6.2 UV, Ozone, Chlorine Dioxide, Chloramines and Disinfection Byproduct Control

Oregon Water and Wastewater Operator Certification Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Oregon Operator Programs and DEQ Wastewater Certification

1.1 Dual-Agency Structure: DEQ Wastewater and OHA Drinking Water Programs 1.2 DEQ Wastewater System Classification and Supervision Rules 1.3 DEQ Certificates: Qualifications, OIT, Provisional Path, Exams and Fees

2 Chapter 2: OHA Drinking Water Certification and Certificate Renewal

2.1 OHA System Classification, Direct Responsible Charge and the Filtration Endorsement 2.2 OHA Certificates: Experience Tables, OIT, Exams, Fees and Small Water System Certification 2.3 Renewal, CEUs, Reinstatement, Reciprocity and Discipline for DEQ and OHA Certificates

3 Chapter 3: Federal Rules, Oregon Water Quality Standards and Cyanotoxins

3.1 Clean Water Act, Safe Drinking Water Act & NPDES Permitting 3.2 Willamette Basin TMDL and Oregon Water Quality Standards 3.3 Harmful Algal Blooms (HABs) & Oregon Cyanotoxin Rules (OAR 333-061-0510)

4 Chapter 4: Source Water, Intakes and Wells

4.1 Raw Water Sources, Intake Structures & Pretreatment 4.2 Groundwater Sources and Wells: Hydraulics, Construction and Protection

5 Chapter 5: Coagulation, Clarification and Filtration

5.1 Coagulation, Flocculation & Jar Testing Dynamics 5.2 Sedimentation, Clarification & Media Filtration Systems 5.3 Slow Sand, Diatomaceous Earth, Cartridge and Membrane Filtration

6 Chapter 6: Drinking Water Disinfection

6.1 Disinfection Chemistry, Chlorination Dynamics & CT Calculations 6.2 UV, Ozone, Chlorine Dioxide, Chloramines and Disinfection Byproduct Control

7 Chapter 7: Specialty Water Treatment and Residuals

7.1 Iron and Manganese Removal, Softening, and Taste and Odor Control 7.2 Corrosion Control, Lead and Copper, and Fluoridation 7.3 Water Treatment Residuals: Sludge, Backwash Water and Membrane Concentrate

8 Chapter 8: Distribution System Infrastructure

8.1 Distribution System Hydraulics, Piping Materials & Storage Facilities 8.2 Valves, Fire Hydrants & Water Main Installation / Disinfection 8.3 Service Connections, Meters, Water Loss Control and Utility Locating

9 Chapter 9: Distribution Operations, Cross-Connection Control and Water Quality

9.1 Storage Tank and Booster Pump Station Operation, Inspection and Disinfection 9.2 Cross-Connection Control & Backflow Prevention Assemblies (OAR 333-061-0070) 9.3 Water Quality in Distribution: Water Age, Nitrification & Flushing Programs

10 Chapter 10: Wastewater Preliminary and Primary Treatment and Lagoons

10.1 Preliminary Treatment: Screening, Grit Removal & Flow Measurement 10.2 Primary Clarification & Sedimentation Hydraulics 10.3 Stabilization Ponds and Aerated Lagoons

11 Chapter 11: Biological Wastewater Treatment

11.1 Secondary Treatment: Activated Sludge Process Control & Variations 11.2 Fixed-Film Treatment: Trickling Filters, RBCs, MBBR and IFAS 11.3 Biological Nutrient Removal: Nitrification, Denitrification & Phosphorus Removal

12 Chapter 12: Tertiary Treatment, Disinfection, Recycled Water and Small Systems

12.1 Tertiary Filtration, Membrane Bioreactors and Oregon Recycled Water Classes 12.2 Wastewater Disinfection and Dechlorination 12.3 Small Wastewater Systems, Septage Handling and Odor Control

13 Chapter 13: Solids Handling and Biosolids

13.1 Sludge Thickening, Conditioning & Dewatering Technologies 13.2 Anaerobic and Aerobic Digestion Operations & Control 13.3 Biosolids Quality, Land Application Rules & OAR 340-050 / 40 CFR 503

