13.1 Analog and Discrete Signal Types

NCEES PE Control Systems Engineering Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 Current Exam Facts 1.2 Handbook, ISA-5.1, and IEC 61511 on Exam Day 1.3 CBT Strategy, AITs, Calculators, and Pacing

2 Process Measurement Sensors

2.1 Pressure, Level, and Temperature Sensors 2.2 Flow, Counter, and Motion Sensors 2.3 Analytical Instruments and Sampling Systems

3 Specialty Sensors and Characteristics

3.1 Fire and Gas Detectors 3.2 Machinery Monitoring and Protection 3.3 Sensor Characteristics: Accuracy, Calibration, and Dynamics

4 Selection, Installation, and Primary Calculations

4.1 Sensor Selection and Material Compatibility 4.2 Sensor Installation Details and Drawings 4.3 Flow Calculations 4.4 Level Calculations

5 Conversions, Thermowells, and Checkout

5.1 Process Measurement Unit Conversions 5.2 Thermowell Design and Wake Frequency 5.3 Sensor Testing and Commissioning

6 Drawings, Dynamics, and PID

6.1 P&IDs, Loop Diagrams, and ISA-5.1 Symbology 6.2 Process Dynamics and Loop Response 6.3 Feedback Control and PID

7 Advanced, Discrete, and Process Applications

7.1 Feedforward, Cascade, Ratio, Override, and Split-Range 7.2 Discrete and Sequential Control 7.3 Control of Common Process Equipment

8 HMI, Alarms, Logic, and Architecture

8.1 HMI, Displays, and Control-Room Layout 8.2 Alarm Management 8.3 IEC 61131-3 Logic Implementation 8.4 DCS, PLC, SCADA Architecture and Interfaces

9 Capacity, Testing, and Cybersecurity

9.1 Capacity, Availability, Heat Load, Power, and Environment 9.2 FAT, IST, SAT, and Commissioning 9.3 Performance Monitoring and Management of Change 9.4 Control-System Cybersecurity

10 Valve Type, Trim, Sizing, and Actuators

10.1 Valve Types and Materials 10.2 Valve Trim, Leakage Class, and Characteristics 10.3 Valve Sizing, Pressure Drop, and Split-Range 10.4 Actuators and Failure Modes

11 Fluid Dynamics, Accessories, and Relief Types

11.1 Cavitation, Flashing, Choked Flow, and Noise 11.2 Valve Accessories and Installation 11.3 Pressure-Relieving Device Types and Installation 11.4 Pressure-Relieving Device Calculations

12 Motors, Solenoids, Regulators, and Checkout

12.1 Motor Starters, VSDs, and Soft Starters 12.2 Solenoid Valves and Relays as Final Elements 12.3 Self-Regulating Devices 12.4 Final Element Testing and Commissioning

13 Signal Types and Conversion

13.1 Analog and Discrete Signal Types 13.2 Buses, Topologies, and Digital Protocols 13.3 Signal Conversion, I/P, Splitters, and Bit Precision

14 Hazardous Areas, Power, and Circuits

14.1 Hazardous-Area Methods and Intrinsic Safety 14.2 Power, Grounding, Segregation, and EMI 14.3 Two-Wire, Four-Wire, and Loop Calculations

15 Media and Network Architecture

15.1 Transmission Media: Copper, Fiber, Wireless 15.2 TCP/IP, OPC, Addressing, and Architectures 15.3 OPC, Network Addressing, and Segmentation

16 Lifecycle and Risk Allocation

16.1 IEC 61511 Lifecycle Structure and Phases 16.2 Hazard and Risk Assessment 16.3 LOPA, IPLs, and SIF Identification

17 SRS, Design, and SIL Calculations

17.1 Safety Requirements Specification 17.2 SIS Design, Device Selection, and Constraints 17.3 SIL Calculations and Formulas

18 SAT, Proof Testing, and MOC

18.1 Installation, Commissioning, Validation, and SAT 18.2 Operation, Proof Testing, Demands, and Bypasses 18.3 Modification, Decommissioning, and MOC

13.1 Analog and Discrete Signal Types

Key Takeaways Explain This Topic AI

A 4–20 mA live zero encodes 0% of span at 4 mA and 100% at 20 mA; about 0 mA is an open or unpowered loop, not a valid zero process reading.

Process value scales on the 16 mA span: PV = LRV + (I − 4)/16 × (URV − LRV), so 12 mA is always 50% of a 4–20 mA calibration.

