Study guide
13.2 Unsymmetrical Fault Analysis (SLG, L-L, DLG Fault Calculations)
PE Electrical and Computer: Power Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Strategy & Reference Handbook
1.1 PE Power Exam Format, CBT Navigation & Reference Handbook 1.2 2026 Reference Standards (NEC 2020, NFPA 70E-2021, NESC) & Scoring Mechanics 1.3 CBT Pacing, AIT Question Formats & Formula Sheet Mastery
2 Chapter 2: Measurement, Metering & Field Testing
2.1 Current Transformers (CTs), Potential Transformers (PTs) & Meter Connections 2.2 Instrument Transformer Burdens, Saturation Curves & Ratio Correction Factors 2.3 Insulation Resistance Testing (Megger, Polarization Index, Dielectric Absorption) 2.4 Ground Resistance Testing (Fall-of-Potential 62% Rule & Clamp-on Methods)
3 Chapter 3: General Applications — Grounding & Surge Protection
3.1 Substation Ground Grid Design & IEEE 80 Touch/Step Voltage Criteria 3.2 Lightning Protection Systems & Rolling Sphere / Cone of Protection Methods 3.3 Surge Protective Devices (SPDs) & Voltage Surge Arresters
4 Chapter 4: General Applications — Lighting & Energy Management
4.1 Illumination Engineering & Zonal Cavity / Lumen Method Calculations 4.2 Energy Management, Demand Factors & Load Factor Calculations 4.3 Economic Dispatch, Energy Efficiency & Load Profile Analysis
5 Chapter 5: Electrical Safety & NFPA Standards
5.1 NFPA 70E Shock Protection, Approach Boundaries & PPE Requirements 5.2 Arc-Flash Hazard Analysis & IEEE 1584-2018 Incident Energy Calculations 5.3 Hazardous (Classified) Locations (Class I, II, III & Division/Zone Systems) 5.4 Special Occupancies & Critical Systems (NEC Articles 517 Health Care, 700/701/702 Emergency)
6 Chapter 6: NEC Wiring Methods & Installation Requirements
6.1 Conductor Ampacity & NEC Table 310.16 Derating Adjustments 6.2 Raceway Fill, Box Sizing & Conduit Bending Calculations (Chapter 9 Tables) 6.3 Equipment Grounding Conductors & Grounding Electrode Sizing (NEC Article 250)
7 Chapter 7: Circuit Analysis — Fundamentals & Symmetrical Components
7.1 DC & Single-Phase AC Network Analysis (Thevenin, Norton, Superposition) 7.2 Balanced Three-Phase Circuits (Wye-Delta Configurations & Power Formulas) 7.3 Symmetrical Components & Fortescue Sequence Transformation Matrices 7.4 Sequence Impedances & Positive, Negative, Zero Sequence Network Construction
8 Chapter 8: Circuit Analysis — Per-Unit & Phasor Analysis
8.1 Per-Unit System Fundamentals & Base Conversion Formulas 8.2 Three-Phase Per-Unit Network Modeling & Equipment Impedance Conversion 8.3 Phasor Diagrams, Complex Power & Power Triangle Relationships
9 Chapter 9: Power Electronics & Logic Controls
9.1 Power Electronic Converters (Rectifiers, Inverters & DC-DC Topologies) 9.2 Inverter-Based Resources (IBRs), Grid-Forming & Grid-Following Controls 9.3 Variable Frequency Drives (VFDs), PWM Operation & Harmonic Mitigation 9.4 Boolean Algebra, Logic Gates, De Morgan's Laws & Ladder Logic Control Diagrams
10 Chapter 10: Rotating Machines — Induction & Synchronous
10.1 Three-Phase Induction Motors (Equivalent Circuits, Slip & Performance) 10.2 Induction Motor Torque-Speed Characteristics & NEMA Design Classes 10.3 Synchronous Machines (Operating Principles, Power-Angle Curves & V-Curves) 10.4 Motor Starting Methods (DOL, Wye-Delta, Autotransformer, Soft-Start) & Voltage Dip
11 Chapter 11: Electric Power Devices & Renewable Energy
11.1 Power Transformers (Equivalent Circuits, Efficiency & Voltage Regulation) 11.2 Power Factor Correction Capacitors & Shunt Bank Sizing 11.3 Battery Energy Storage Systems (BESS) & Ultracapacitors 11.4 Renewable Energy Generation (Solar Photovoltaic Systems & Wind Turbines)
12 Chapter 12: Transmission & Distribution — Steady-State & Power Quality
12.1 Transmission Line Modeling, Voltage Drop & Conductor Sizing 12.2 Voltage Regulation, Reactive Power Support & Tap-Changer Controls 12.3 Power Quality, Harmonics, THD & IEEE 519 Compliance 12.4 Power Flow Analysis & System Stability (Steady-State, Transient & Swing Equation)
13 Chapter 13: Transmission & Distribution — Fault Analysis & Transformer Shifts
13.1 Symmetrical Three-Phase Bolted Fault Calculations 13.2 Unsymmetrical Fault Analysis (SLG, L-L, DLG Fault Calculations) 13.3 Transformer Connection Types, Zero-Sequence Paths & 30-Degree Phase Shifts
14 Chapter 14: Protection Systems & Device Coordination
14.1 Overcurrent Protection & Time-Current Characteristic (TCC) Curves 14.2 Protective Relaying Schemes (Differential 87, Distance 21, Undervoltage 27) 14.3 Circuit Breakers, Fuses & Automatic Reclosers 14.4 Protection Coordination, Selectivity & Coordination Time Intervals (CTI)
13.2 Unsymmetrical Fault Analysis (SLG, L-L, DLG Fault Calculations)
Key Takeaways Explain This Topic AI
Symmetrical components decompose unbalanced three-phase systems into three uncoupled sequence networks: Positive sequence ( 012 → 1 012\to 1 012 → 1 ), Negative sequence ( 012 → 2 012\to 2 012 → 2 ), and Zero sequence ( 012 → 0 012\to 0 012 → 0 ) via the Fortescue transformation matrix A \mathbf{A} A with a = 1 ∠ 120 ∘ a = 1\angle 120^\circ a = 1∠12 0 ∘ .
