filtration Systems 5.3 Slow Sand, Diatomaceous Earth, Cartridge and Membrane Filtration

6 Chapter 6: Drinking Water Disinfection

6.1 Disinfection Chemistry, Chlorination Dynamics & CT Calculations 6.2 UV, Ozone, Chlorine Dioxide, Chloramines and Disinfection Byproduct Control

7 Chapter 7: Specialty Water Treatment and Residuals

7.1 Iron and Manganese Removal, Softening, and Taste and Odor Control 7.2 Corrosion Control, Lead and Copper, and Fluoridation 7.3 Water Treatment Residuals: Sludge, Backwash Water and Membrane Concentrate

8 Chapter 8: Distribution System Infrastructure

8.1 Distribution System Hydraulics, Piping Materials & Storage Facilities 8.2 Valves, Fire Hydrants & Water Main Installation / Disinfection 8.3 Service Connections, Meters, Water Loss Control and Utility Locating

9 Chapter 9: Distribution Operations, Cross-Connection Control and Water Quality

9.1 Storage Tank and Booster Pump Station Operation, Inspection and Disinfection 9.2 Cross-Connection Control & Backflow Prevention Assemblies (OAR 333-061-0070) 9.3 Water Quality in Distribution: Water Age, Nitrification & Flushing Programs

10 Chapter 10: Wastewater Preliminary and Primary Treatment and Lagoons

10.1 Preliminary Treatment: Screening, Grit Removal & Flow Measurement 10.2 Primary Clarification & Sedimentation Hydraulics 10.3 Stabilization Ponds and Aerated Lagoons

11 Chapter 11: Biological Wastewater Treatment

11.1 Secondary Treatment: Activated Sludge Process Control & Variations 11.2 Fixed-Film Treatment: Trickling Filters, RBCs, MBBR and IFAS 11.3 Biological Nutrient Removal: Nitrification, Denitrification & Phosphorus Removal

12 Chapter 12: Tertiary Treatment, Disinfection, Recycled Water and Small Systems

12.1 Tertiary Filtration, Membrane Bioreactors and Oregon Recycled Water Classes 12.2 Wastewater Disinfection and Dechlorination 12.3 Small Wastewater Systems, Septage Handling and Odor Control

13 Chapter 13: Solids Handling and Biosolids

13.1 Sludge Thickening, Conditioning & Dewatering Technologies 13.2 Anaerobic and Aerobic Digestion Operations & Control 13.3 Biosolids Quality, Land Application Rules & OAR 340-050 / 40 CFR 503

14 Chapter 14: Wastewater Collection Systems and Pumping

14.1 Gravity Sewer Design, Manholes & Inflow/Infiltration (I/I) Management 14.2 Lift Station Design, Wet Wells & Submersible / Centrifugal Pumps 14.3 Collection System Maintenance, Pipeline Inspection (CCTV) & Trench Safety

15 Chapter 15: Collection System Rehabilitation and Overflow Control

15.1 Sewer Rehabilitation, Trenchless Renewal and New-Pipe Acceptance Testing 15.2 Overflow Response, Bypass Pumping, CMOM Programs and Sewer Sulfide Control

16 Chapter 16: Laboratory Procedures and Water Quality Testing

16.1 Drinking Water Microbiological Testing: Coliform, E. coli & RTCR 16.2 Wastewater Lab Analysis: BOD5, TSS, COD & Volatile Solids 16.3 Wastewater Lab: Nutrients, Alkalinity, Bacteria, Toxicity Testing and Lab Accreditation 16.4 Process Monitoring: pH, Turbidity, Dissolved Oxygen & Chlorine Residuals 16.5 Sampling Protocols, Quality Assurance / Chain of Custody & Reporting

17 Chapter 17: Equipment, Electrical Systems and Maintenance

17.1 Pumps, Blowers and Mechanical Maintenance Programs 17.2 Electrical Systems, Motors, Generators, Instrumentation and SCADA

18 Chapter 18: Applied Water and Wastewater Mathematics

18.1 Dimensional Analysis, Flow Conversions & Detention Time 18.2 Chemical Feed, Dosage Calculations & the Pounds Formula 18.3 Treatment Plant Hydraulics, Loading Rates (SOR, WOR) & Pumping Horsepower

19 Chapter 19: Utility Safety

19.1 OSHA Standards, Confined Space Entry & Hazardous Chemical Safety 19.2 Field Safety: Electrical Hazards, Fall Protection, Work Zones, PPE and Oregon OSHA Rules

20 Chapter 20: Emergency Preparedness, Security and Utility Management

20.1 Cascadia Subduction Zone (CSZ) Seismic Preparedness & Infrastructure Hardening 20.2 Wildfire Impacts on Watersheds, Post-Fire Water Quality & Emergency Operations 20.3 Security, Cybersecurity, Emergency Response Planning and Utility Management

9.1 Storage Tank and Booster Pump Station Operation, Inspection and Disinfection

Key Takeaways Explain This Topic AI

OHA treats an unsecured or leaky roof or hatch, an unscreened vent, or a drain or overflow without a flap valve or screen as a significant deficiency at storage facilities.

