7.2 Corrosion Control, Lead and Copper, and Fluoridation

Oregon Water and Wastewater Operator Certification Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Oregon Operator Programs and DEQ Wastewater Certification

1.1 Dual-Agency Structure: DEQ Wastewater and OHA Drinking Water Programs 1.2 DEQ Wastewater System Classification and Supervision Rules 1.3 DEQ Certificates: Qualifications, OIT, Provisional Path, Exams and Fees

2 Chapter 2: OHA Drinking Water Certification and Certificate Renewal

2.1 OHA System Classification, Direct Responsible Charge and the Filtration Endorsement 2.2 OHA Certificates: Experience Tables, OIT, Exams, Fees and Small Water System Certification 2.3 Renewal, CEUs, Reinstatement, Reciprocity and Discipline for DEQ and OHA Certificates

3 Chapter 3: Federal Rules, Oregon Water Quality Standards and Cyanotoxins

3.1 Clean Water Act, Safe Drinking Water Act & NPDES Permitting 3.2 Willamette Basin TMDL and Oregon Water Quality Standards 3.3 Harmful Algal Blooms (HABs) & Oregon Cyanotoxin Rules (OAR 333-061-0510)

4 Chapter 4: Source Water, Intakes and Wells

4.1 Raw Water Sources, Intake Structures & Pretreatment 4.2 Groundwater Sources and Wells: Hydraulics, Construction and Protection

5 Chapter 5: Coagulation, Clarification and Filtration

5.1 Coagulation, Flocculation & Jar Testing Dynamics 5.2 Sedimentation, Clarification & Media Filtration Systems 5.3 Slow Sand, Diatomaceous Earth, Cartridge and Membrane Filtration

6 Chapter 6: Drinking Water Disinfection

6.1 Disinfection Chemistry, Chlorination Dynamics & CT Calculations 6.2 UV, Ozone, Chlorine Dioxide, Chloramines and Disinfection Byproduct Control

7 Chapter 7: Specialty Water Treatment and Residuals

7.1 Iron and Manganese Removal, Softening, and Taste and Odor Control 7.2 Corrosion Control, Lead and Copper, and Fluoridation 7.3 Water Treatment Residuals: Sludge, Backwash Water and Membrane Concentrate

8 Chapter 8: Distribution System Infrastructure

8.1 Distribution System Hydraulics, Piping Materials & Storage Facilities 8.2 Valves, Fire Hydrants & Water Main Installation / Disinfection 8.3 Service Connections, Meters, Water Loss Control and Utility Locating

9 Chapter 9: Distribution Operations, Cross-Connection Control and Water Quality

9.1 Storage Tank and Booster Pump Station Operation, Inspection and Disinfection 9.2 Cross-Connection Control & Backflow Prevention Assemblies (OAR 333-061-0070) 9.3 Water Quality in Distribution: Water Age, Nitrification & Flushing Programs

10 Chapter 10: Wastewater Preliminary and Primary Treatment and Lagoons

10.1 Preliminary Treatment: Screening, Grit Removal & Flow Measurement 10.2 Primary Clarification & Sedimentation Hydraulics 10.3 Stabilization Ponds and Aerated Lagoons

11 Chapter 11: Biological Wastewater Treatment

11.1 Secondary Treatment: Activated Sludge Process Control & Variations 11.2 Fixed-Film Treatment: Trickling Filters, RBCs, MBBR and IFAS 11.3 Biological Nutrient Removal: Nitrification, Denitrification & Phosphorus Removal

12 Chapter 12: Tertiary Treatment, Disinfection, Recycled Water and Small Systems

12.1 Tertiary Filtration, Membrane Bioreactors and Oregon Recycled Water Classes 12.2 Wastewater Disinfection and Dechlorination 12.3 Small Wastewater Systems, Septage Handling and Odor Control

13 Chapter 13: Solids Handling and Biosolids

13.1 Sludge Thickening, Conditioning & Dewatering Technologies 13.2 Anaerobic and Aerobic Digestion Operations & Control 13.3 Biosolids Quality, Land Application Rules & OAR 340-050 / 40 CFR 503