Single Line-to-Ground (SLG) faults require connecting positive, negative, and zero sequence networks in series: I a 0 = I a 1 = I a 2 = V F Z 1 + Z 2 + Z 0 + 3 Z f I_{a0} = I_{a1} = I_{a2} = \frac{V_F}{Z_1 + Z_2 + Z_0 + 3Z_f} I a 0 = I a 1 = I a 2 = Z 1 + Z 2 + Z 0 + 3 Z f V F , with total fault current I f = 3 I a 0 I_f = 3I_{a0} I f = 3 I a 0 .
Line-to-Line (L-L) faults involve only positive and negative sequence networks connected in parallel ( I a 0 = 0 , I a 1 = − I a 2 I_{a0} = 0, I_{a1} = -I_{a2} I a 0 = 0 , I a 1 = − I a 2 ), yielding ∣ I f , L L ∣ = 3 ∣ I a 1 ∣ = 3 V F ∣ Z 1 + Z 2 + Z f ∣ |I_{f,LL}| = \sqrt{3}|I_{a1}| = \frac{\sqrt{3}V_F}{|Z_1 + Z_2 + Z_f|} ∣ I f , LL ∣ = 3 ∣ I a 1 ∣ = ∣ Z 1 + Z 2 + Z f ∣ 3 V F , which equals 86.6 % 86.6\% 86.6% of I 3 ϕ I_{3\phi} I 3 ϕ when Z 1 = Z 2 Z_1 = Z_2 Z 1 = Z 2 .
Double Line-to-Ground (DLG) faults connect positive, negative, and zero sequence networks in parallel: I a 1 = V F Z 1 + ( Z 2 ∥ ( Z 0 + 3 Z f ) ) I_{a1} = \frac{V_F}{Z_1 + (Z_2 \parallel (Z_0 + 3Z_f))} I a 1 = Z 1 + ( Z 2 ∥ ( Z 0 + 3 Z f )) V F , where total ground return current is I g = 3 I a 0 I_g = 3I_{a0} I g = 3 I a 0 .
When zero-sequence impedance is less than positive-sequence impedance ( Z 0 < Z 1 Z_0 < Z_1 Z 0 < Z 1 , common near solidly grounded generators and Δ − Y g \Delta-Y_g Δ − Y g transformers), the SLG fault current strictly exceeds the symmetrical 3-phase fault current ( I S L G > I 3 ϕ I_{SLG} > I_{3\phi} I S L G > I 3 ϕ ).
Last updated: August 2026
13.2 Unsymmetrical Fault Analysis (SLG, L-L, DLG Fault Calculations)
Executive Overview: While three-phase faults represent the most severe balanced condition, the vast majority of real-world power system faults are unsymmetrical : Single Line-to-Ground (SLG, ∼ 70 % \sim 70\% ∼ 70% of all faults), Line-to-Line (L-L, ∼ 15 % \sim 15\% ∼ 15% ), and Double Line-to-Ground (DLG, ∼ 10 % \sim 10\% ∼ 10% ). Analyzing unsymmetrical faults requires Fortescue symmetrical component transformations to decouple mutually coupled three-phase networks into independent Positive ( 1 1 1 ), Negative ( 2 2 2 ), and Zero ( 0 0 0 ) sequence networks. On the NCEES PE Power exam, candidates must master the boundary conditions, sequence network interconnections, ground potential rise ( G P R GPR GPR ), and unfaulted phase voltage shifts across all fault types.