A 250 Ω burden converts 4–20 mA to 1–5 V; voltage signals then treat IR drop as measurement error, which is why current is used for long analog runs.

3–15 psi pneumatic is the live-zero air analog of 4–20 mA (3 psi = 0%, 15 psi = 100%, 9 psi = 50%); lost air goes toward 0 psig, not 0% process.

NAMUR NE43 fail bands (about ≤ 3.6 mA or ≥ 21 mA) are industry practice for smart analog transmitters, not an NCEES-supplied handbook table; do not confuse them with NAMUR proximity currents.

Last updated: August 2026

Why analog versus discrete is a Signals item

The PE Control Systems Signals domain is 11–17 questions . Specification 4.A opens with analog and discrete types because loop voltage budget, HART overlay, analog-input scaling, and discrete diagnostics all assume you can look at a milliamp, a volt, a psi, a millivolt, or a contact and know what a broken wire would do. Those signals usually terminate in a distributed control system (DCS) or programmable logic controller (PLC) analog or discrete input. Picking the wrong family is a failed design, not a unit-conversion slip.

Live zero: 4–20 mA, and why 0 mA is not 0%

A 4–20 mA current loop encodes 0% of calibrated span at 4 mA and 100% at 20 mA . The 4 mA floor is a live zero (elevated zero). Two reasons both show up on the exam:

Fault discrimination. An open pair, a dead supply, or a transmitter that has stopped conducting produces about 0 mA . That is a circuit failure, not a process sitting at lower range value. If the span started at 0 mA, a broken wire would look identical to a valid zero reading.

Two-wire power. A loop-powered transmitter must take operating current from the same pair that carries the signal. The 4 mA floor is the current the electronics are allowed to consume at 0% process; the remaining 16 mA is the modulation span.

Scale linearly on that 16 mA span. If I I I is loop current in milliamps, LRV is lower range value, and URV is upper range value: fraction of span = I − 4 20 − 4 = I − 4 16 \text{fraction of span} = \frac{I - 4}{20 - 4} = \frac{I - 4}{16} fraction of span = 20 − 4 I − 4 ​ = 16 I − 4 ​ PV = LRV + I − 4 16 ( URV − LRV ) \text{PV} = \text{LRV} + \frac{I - 4}{16}\,(\text{URV} - \text{LRV}) PV = LRV + 16 I − 4 ​ ( URV − LRV )

Worked example: 12 mA is 50%

A differential-pressure transmitter is calibrated 4–20 mA = 0–200 inH2O . The analog input reads 12.00 mA . 12 − 4 16 = 8 16 = 0.50 ⇒ PV = 0 + 0.50 × 200 = 100 inH2O \frac{12 - 4}{16} = \frac{8}{16} = 0.50 \quad \Rightarrow \quad \text{PV} = 0 + 0.50 \times 200 = 100\text{ inH2O} 16 12 − 4 ​ = 16 8 ​ = 0.50 ⇒ PV = 0 + 0.50 × 200 = 100 inH2O

12 mA is always 50% of a 4–20 mA span , regardless of engineering units. Check a second point: 7.2 mA is ( 7.2 − 4 ) / 16 = 0.20 (7.2 - 4)/16 = 0.20 ( 7.2 − 4 ) /16 = 0.20 , so the same 0–200 inH2O range reads 40 inH2O . The classic trap is treating 12 mA as 12 / 20 = 60 % 12/20 = 60\% 12/20 = 60% and reporting 120 inH2O — that ignores live zero.

The 1–5 V signal is the same live-zero idea after Ohm's law. A 250 Ω precision resistor (or analog-input burden) converts 4.00 mA → 1.00 V and 20.00 mA → 5.00 V . Voltage drop in the signal leads then appears as a reading error, which is why current — not voltage — is the long-run analog workhorse.

Other analog families

3–15 psi pneumatic is the live-zero air analog: 3 psig = 0% , 15 psig = 100% , span 12 psi . 9 psi is 50% . A failed air supply or a blown tube heads toward 0 psig , which is not 0% process. Pneumatic still appears on valve actuators, I/P (current-to-pneumatic) transducers, and electrically dead or intrinsically safe areas. Limits are compressibility lag, leaks, freeze-up of wet instrument air, and tubing volume — not induced millivolts.

Thermocouple millivolts are tens of millivolts. They need cold-junction compensation, shielded twisted pair, and usually a local transmitter if the run is long. Ground loops and electromagnetic interference swamp millivolts long before they swamp 4–20 mA.