14 Chapter 14: Wastewater Collection Systems and Pumping

14.1 Gravity Sewer Design, Manholes & Inflow/Infiltration (I/I) Management 14.2 Lift Station Design, Wet Wells & Submersible / Centrifugal Pumps 14.3 Collection System Maintenance, Pipeline Inspection (CCTV) & Trench Safety

15 Chapter 15: Collection System Rehabilitation and Overflow Control

15.1 Sewer Rehabilitation, Trenchless Renewal and New-Pipe Acceptance Testing 15.2 Overflow Response, Bypass Pumping, CMOM Programs and Sewer Sulfide Control

16 Chapter 16: Laboratory Procedures and Water Quality Testing

16.1 Drinking Water Microbiological Testing: Coliform, E. coli & RTCR 16.2 Wastewater Lab Analysis: BOD5, TSS, COD & Volatile Solids 16.3 Wastewater Lab: Nutrients, Alkalinity, Bacteria, Toxicity Testing and Lab Accreditation 16.4 Process Monitoring: pH, Turbidity, Dissolved Oxygen & Chlorine Residuals 16.5 Sampling Protocols, Quality Assurance / Chain of Custody & Reporting

17 Chapter 17: Equipment, Electrical Systems and Maintenance

17.1 Pumps, Blowers and Mechanical Maintenance Programs 17.2 Electrical Systems, Motors, Generators, Instrumentation and SCADA

18 Chapter 18: Applied Water and Wastewater Mathematics

18.1 Dimensional Analysis, Flow Conversions & Detention Time 18.2 Chemical Feed, Dosage Calculations & the Pounds Formula 18.3 Treatment Plant Hydraulics, Loading Rates (SOR, WOR) & Pumping Horsepower

19 Chapter 19: Utility Safety

19.1 OSHA Standards, Confined Space Entry & Hazardous Chemical Safety 19.2 Field Safety: Electrical Hazards, Fall Protection, Work Zones, PPE and Oregon OSHA Rules

20 Chapter 20: Emergency Preparedness, Security and Utility Management

20.1 Cascadia Subduction Zone (CSZ) Seismic Preparedness & Infrastructure Hardening 20.2 Wildfire Impacts on Watersheds, Post-Fire Water Quality & Emergency Operations 20.3 Security, Cybersecurity, Emergency Response Planning and Utility Management

6.2 UV, Ozone, Chlorine Dioxide, Chloramines and Disinfection Byproduct Control

Key Takeaways Explain This Topic AI

UV dose equals intensity times exposure time in mJ/sq cm; federal UV dose tables require 12 mJ/sq cm for 3-log Cryptosporidium, 11 for 3-log Giardia and 186 for 4-log virus.

Oregon UV installations need validated reactors, an intensity sensor with alarms, a flow-limiting device, and no bypass piping around the unit.

Ozone is the strongest common oxidant but leaves no residual; its byproduct bromate has an MCL of 0.010 mg/L, and chlorine dioxide is limited by a 0.8 mg/L MRDL and a 1.0 mg/L chlorite MCL.

Chloramines are formed at about 4.5-5 parts chlorine to 1 part ammonia-nitrogen and are used mainly to hold a stable distribution residual with fewer THMs.

DBP control starts with removing precursors through enhanced coagulation, then moves the chlorination point, lowers the dose, shortens water age, or switches the residual disinfectant.

Last updated: October 2026

Matching the Disinfectant to the Job

Disinfectant Strengths Limits Key regulatory numbers

Free chlorine Cheap, residual, strong against bacteria and viruses Weak against Cryptosporidium ; forms THMs and HAAs MRDL 4.0 mg/L as Cl2

UV light Excellent against Cryptosporidium and Giardia ; no DBPs No residual; needs high UV transmittance; viruses need high doses Dose tables in mJ/sq cm

Ozone Strongest oxidant; removes taste and odor; inactivates Crypto No residual; forms bromate; raises biodegradable organics Bromate MCL 0.010 mg/L

Chlorine dioxide Oxidizes iron, manganese and taste/odor; no THMs Forms chlorite and chlorate MRDL 0.8 mg/L; chlorite MCL 1.0 mg/L

Chloramines Long-lasting residual; far fewer THMs and HAAs Weak primary disinfectant; nitrification risk; harmful to dialysis patients and fish MRDL 4.0 mg/L as Cl2