1. Symmetrical Components Matrix Foundations
In 1918, Charles LeGeyt Fortescue proved that any unbalanced set of three-phase phasors ( I a , I b , I c \mathbf{I}_a, \mathbf{I}_b, \mathbf{I}_c I a , I b , I c ) can be decomposed into three symmetrical sequence components: [ I a I b I c ] = [ 1 1 1 1 a 2 a 1 a a 2 ] [ I a 0 I a 1 I a 2 ] = A I 012 \begin{bmatrix} \mathbf{I}_a \\ \mathbf{I}_b \\ \mathbf{I}_c \end{bmatrix} = \begin{bmatrix} 1 & 1 & 1 \\ 1 & a^2 & a \\ 1 & a & a^2 \end{bmatrix} \begin{bmatrix} \mathbf{I}_{a0} \\ \mathbf{I}_{a1} \\ \mathbf{I}_{a2} \end{bmatrix} = \mathbf{A} \mathbf{I}_{012} I a I b I c = 1 1 1 1 a 2 a 1 a a 2 I a 0 I a 1 I a 2 = A I 012
where the complex rotation operator a = 1 ∠ 120 ∘ = − 0.5 + j 3 2 = − 0.5 + j 0.8660 a = 1\angle 120^\circ = -0.5 + j\frac{\sqrt{3}}{2} = -0.5 + j0.8660 a = 1∠12 0 ∘ = − 0.5 + j 2 3 = − 0.5 + j 0.8660 has properties:
a 2 = 1 ∠ 240 ∘ = 1 ∠ − 120 ∘ = − 0.5 − j 0.8660 a^2 = 1\angle 240^\circ = 1\angle -120^\circ = -0.5 - j0.8660 a 2 = 1∠24 0 ∘ = 1∠ − 12 0 ∘ = − 0.5 − j 0.8660
- a 3 = 1 ∠ 360 ∘ = 1.0 ∠ 0 ∘ a^3 = 1\angle 360^\circ = 1.0\angle 0^\circ a 3 = 1∠36 0 ∘ = 1.0∠ 0 ∘
- 1 + a + a 2 = 0 1 + a + a^2 = 0 1 + a + a 2 = 0
Inverting the transformation matrix A \mathbf{A} A gives sequence currents from phase currents: I 012 = A − 1 I a b c = 1 3 [ 1 1 1 1 a a 2 1 a 2 a ] [ I a I b I c ] \mathbf{I}_{012} = \mathbf{A}^{-1} \mathbf{I}_{abc} = \frac{1}{3} \begin{bmatrix} 1 & 1 & 1 \\ 1 & a & a^2 \\ 1 & a^2 & a \end{bmatrix} \begin{bmatrix} \mathbf{I}_a \\ \mathbf{I}_b \\ \mathbf{I}_c \end{bmatrix} I 012 = A − 1 I ab c = 3 1 1 1 1 1 a a 2 1 a 2 a I a I b I c I a 0 = 1 3 ( I a + I b + I c ) [ Zero Sequence: In-phase, returns via ground ] I a 1 = 1 3 ( I a + a I b + a 2 I c ) [ Positive Sequence: Normal a − b − c phase rotation ] I a 2 = 1 3 ( I a + a 2 I b + a I c ) [ Negative Sequence: Reversed a − c − b phase rotation ] \begin{aligned} \mathbf{I}_{a0} &= \frac{1}{3} (\mathbf{I}_a + \mathbf{I}_b + \mathbf{I}_c) \quad &[\text{Zero Sequence: In-phase, returns via ground}] \\ \mathbf{I}_{a1} &= \frac{1}{3} (\mathbf{I}_a + a\mathbf{I}_b + a^2\mathbf{I}_c) \quad &[\text{Positive Sequence: Normal } a-b-c \text{ phase rotation}] \\ \mathbf{I}_{a2} &= \frac{1}{3} (\mathbf{I}_a + a^2\mathbf{I}_b + a\mathbf{I}_c) \quad &[\text{Negative Sequence: Reversed } a-c-b \text{ phase rotation}] \end{aligned} I a 0 I a 1 I a 2 = 3 1 ( I a + I b + I c ) = 3 1 ( I a + a I b + a 2 I c ) = 3 1 ( I a + a 2 I b + a I c ) [ Zero Sequence: In-phase, returns via ground ] [ Positive Sequence: Normal a − b − c phase rotation ] [ Negative Sequence: Reversed a − c − b phase rotation ]
2. Single Line-to-Ground (SLG) Fault Analysis
Consider an SLG fault on phase a a a through fault impedance Z f Z_f Z f to ground:
- Boundary Conditions in Physical Domain
- I b = 0 \mathbf{I}_b = 0 I b = 0
- I c = 0 \mathbf{I}_c = 0 I c = 0
- V a = I a Z f \mathbf{V}_a = \mathbf{I}_a Z_f V a = I a Z f