A resistance temperature detector (RTD) (typically Pt100 = 100 Ω at 0 °C ) is a resistance, not a current. Lead-wire resistance is a direct temperature bias on 2-wire connections; 3-wire and 4-wire circuits cancel or measure the leads. An RTD does not “output 12 mA” unless a transmitter is already in the loop.

Pulse / frequency comes from turbine meters, positive-displacement meters, speed probes, and some flow computers. The information is in the count or frequency, not in an analog level. Debounce, pull-up, and the maximum frequency of the high-speed counter card matter. A 4–20 mA analog of the same flow is a different signal with a different error budget.

Discrete: dry contact and NAMUR proximity

A dry contact is a switch with no voltage of its own. The discrete-input card supplies wetting voltage ; the field device only closes or opens. Wetting current too low → oxidized contacts and missed closures. Leakage on a wet long cable → false ON. Polarity usually does not matter for a true dry contact, but it does matter if the “contact” is actually a solid-state output.

A NAMUR proximity sensor ( IEC 60947-5-6 ) is a 2-wire current-level discrete, typically powered at about 8.2 V through a switching amplifier. Conventional bands: ≤ about 1.2 mA with the target present (damped), ≥ about 2.1 mA with the target absent. About 0 mA is an open wire; a very high current is a short. That three-way diagnostic (off / on / cable fault) is why NAMUR sensors appear in safety and hazardous-area designs. Do not confuse NAMUR proximity currents with NAMUR NE43 analog-failure currents — different documents, different milliamps.

NAMUR NE43 analog failure currents (practice, not a supplied table)

NAMUR NE43 is a user-association recommendation for how a smart 4–20 mA transmitter should use currents outside 4–20 mA to declare a fault. Typical practice bands:

  • Current Usual meaning (NE43 practice)
  • 3.8–20.5 mA Valid measurement (3.8–4.0 mA and 20.0–20.5 mA are saturation, still “good”)
  • ≤ 3.6 mA Fail-low (downscale diagnostic)
  • ≥ 21.0 mA Fail-high (upscale diagnostic)
  • ~0 mA Open circuit or unpowered transmitter — not, by itself, a NE43 fail-low

NCEES does not hand you NE43 as a design-standard table on the Control Systems exam. Treat 3.6 mA / 21 mA as industry practice you should recognize, not as a lookup you can assume is in the electronic handbook. If an item gives the thresholds, use them. If it does not, reason from live zero ( 0 mA ≠ 0% ) rather than inventing a code clause.

Limitations that actually fail loops

Voltage drop. At 20 mA, every ohm of wire, barrier, isolator, and analog-input burden costs 0.020 V . The transmitter still needs its minimum terminal voltage. Design the loop at 20 mA , not at 4 mA.

Leakage. Parallel moisture or damaged insulation steals current around a transmitter or holds a dry-contact input ON.

Polarity. Two-wire transmitters, NAMUR amplifiers, and most analog inputs are polarized. Reverse them and you get 0 mA, a protection-diode drop, or a damaged input — not a negative process value.

Distance versus noise. Current loops reject induced voltage; millivolt and 1–5 V circuits do not.

Signal Typical use Noise immunity Practical distance

4–20 mA (2-wire) Process variable to DCS/PLC High (current; induced volts add little) Hundreds to thousands of feet if the voltage budget holds

1–5 V / 0–10 V Short panel or same cabinet Low; IR drop is error Feet to tens of feet unless converted to current

3–15 psi I/P, positioner, older loops Immune to EMI; sensitive to leaks and lag Limited by volume, lag, and freeze, not EMI

  • Thermocouple mV Temperature, local or to a transmitter Very low Short unless the transmitter is at the head
  • RTD resistance Temperature Moderate; lead resistance is bias 3-wire / 4-wire extends the usable run
  • Pulse / frequency Flow total, speed Edges need clean thresholds Limited by cable quality and maximum frequency

Dry contact Discrete status, shutdown inputs Bounce; leakage can false-ON Long runs need wetting current and attention to leakage

NAMUR proximity Discrete plus wire-fault detect, IS Current-level; suited to IS amplifiers Set by the amplifier and IS parameters

Tip

Exam habit

When a stem gives milliamps and a range, convert with ( I − 4 ) / 16 (I-4)/16 ( I − 4 ) /16 . When it gives 0 mA, think open or unpowered , not lower range value.

Loading diagram... Live-zero 4–20 mA loop versus 0 mA fault