Ultraviolet (UV) Disinfection

UV lamps emit light near 254 nm that damages microbial DNA so organisms cannot reproduce. UV dose (mJ/cm 2 ) = Intensity (mW/cm 2 ) × Exposure time (s) \text{UV dose (mJ/cm}^2\text{)} = \text{Intensity (mW/cm}^2\text{)} \times \text{Exposure time (s)} UV dose (mJ/cm 2 ) = Intensity (mW/cm 2 ) × Exposure time (s)

Required doses come from the federal UV dose table that OHA uses (OAR 333-061-0036, Table 32):

  • Log inactivation Cryptosporidium Giardia Virus
  • 2.0-log 5.8 5.2 100
  • 3.0-log 12 11 143
  • 4.0-log 22 22 186

Protozoa are easy to inactivate with UV, while viruses (especially adenovirus) need much higher doses. A UV-only groundwater system seeking 4-log virus credit needs a dose near 186 mJ/sq cm.

Oregon design and operating requirements (OAR 333-061-0050(5)(k)) include:

  • reactors validated for flow, intensity, UV transmittance and lamp status;
  • an upstream valve or device that keeps flow below the rated maximum;
  • a UV intensity sensor with visual and audible alarms and a visual check that every lamp is lit;
  • shut-off valves on the inlet and outlet, and no bypass piping ; and

lamp replacement on the manufacturer's schedule, with regular cleaning of sleeves and sensor windows.

Small groundwater units may need NSF/ANSI 55 Class A certification. Watch UV transmittance (UVT) : iron, manganese, organic color and turbidity absorb UV and lower the delivered dose.

Ozone

Ozone (O3) is generated on site by passing dry air or oxygen through a corona discharge. It is dissolved in contact chambers through fine-bubble diffusers or side-stream injection. Leftover gas must pass through an off-gas destruct unit because ozone is a toxic respiratory hazard.

Ozone oxidizes geosmin, MIB, iron, manganese and many organics, and inactivates Cryptosporidium with enough CT.

It leaves no residual , so chlorine or chloramine is still needed for distribution.

It oxidizes bromide to bromate (MCL 0.010 mg/L). It also breaks organics into biodegradable fragments, so ozone is often followed by biologically active filters to keep distribution water stable.

Chlorine Dioxide

Chlorine dioxide (ClO2) is generated on site, usually by reacting sodium chlorite with chlorine or acid. It does not form THMs or HAAs and works well for iron, manganese and taste-and-odor control.

MRDL : 0.8 mg/L.

Byproduct : chlorite (MCL 1.0 mg/L), with daily chlorite monitoring at the entrance to distribution. A ClO2 MRDL exceedance at the entry point can require Tier 1 public notice.

Generators must be tuned so unreacted chlorite stays low.

Chloramines

Chloramination adds ammonia to chlorinated water, usually after primary disinfection with free chlorine.

Target about 4.5 to 5 parts Cl2 to 1 part NH3-N by weight and pH above about 7.5 to favor monochloramine. Lower ratios leave free ammonia that feeds nitrifying bacteria; higher ratios move toward breakpoint and odorous dichloramine.

Oregon's groundwater design standard calls for at least 2.0 mg/L combined chlorine after 3 hours of contact when chloramine is the primary disinfectant (OAR 333-061-0050(5)(d)).

Customers need notice before conversion. Dialysis centers must remove chloramines, and aquarium and fish-pond owners must neutralize them.

Controlling Disinfection Byproducts

THMs and HAAs form when chlorine reacts with natural organic matter. Under Stage 2, compliance is a locational running annual average (LRAA) at each monitoring site (TTHM 0.080 mg/L, HAA5 0.060 mg/L), and operational evaluation levels warn of coming problems. Control tools, roughly in order:

Remove precursors. Conventional plants on surface water must practice enhanced coagulation under the Stage 1 rule. Required TOC removal depends on source TOC and alkalinity. For example, source TOC of 4-8 mg/L with alkalinity of 0-60 mg/L calls for 45 percent removal; TOC over 8 mg/L at that alkalinity calls for 50 percent .

Move the chlorination point downstream of clarification, so chlorine meets less organic carbon.

Lower dose and contact with precursors while still meeting CT.

Reduce water age through tank cycling, flushing and closing dead ends.

Switch the residual disinfectant to chloramines, or add GAC or tank aeration for THMs.