- Sequence Domain Transformations
Substituting boundary conditions into A − 1 \mathbf{A}^{-1} A − 1 : I a 0 = 1 3 ( I a + 0 + 0 ) = 1 3 I a , I a 1 = 1 3 I a , I a 2 = 1 3 I a \mathbf{I}_{a0} = \frac{1}{3}(\mathbf{I}_a + 0 + 0) = \frac{1}{3}\mathbf{I}_a, \qquad \mathbf{I}_{a1} = \frac{1}{3}\mathbf{I}_a, \qquad \mathbf{I}_{a2} = \frac{1}{3}\mathbf{I}_a I a 0 = 3 1 ( I a + 0 + 0 ) = 3 1 I a , I a 1 = 3 1 I a , I a 2 = 3 1 I a ∴ I a 0 = I a 1 = I a 2 = 1 3 I a \therefore \mathbf{I}_{a0} = \mathbf{I}_{a1} = \mathbf{I}_{a2} = \frac{1}{3}\mathbf{I}_a ∴ I a 0 = I a 1 = I a 2 = 3 1 I a
Because the sequence currents are strictly identical, the positive, negative, and zero sequence networks are connected in SERIES . Sequence Network Connection for Single Line-to-Ground (SLG) Fault:
- (+) o---(~) V_F ---[ Z_1 ]---o
- |
- (+) o--------------[ Z_2 ]---o (SERIES CONNECTION)
- |
- (+) o--------------[ Z_0 ]---o
- |
- [ 3*Z_f ]
- |
- (-) o------------------------o Neutral Reference Bus
SLG Fault Current Formulas I a 0 = I a 1 = I a 2 = V F Z 1 + Z 2 + Z 0 + 3 Z f \mathbf{I}_{a0} = \mathbf{I}_{a1} = \mathbf{I}_{a2} = \frac{\mathbf{V}_F}{\mathbf{Z}_1 + \mathbf{Z}_2 + \mathbf{Z}_0 + 3 Z_f} I a 0 = I a 1 = I a 2 = Z 1 + Z 2 + Z 0 + 3 Z f V F I f = I a = I a 0 + I a 1 + I a 2 = 3 I a 0 = 3 V F Z 1 + Z 2 + Z 0 + 3 Z f \mathbf{I}_f = \mathbf{I}_a = \mathbf{I}_{a0} + \mathbf{I}_{a1} + \mathbf{I}_{a2} = 3\mathbf{I}_{a0} = \frac{3\mathbf{V}_F}{\mathbf{Z}_1 + \mathbf{Z}_2 + \mathbf{Z}_0 + 3 Z_f} I f = I a = I a 0 + I a 1 + I a 2 = 3 I a 0 = Z 1 + Z 2 + Z 0 + 3 Z f 3 V F
Ground Potential Rise & Unfaulted Phase Voltage Swell
When an SLG fault occurs, current returning through grounding resistance R g R_g R g elevates substation ground grid voltage: G P R = ∣ I g ∣ ⋅ R g = 3 ∣ I a 0 ∣ ⋅ R g GPR = |\mathbf{I}_g| \cdot R_g = 3|\mathbf{I}_{a0}| \cdot R_g GPR = ∣ I g ∣ ⋅ R g = 3∣ I a 0 ∣ ⋅ R g
On ungrounded systems ( Z 0 → ∞ Z_0 \to \infty Z 0 → ∞ ), the fault current is limited only by distributed line-to-ground capacitance ( I f ≈ 3 I C 0 I_f \approx 3 I_{C0} I f ≈ 3 I C 0 ), but the voltages of unfaulted phases b b b and c c c shift from line-to-neutral to full line-to-line magnitude : V b , f a u l t = 3 V L N ∠ − 150 ∘ , V c , f a u l t = 3 V L N ∠ 150 ∘ ⟹ ∣ V u n f a u l t e d ∣ = 3 ∣ V L N ∣ = ∣ V L L ∣ V_{b,fault} = \sqrt{3} V_{LN} \angle -150^\circ, \qquad V_{c,fault} = \sqrt{3} V_{LN} \angle 150^\circ \quad \Longrightarrow \quad |V_{unfaulted}| = \sqrt{3} |V_{LN}| = |V_{LL}| V b , f a u lt = 3 V L N ∠ − 15 0 ∘ , V c , f a u lt = 3 V L N ∠15 0 ∘ ⟹ ∣ V u n f a u lt e d ∣ = 3 ∣ V L N ∣ = ∣ V LL ∣
3. Line-to-Line (L-L) Fault Analysis
Consider an L-L fault between phases b b b and c c c through fault impedance Z f Z_f Z f :
- Boundary Conditions in Physical Domain
- I a = 0 \mathbf{I}_a = 0 I a = 0
- I b = − I c \mathbf{I}_b = -\mathbf{I}_c I b = − I c