14 Chapter 14: Wastewater Collection Systems and Pumping

14.1 Gravity Sewer Design, Manholes & Inflow/Infiltration (I/I) Management 14.2 Lift Station Design, Wet Wells & Submersible / Centrifugal Pumps 14.3 Collection System Maintenance, Pipeline Inspection (CCTV) & Trench Safety

15 Chapter 15: Collection System Rehabilitation and Overflow Control

15.1 Sewer Rehabilitation, Trenchless Renewal and New-Pipe Acceptance Testing 15.2 Overflow Response, Bypass Pumping, CMOM Programs and Sewer Sulfide Control

16 Chapter 16: Laboratory Procedures and Water Quality Testing

16.1 Drinking Water Microbiological Testing: Coliform, E. coli & RTCR 16.2 Wastewater Lab Analysis: BOD5, TSS, COD & Volatile Solids 16.3 Wastewater Lab: Nutrients, Alkalinity, Bacteria, Toxicity Testing and Lab Accreditation 16.4 Process Monitoring: pH, Turbidity, Dissolved Oxygen & Chlorine Residuals 16.5 Sampling Protocols, Quality Assurance / Chain of Custody & Reporting

17 Chapter 17: Equipment, Electrical Systems and Maintenance

17.1 Pumps, Blowers and Mechanical Maintenance Programs 17.2 Electrical Systems, Motors, Generators, Instrumentation and SCADA

18 Chapter 18: Applied Water and Wastewater Mathematics

18.1 Dimensional Analysis, Flow Conversions & Detention Time 18.2 Chemical Feed, Dosage Calculations & the Pounds Formula 18.3 Treatment Plant Hydraulics, Loading Rates (SOR, WOR) & Pumping Horsepower

19 Chapter 19: Utility Safety

19.1 OSHA Standards, Confined Space Entry & Hazardous Chemical Safety 19.2 Field Safety: Electrical Hazards, Fall Protection, Work Zones, PPE and Oregon OSHA Rules

20 Chapter 20: Emergency Preparedness, Security and Utility Management

20.1 Cascadia Subduction Zone (CSZ) Seismic Preparedness & Infrastructure Hardening 20.2 Wildfire Impacts on Watersheds, Post-Fire Water Quality & Emergency Operations 20.3 Security, Cybersecurity, Emergency Response Planning and Utility Management

7.2 Corrosion Control, Lead and Copper, and Fluoridation

Key Takeaways Explain This Topic AI

A negative Langelier Saturation Index means water tends to dissolve calcium carbonate and is corrosive; a positive LSI means it tends to deposit scale.

Corrosion control treatment adjusts pH and alkalinity (caustic soda, soda ash, lime, CO2) or adds orthophosphate to form a protective scale on lead and copper.

The lead action level is 0.015 mg/L at the 90th percentile of tap samples, and copper is 1.3 mg/L; the Lead and Copper Rule Improvements lower the lead action level to 0.010 mg/L starting November 1, 2027.

The U.S. Public Health Service recommends 0.7 mg/L fluoride; the fluoride MCL is 4.0 mg/L, and Oregon systems must report on-site fluoride results above 4.0 mg/L within 48 hours.

Fluoride feed must be interlocked with plant flow and sized to prevent overfeed; a sodium fluoride saturator delivers about 18,000 mg/L fluoride ion.

Last updated: October 2026

Why Oregon Water Is Corrosive

Snowmelt- and rain-fed rivers draining Oregon's volcanic ranges often have alkalinity under 20 mg/L as CaCO3, pH near neutral and very low hardness. Water like that has little buffering capacity. Pipes, service lines and household plumbing slowly dissolve, releasing iron (red water), copper (blue-green stains) and, where present, lead. Corrosion also wastes chlorine and roughens pipes.

Corrosion Basics

Electrochemical cells : corrosion needs an anode (where metal dissolves), a cathode, an electrolyte (the water) and a connection. Joining dissimilar metals, such as copper and galvanized steel, creates a galvanic cell that speeds attack on the less noble metal.

Factors that increase corrosivity : low pH, low alkalinity and dissolved inorganic carbon, high dissolved oxygen, high chloride and sulfate relative to alkalinity, warm temperature, high velocity and stray electrical currents.