AWWA C652 tank disinfection options are 10 mg/L free chlorine held 6 or 24 hours, 50 mg/L held 6 hours, or a 200 mg/L spray of all wetted surfaces.

After routine maintenance, an Oregon reservoir may return to service before bacteriological results if the water leaving it has at least 0.4 mg/L free or 2.0 mg/L combined chlorine.

Divers in drinking water reservoirs must wear a full-body dry suit and hardhat with an external air supply and be sprayed with 200 mg/L chlorine solution.

Booster pumps taking suction from mains need a low-pressure cut-off set at no less than 20 psi, and pressure tanks must be rated at least 50 percent above maximum system pressure.

Last updated: October 2026

Why Storage Gets Special Attention

Reservoirs hold large volumes of finished water that is open to the outside world through vents, hatches, overflows and drains. Birds, rodents, insects and stormwater entering through a failed screen or hatch have caused waterborne outbreaks. That is why OAR 333-061-0076 lists these storage problems as significant deficiencies :

  • roof and access hatch not adequately secured;
  • roof and access hatch not watertight;
  • no flap valve, screen or equivalent over the drain and overflow; and

no screened vent.

Routine Inspection Checklist

  • Item What to look for
  • Hatches Locked, gasketed, curbed and watertight; intrusion alarms working
  • Vents Intact screens; downward-facing; no ice or debris blockage that could pull a vacuum

Overflow and drain Flap valve or screen in place; discharge through an air gap to a splash pad or ditch, never directly to a sewer or storm main

Exterior Coating failures, rust streaks, leaks, cracked concrete, ladder and fall-protection condition, vegetation and site security

  • Cathodic protection Rectifier output and pipe-to-water potential readings, on schedule
  • Water quality Disinfectant residual, temperature stratification, water age, sediment depth
  • Controls Level transmitter, altitude valve, high- and low-level alarms

Periodic interior inspections , every few years and more often for older tanks, use washouts or remotely operated vehicles. Divers can inspect while the tank stays in service, under strict sanitary rules. They check sediment, coating condition, corrosion, roof structure and inlet and outlet piping. AWWA M42 (steel tanks) and D100-series standards guide steel tank work, and coatings must be NSF/ANSI 61-certified.

Disinfecting Reservoirs (OAR 333-061-0050(10) and AWWA C652)

Method Procedure Before service

1 Fill the tank and hold a free chlorine residual of at least 10 mg/L for the required 6- or 24-hour period Drain, refill with potable water and collect a coliform sample

2 Fill the tank with a 50 mg/L solution and hold 6 hours Drain, refill and sample

3 Spray or brush a 200 mg/L solution on every surface that will contact water when full Fill without flushing, then sample

The tank goes into service when the coliform sample is negative. Oregon allows an exception after routine maintenance, inspection or repair : the reservoir may return to service before the lab report if the water leaving it has at least 0.4 mg/L free chlorine or 2.0 mg/L combined chlorine (OAR 333-061-0050(10)(h)).

Divers must wear a full-body dry suit with a hardhat and an external air supply. They are disinfected by spraying a 200 mg/L chlorine solution on every surface that will contact drinking water (OAR 333-061-0050(10)(i)).

Super-chlorinated water drained from a tank must be dechlorinated before it reaches a ditch, storm drain or stream.

Operating Storage for Quality and Reliability

Cycle levels. Daily drawdown and refill limit water age and stratification. Many utilities target turning over the volume every few days, balanced against fire and emergency reserves.

Mixing. Separate inlet and outlet locations, mixing nozzles or active mixers prevent short-circuiting and thermal layering.

Freeze protection. Ice can crush vents and hatches. Keep water moving and inspect after cold snaps.

Altitude valves close to prevent overflow when a tank fills from a higher pressure zone. A stuck valve causes overflow; a closed one starves the zone.

Booster Pump Stations

OHA's pumping facility standards (OAR 333-061-0050(7)) include:

Standard Reason

Take suction from tanks or reservoirs where possible Avoids pulling the suction main below atmospheric pressure

Pumps drawing from mains have a low-pressure cut-off on the suction side set at no less than 20 psi Keeps the upstream zone above 20 psi; missing cut-offs are a significant deficiency

Avoid suction lift; install pumps under positive head, or prime with water that meets MCLs Prevents loss of prime and contamination

  • Locate above the 100-year flood level and grade drainage away Protects electrical equipment
  • Durable, lockable, heated and lighted building with sloped floor drains Security and reliable operation

Hydropneumatic tanks in small systems are pressure tanks . They must be steel or another NSF/ANSI 61-certified material and designed for a pressure at least 50 percent greater than the maximum system pressure . They maintain pressure between pump cycles but provide almost no fire storage. Operators check the air-to-water balance (waterlogged tanks cause rapid pump cycling), the pressure switch settings, the relief valve and the sight glass.

Common Booster Station Problems

Short cycling : an undersized or waterlogged pressure tank, or switch differential set too close.

Low suction pressure : upstream demand or a closed valve; the cut-off trips the pumps.

Surges at pump start and stop : check valves slamming. Use soft starters, VFD ramps or surge-anticipating valves.

Overheating motors : blocked ventilation or failed thermostatic controls.

Security : unlocked doors and unmonitored intrusion alarms are both sanitary and safety risks.