- V b − V c = I b Z f \mathbf{V}_b - \mathbf{V}_c = \mathbf{I}_b Z_f V b − V c = I b Z f
Sequence Domain Transformations I a 0 = 1 3 ( I a + I b + I c ) = 1 3 ( 0 + I b − I b ) = 0 \mathbf{I}_{a0} = \frac{1}{3}(\mathbf{I}_a + \mathbf{I}_b + \mathbf{I}_c) = \frac{1}{3}(0 + \mathbf{I}_b - \mathbf{I}_b) = 0 I a 0 = 3 1 ( I a + I b + I c ) = 3 1 ( 0 + I b − I b ) = 0 I a 1 = 1 3 ( 0 + a I b − a 2 I b ) = a − a 2 3 I b = j 3 3 I b = j 3 I b \mathbf{I}_{a1} = \frac{1}{3}(0 + a\mathbf{I}_b - a^2\mathbf{I}_b) = \frac{a - a^2}{3}\mathbf{I}_b = \frac{j\sqrt{3}}{3}\mathbf{I}_b = \frac{j}{\sqrt{3}}\mathbf{I}_b I a 1 = 3 1 ( 0 + a I b − a 2 I b ) = 3 a − a 2 I b = 3 j 3 I b = 3 j I b I a 2 = 1 3 ( 0 + a 2 I b − a I b ) = − I a 1 \mathbf{I}_{a2} = \frac{1}{3}(0 + a^2\mathbf{I}_b - a\mathbf{I}_b) = -\mathbf{I}_{a1} I a 2 = 3 1 ( 0 + a 2 I b − a I b ) = − I a 1
Because I a 0 = 0 \mathbf{I}_{a0} = 0 I a 0 = 0 and I a 1 = − I a 2 \mathbf{I}_{a1} = -\mathbf{I}_{a2} I a 1 = − I a 2 , the zero-sequence network is completely isolated (open-circuit), and the positive and negative sequence networks are connected in PARALLEL . Sequence Network Connection for Line-to-Line (L-L) Fault:
- (+) o---(~) V_F ---[ Z_1 ]---+---o
- | |
- [Z_f]|
- | |
- (+) o--------------[ Z_2 ]---+---o (PARALLEL: Pos || Neg)
(+) o--------------[ Z_0 ] (OPEN CIRCUIT: I_a0 = 0)
L-L Fault Current Formulas I a 1 = − I a 2 = V F Z 1 + Z 2 + Z f , I a 0 = 0 \mathbf{I}_{a1} = -\mathbf{I}_{a2} = \frac{\mathbf{V}_F}{\mathbf{Z}_1 + \mathbf{Z}_2 + Z_f}, \qquad \mathbf{I}_{a0} = 0 I a 1 = − I a 2 = Z 1 + Z 2 + Z f V F , I a 0 = 0 I b = − I c = − j 3 I a 1 = − j 3 V F Z 1 + Z 2 + Z f \mathbf{I}_b = -\mathbf{I}_c = -j\sqrt{3}\mathbf{I}_{a1} = \frac{-j\sqrt{3}\mathbf{V}_F}{\mathbf{Z}_1 + \mathbf{Z}_2 + Z_f} I b = − I c = − j 3 I a 1 = Z 1 + Z 2 + Z f − j 3 V F ∣ I f , L L ∣ = 3 ∣ I a 1 ∣ = 3 ∣ V F ∣ ∣ Z 1 + Z 2 + Z f ∣ |\mathbf{I}_{f,LL}| = \sqrt{3}|\mathbf{I}_{a1}| = \frac{\sqrt{3}|\mathbf{V}_F|}{|\mathbf{Z}_1 + \mathbf{Z}_2 + Z_f|} ∣ I f , LL ∣ = 3 ∣ I a 1 ∣ = ∣ Z 1 + Z 2 + Z f ∣ 3 ∣ V F ∣
Note
L-L vs. 3-Phase Ratio: If Z 1 = Z 2 Z_1 = Z_2 Z 1 = Z 2 and Z f = 0 Z_f = 0 Z f = 0 , the bolted line-to-line fault current is: ∣ I f , L L ∣ = 3 V F 2 Z 1 = 3 2 ( V F Z 1 ) = 3 2 I f , 3 ϕ ≈ 0.8660 ⋅ I f , 3 ϕ |\mathbf{I}_{f,LL}| = \frac{\sqrt{3} V_F}{2 Z_1} = \frac{\sqrt{3}}{2} \left( \frac{V_F}{Z_1} \right) = \frac{\sqrt{3}}{2} I_{f,3\phi} \approx 0.8660 \cdot I_{f,3\phi} ∣ I f , LL ∣ = 2 Z 1 3 V F = 2 3 ( Z 1 V F ) = 2 3 I f , 3 ϕ ≈ 0.8660 ⋅ I f , 3 ϕ
4. Double Line-to-Ground (DLG) Fault Analysis
Consider a DLG fault where phases b b b and c c c contact each other and ground through fault impedance Z f Z_f Z f :
- Boundary Conditions in Physical Domain
- I a = 0 \mathbf{I}_a = 0 I a = 0
V b = V c = ( I b + I c ) Z f = I g Z f \mathbf{V}_b = \mathbf{V}_c = (\mathbf{I}_b + \mathbf{I}_c) Z_f = \mathbf{I}_g Z_f V b = V c = ( I b + I c ) Z f = I g Z f
Sequence Domain Transformations