Indices : the Langelier Saturation Index (LSI) compares actual pH with the pH at which calcium carbonate is saturated (LSI = pH − pHs).

  • LSI Tendency
  • Negative Undersaturated; dissolves CaCO3 and is corrosive
  • About zero Balanced
  • Positive Supersaturated; tends to deposit scale

The Ryznar index and the marble test are related tools. Because corrosivity indices only describe calcium carbonate behavior, lead and copper control is verified by tap sampling and water quality parameters.

Corrosion Control Treatment

Approach Chemicals How it works Watch for

pH and alkalinity adjustment Caustic soda, soda ash, lime, sodium bicarbonate, CO2 Raises pH and buffering so metals dissolve less and pH stays stable in distribution Stable pH at the far ends of the system; calcium carbonate deposits if overdone

Orthophosphate inhibitor Phosphoric acid, zinc orthophosphate, blended phosphates Forms a protective lead or copper phosphate scale; commonly 1-3 mg/L as PO4 Steady residual system-wide; added phosphorus load at the wastewater plant

Silicates Sodium silicate Raises pH and forms a thin film Less common

Optimal corrosion control treatment (OCCT) is set with OHA after studies. Operators then hold the approved water quality parameters , such as entry-point pH, alkalinity and orthophosphate residual, within their ranges. Sudden changes in treatment (a new source, a switch to chloramines, or a new coagulant) can destabilize old pipe scales. OHA reviews these changes before they are made.

Lead and Copper Rule Requirements

Item Requirement

Lead action level (AL) 0.015 mg/L (15 µg/L) at the 90th percentile of first-draw tap samples, through October 31, 2027

  • Copper AL 1.3 mg/L at the 90th percentile
  • Sample sites Tiered; highest-risk homes with lead service lines or lead solder first

Exceeding the AL Not an MCL violation. It triggers corrosion control steps, water quality parameter monitoring, public education, source monitoring and lead service line work. A lead AL exceedance requires Tier 1 public notice within 24 hours under the 2021 revisions.

Service line inventory Initial inventory of every service line's material was due October 16, 2024 , with customer notification

Lead and Copper Rule Improvements (LCRI) Compliance date November 1, 2027 . Lead AL drops to 0.010 mg/L , sampling protocols change, and lead and galvanized-requiring-replacement service lines must generally be replaced by December 31, 2037 .

Oregon systems follow these federal requirements through OHA and OAR 333-061-0034 and -0036. Check OHA for adoption details and deadlines specific to your system.

Fluoridation

Fluoridation is a local decision in Oregon. There is no statewide mandate, and Portland, for example, does not fluoridate. Where systems do add fluoride:

Target : the U.S. Public Health Service recommends 0.7 mg/L .

Limits : MCL 4.0 mg/L (skeletal fluorosis); secondary MCL 2.0 mg/L (dental fluorosis).

Oregon reporting : on-site analyses are reported to OHA within 10 days after the end of the month, but results showing fluoride above 4.0 mg/L must be reported within 48 hours (OAR 333-061-0040).

Chemical Form Available fluoride

Fluorosilicic (hydrofluosilicic) acid, H2SiF6 Liquid, about 23-25% about 0.79 of the acid weight is fluoride (about 19% of the solution)

Sodium fluorosilicate, Na2SiF6 Powder about 61%

Sodium fluoride, NaF Powder or crystals, often in a saturator about 45%; a saturated solution holds about 18,000 mg/L fluoride ion

Safety and overfeed prevention : interlock the feed pump with plant flow so it cannot run when the plant stops, use a small day tank, and size the pump close to the needed rate. Acid fumes are corrosive, and powders need dust control and respirators. Verify the dose with daily analyses (SPADNS colorimetric or ion-selective electrode) and compare them with chemical used.

Worked saturator example

A 1.0 MGD well needs to rise from 0.1 to 0.7 mg/L fluoride using a sodium fluoride saturator.

  • Fluoride needed = 1.0 MGD × 0.6 mg/L × 8.34 = 5.0 lb/day
  • Saturator strength = 18,000 mg/L × 8.34 ÷ 1,000,000 = 0.150 lb fluoride per gallon
  • Feed rate = 5.0 ÷ 0.150 = about 33 gallons per day of saturated solution