Connecting positive, negative, and zero sequence networks in PARALLEL : Sequence Network Connection for Double Line-to-Ground (DLG) Fault:
- +---[ Z_1 ]---(~) V_F
- |
- (+) o----+---[ Z_2 ]-----------o (-) (PARALLEL COMBINATION)
- |
- +---[ Z_0 + 3*Z_f ]---o
DLG Fault Current Formulas I a 1 = V F Z 1 + ( Z 2 ( Z 0 + 3 Z f ) Z 2 + Z 0 + 3 Z f ) \mathbf{I}_{a1} = \frac{\mathbf{V}_F}{\mathbf{Z}_1 + \left( \frac{\mathbf{Z}_2 (\mathbf{Z}_0 + 3Z_f)}{\mathbf{Z}_2 + \mathbf{Z}_0 + 3Z_f} \right)} I a 1 = Z 1 + ( Z 2 + Z 0 + 3 Z f Z 2 ( Z 0 + 3 Z f ) ) V F
Using current division to find negative and zero sequence currents: I a 2 = − I a 1 ( Z 0 + 3 Z f Z 2 + Z 0 + 3 Z f ) , I a 0 = − I a 1 ( Z 2 Z 2 + Z 0 + 3 Z f ) \mathbf{I}_{a2} = -\mathbf{I}_{a1} \left( \frac{\mathbf{Z}_0 + 3Z_f}{\mathbf{Z}_2 + \mathbf{Z}_0 + 3Z_f} \right), \qquad \mathbf{I}_{a0} = -\mathbf{I}_{a1} \left( \frac{\mathbf{Z}_2}{\mathbf{Z}_2 + \mathbf{Z}_0 + 3Z_f} \right) I a 2 = − I a 1 ( Z 2 + Z 0 + 3 Z f Z 0 + 3 Z f ) , I a 0 = − I a 1 ( Z 2 + Z 0 + 3 Z f Z 2 )
Total ground return current: I g = I b + I c = 3 I a 0 = − 3 I a 1 ( Z 2 Z 2 + Z 0 + 3 Z f ) \mathbf{I}_g = \mathbf{I}_b + \mathbf{I}_c = 3\mathbf{I}_{a0} = -3\mathbf{I}_{a1} \left( \frac{\mathbf{Z}_2}{\mathbf{Z}_2 + \mathbf{Z}_0 + 3Z_f} \right) I g = I b + I c = 3 I a 0 = − 3 I a 1 ( Z 2 + Z 0 + 3 Z f Z 2 )
5. Fault Severity Comparison ( Z 0 Z_0 Z 0 vs. Z 1 Z_1 Z 1 Dynamics)
Many engineers intuitively assume that three-phase faults always produce the highest current. However, in solidly grounded transmission substations and near generating stations, the zero-sequence impedance is frequently lower than positive-sequence impedance ( Z 0 < Z 1 Z_0 < Z_1 Z 0 < Z 1 ).
When is SLG Fault Current Greater than 3-Phase Fault Current? I f , S L G = 3 V F Z 1 + Z 2 + Z 0 > V F Z 1 = I f , 3 ϕ I_{f,SLG} = \frac{3 V_F}{Z_1 + Z_2 + Z_0} > \frac{V_F}{Z_1} = I_{f,3\phi} I f , S L G = Z 1 + Z 2 + Z 0 3 V F > Z 1 V F = I f , 3 ϕ
Assuming Z 1 = Z 2 Z_1 = Z_2 Z 1 = Z 2 : 3 2 Z 1 + Z 0 > 1 Z 1 ⟹ 3 Z 1 > 2 Z 1 + Z 0 ⟹ Z 0 < Z 1 \frac{3}{2 Z_1 + Z_0} > \frac{1}{Z_1} \implies 3 Z_1 > 2 Z_1 + Z_0 \implies \mathbf{Z}_0 < \mathbf{Z}_1 2 Z 1 + Z 0 3 > Z 1 1 ⟹ 3 Z 1 > 2 Z 1 + Z 0 ⟹ Z 0 < Z 1 Fault Type Sequence Interconnection Fault Current Formula ( Z f = 0 ) Ratio to I 3 ϕ (when Z 1 = Z 2 = Z 0 ) 3-Phase Bolted ( 3 ϕ ) Positive Sequence Only I f = V F Z 1 1.000 Single Line-to-Ground ( S L G ) Series: Z 1 + Z 2 + Z 0 I f = 3 V F Z 1 + Z 2 + Z 0 1.000 Line-to-Line ( L − L ) Parallel: Z 1 ∥ Z 2 I f = 3 V F Z 1 + Z 2 0.866 Double Line-to-Ground ( D L G ) Parallel: Z 1 ∥ Z 2 ∥ Z 0 I f = Phase Current: I b , I c 0.866 − 1.732 \begin{array}{|l|c|c|c|} \hline \textbf{Fault Type} & \textbf{Sequence Interconnection} & \textbf{Fault Current Formula } (Z_f = 0) & \textbf{Ratio to } I_{3\phi} \text{ (when } Z_1 = Z_2 = Z_0) \\ \hline \textbf{3-Phase Bolted } (3\phi) & \text{Positive Sequence Only} & I_f = \frac{V_F}{Z_1} & 1.000 \\ \hline \textbf{Single Line-to-Ground } (SLG) & \text{Series: } Z_1 + Z_2 + Z_0 & I_f = \frac{3 V_F}{Z_1 + Z_2 + Z_0} & 1.000 \\ \hline \textbf{Line-to-Line } (L-L) & \text{Parallel: } Z_1 \parallel Z_2 & I_f = \frac{\sqrt{3} V_F}{Z_1 + Z_2} & 0.866 \\ \hline \textbf{Double Line-to-Ground } (DLG) & \text{Parallel: } Z_1 \parallel Z_2 \parallel Z_0 & I_f = \text{Phase Current: } I_b, I_c & 0.866 - 1.732 \\ \hline \end{array} Fault Type 3-Phase Bolted ( 3 ϕ ) Single Line-to-Ground ( S L G ) Line-to-Line ( L − L ) Double Line-to-Ground ( D L G ) Sequence Interconnection Positive Sequence Only Series: Z 1 + Z 2 + Z 0 Parallel: Z 1 ∥ Z 2 Parallel: Z 1 ∥ Z 2 ∥ Z 0 Fault Current Formula ( Z f = 0 ) I f = Z 1 V F I f = Z 1 + Z 2 + Z 0 3 V F I f = Z 1 + Z 2 3 V F I f = Phase Current: I b , I c Ratio to I 3 ϕ (when Z 1 = Z 2 = Z 0 ) 1.000 1.000 0.866 0.866 − 1.732
- 6. Comprehensive Worked Calculation: Multi-Fault Analysis
- Problem Statement
A 13.8 kV 13.8\text{ kV} 13.8 kV solidly grounded substation bus has the following Thevenin sequence impedances:
- Z 1 = j 0.10 pu \mathbf{Z}_1 = j0.10\text{ pu} Z 1 = j 0.10 pu
- Z 2 = j 0.10 pu \mathbf{Z}_2 = j0.10\text{ pu} Z 2 = j 0.10 pu
Z 0 = j 0.05 pu \mathbf{Z}_0 = j0.05\text{ pu} Z 0 = j 0.05 pu ( Z 0 < Z 1 Z_0 < Z_1 Z 0 < Z 1 due to proximity of a large solidly grounded Y g − Δ Y_g-\Delta Y g − Δ generator step-up transformer)
System Base: S b a s e = 100 MVA S_{base} = 100\text{ MVA} S ba se = 100 MVA , V b a s e = 13.8 kV V_{base} = 13.8\text{ kV} V ba se = 13.8 kV
- Prefault Voltage: V F = 1.0 ∠ 0 ∘ pu \mathbf{V}_F = 1.0\angle 0^\circ\text{ pu} V F = 1.0∠ 0 ∘ pu
- Fault Impedance: Z f = 0 Z_f = 0 Z f = 0 (bolted faults)
Calculate for all four fault types:
Symmetrical three-phase ( 3 ϕ 3\phi 3 ϕ ) bolted fault current.
Single line-to-ground (SLG) fault current and ground current.
Line-to-line (L-L) fault current.
Double line-to-ground (DLG) sequence currents, phase currents, and total ground return current.
============================== STEP-BY-STEP SOLUTION ==============================
- Step 1: Compute System Base Current at 13.8 kV
- I_base = S_base / (sqrt(3) * V_base) = 100,000 kVA / (sqrt(3) * 13.8 kV)
- = 4,183.70 A = 4.1837 kA
- Step 2: Symmetrical Three-Phase Fault (3ph)
- I_a1 = V_F / Z_1 = 1.0 / (j0.10) = -j10.00 pu = 10.00 /_ -90 deg pu
- I_f,3ph = 10.00 pu
- Physical Current: I_f,3ph = 10.00 * 4.1837 kA = 41.84 kA
- Step 3: Single Line-to-Ground Fault (SLG on Phase a)
- Z_total = Z_1 + Z_2 + Z_0 = j0.10 + j0.10 + j0.05 = j0.25 pu
- I_a0 = I_a1 = I_a2 = V_F / Z_total = 1.0 / (j0.25) = -j4.00 pu = 4.00 /_ -90 deg pu
Total Fault Current in Phase a:
- I_f,SLG = I_a = 3 * I_a0 = 3 * (-j4.00 pu) = -j12.00 pu = 12.00 /_ -90 deg pu
- Physical Current: I_f,SLG = 12.00 * 4.1837 kA = 50.20 kA
>> CRITICAL OBSERVATION: I_SLG (50.20 kA) is 20% LARGER than I_3ph (41.84 kA)
because Z_0 (0.05 pu) < Z_1 (0.10 pu)!
- Step 4: Line-to-Line Fault (L-L between Phases b and c)
- I_a0 = 0
- I_a1 = -I_a2 = V_F / (Z_1 + Z_2) = 1.0 / (j0.10 + j0.10) = 1.0 / (j0.20)
- = -j5.00 pu = 5.00 /_ -90 deg pu
Fault Current Magnitude:
- |I_f,LL| = sqrt(3) * |I_a1| = sqrt(3) * 5.00 pu = 8.660 pu
- Physical Current: I_f,LL = 8.660 * 4.1837 kA = 36.23 kA
- Check Ratio: I_LL / I_3ph = 36.23 / 41.84 = 0.8660 = sqrt(3)/2 (Exact)
Step 5: Double Line-to-Ground Fault (DLG on Phases b and c)
Parallel combination of Z_2 and Z_0:
- Z_parallel = (Z_2 * Z_0) / (Z_2 + Z_0) = (j0.10 * j0.05) / (j0.10 + j0.05)
- = -0.005 / (j0.15) = j0.03333 pu
Positive-Sequence Current:
- I_a1 = V_F / (Z_1 + Z_parallel) = 1.0 / (j0.10 + j0.03333) = 1.0 / (j0.13333)
- = -j7.500 pu = 7.500 /_ -90 deg pu
Negative and Zero Sequence Currents (Current Divider):
- I_a2 = -I_a1 * [ Z_0 / (Z_2 + Z_0) ] = -(-j7.500) * [ 0.05 / 0.15 ]
- = j2.500 pu = 2.500 /_ 90 deg pu
- I_a0 = -I_a1 * [ Z_2 / (Z_2 + Z_0) ] = -(-j7.500) * [ 0.10 / 0.15 ]
- = j5.000 pu = 5.000 /_ 90 deg pu
Verify Phase a Current: I_a = I_a0 + I_a1 + I_a2 = j5.0 - j7.5 + j2.5 = 0 pu (Verified)
Phase b and Phase c Fault Currents:
- I_b = I_a0 + (a^2)*I_a1 + a*I_a2
- = j5.0 + (-0.5 - j0.8660)*(-j7.5) + (-0.5 + j0.8660)*(j2.5)
- = j5.0 + (-6.495 + j3.750) + (-2.165 - j1.250)
- = -8.660 + j7.500 pu = 11.456 /_ 140.89 deg pu
- |I_b| = |I_c| = 11.456 pu
- Physical Phase Fault Current: I_b = 11.456 * 4.1837 kA = 47.93 kA
Total Ground Return Current:
- I_g = 3 * I_a0 = 3 * (j5.000 pu) = j15.000 pu = 15.000 /_ 90 deg pu
- Physical Ground Current: I_g = 15.000 * 4.1837 kA = 62.76 kA
- ============================== SUMMARY OF RESULTS ==============================
- 3-Phase Bolted Fault Current (I_3ph) = 10.00 pu = 41.84 kA
- Single Line-to-Ground Current (I_SLG) = 12.00 pu = 50.20 kA (+20.0% vs 3ph)
- Line-to-Line Fault Current (I_LL) = 8.66 pu = 36.23 kA (-13.4% vs 3ph)
- DLG Phase Fault Current (|I_b|, |I_c|)= 11.46 pu = 47.93 kA (+14.6% vs 3ph)
- DLG Ground Return Current (I_g) = 15.00 pu = 62.76 kA (+50.0% vs 3ph)
- ===================================================================================
- 7. Common Exam Traps & Strategic Pitfalls
The "Factor of 3" Ground Current Omission: Calculating I a 0 I_{a0} I a 0 in an SLG fault and forgetting to multiply by 3 3 3 to obtain the physical phase/ground fault current ( I f = 3 I a 0 I_f = 3 I_{a0} I f = 3 I a 0 ). Relay engineers size ground overcurrent elements (50N/51N) based on 3 I a 0 3 I_{a0} 3 I a 0 .
Assuming Three-Phase Fault Current is Always the Highest: Sizing circuit breakers exclusively for I 3 ϕ I_{3\phi} I 3 ϕ without checking I S L G I_{SLG} I S L G . If Z 0 < Z 1 Z_0 < Z_1 Z 0 < Z 1 , the SLG fault produces the maximum interrupting duty.
Applying Zero-Sequence Networks to Line-to-Line Faults: Incorrectly including Z 0 Z_0 Z 0 in L-L fault calculations. Because the fault does not touch ground and I b = − I c I_b = -I_c I b = − I c , no zero-sequence current can flow ( I a 0 = 0 I_{a0} = 0 I a 0 = 0 ).
Confusing Fault Impedance Factor 3 Z f 3Z_f 3 Z f with Z f Z_f Z f : In SLG and DLG sequence networks, the physical fault impedance to ground Z f Z_f Z f must be multiplied by 3 3 3 in the zero-sequence branch ( 3 Z f 3Z_f 3 Z f ) because 3 I a 0 3I_{a0} 3 I a 0 flows through the neutral ground path.