3.1 Substation Ground Grid Design & IEEE 80 Touch/Step Voltage Criteria

PE Electrical and Computer: Power Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Exam Overview, Strategy & Reference Handbook

1.1 PE Power Exam Format, CBT Navigation & Reference Handbook 1.2 2026 Reference Standards (NEC 2020, NFPA 70E-2021, NESC) & Scoring Mechanics 1.3 CBT Pacing, AIT Question Formats & Formula Sheet Mastery

2 Chapter 2: Measurement, Metering & Field Testing

2.1 Current Transformers (CTs), Potential Transformers (PTs) & Meter Connections 2.2 Instrument Transformer Burdens, Saturation Curves & Ratio Correction Factors 2.3 Insulation Resistance Testing (Megger, Polarization Index, Dielectric Absorption) 2.4 Ground Resistance Testing (Fall-of-Potential 62% Rule & Clamp-on Methods)

3 Chapter 3: General Applications — Grounding & Surge Protection

3.1 Substation Ground Grid Design & IEEE 80 Touch/Step Voltage Criteria 3.2 Lightning Protection Systems & Rolling Sphere / Cone of Protection Methods 3.3 Surge Protective Devices (SPDs) & Voltage Surge Arresters

4 Chapter 4: General Applications — Lighting & Energy Management

4.1 Illumination Engineering & Zonal Cavity / Lumen Method Calculations 4.2 Energy Management, Demand Factors & Load Factor Calculations 4.3 Economic Dispatch, Energy Efficiency & Load Profile Analysis

5 Chapter 5: Electrical Safety & NFPA Standards

5.1 NFPA 70E Shock Protection, Approach Boundaries & PPE Requirements 5.2 Arc-Flash Hazard Analysis & IEEE 1584-2018 Incident Energy Calculations 5.3 Hazardous (Classified) Locations (Class I, II, III & Division/Zone Systems) 5.4 Special Occupancies & Critical Systems (NEC Articles 517 Health Care, 700/701/702 Emergency)

6 Chapter 6: NEC Wiring Methods & Installation Requirements

6.1 Conductor Ampacity & NEC Table 310.16 Derating Adjustments 6.2 Raceway Fill, Box Sizing & Conduit Bending Calculations (Chapter 9 Tables) 6.3 Equipment Grounding Conductors & Grounding Electrode Sizing (NEC Article 250)

7 Chapter 7: Circuit Analysis — Fundamentals & Symmetrical Components

7.1 DC & Single-Phase AC Network Analysis (Thevenin, Norton, Superposition) 7.2 Balanced Three-Phase Circuits (Wye-Delta Configurations & Power Formulas) 7.3 Symmetrical Components & Fortescue Sequence Transformation Matrices 7.4 Sequence Impedances & Positive, Negative, Zero Sequence Network Construction

8 Chapter 8: Circuit Analysis — Per-Unit & Phasor Analysis

8.1 Per-Unit System Fundamentals & Base Conversion Formulas 8.2 Three-Phase Per-Unit Network Modeling & Equipment Impedance Conversion 8.3 Phasor Diagrams, Complex Power & Power Triangle Relationships

9 Chapter 9: Power Electronics & Logic Controls

9.1 Power Electronic Converters (Rectifiers, Inverters & DC-DC Topologies) 9.2 Inverter-Based Resources (IBRs), Grid-Forming & Grid-Following Controls 9.3 Variable Frequency Drives (VFDs), PWM Operation & Harmonic Mitigation 9.4 Boolean Algebra, Logic Gates, De Morgan's Laws & Ladder Logic Control Diagrams

10 Chapter 10: Rotating Machines — Induction & Synchronous

10.1 Three-Phase Induction Motors (Equivalent Circuits, Slip & Performance) 10.2 Induction Motor Torque-Speed Characteristics & NEMA Design Classes 10.3 Synchronous Machines (Operating Principles, Power-Angle Curves & V-Curves) 10.4 Motor Starting Methods (DOL, Wye-Delta, Autotransformer, Soft-Start) & Voltage Dip

11 Chapter 11: Electric Power Devices & Renewable Energy

11.1 Power Transformers (Equivalent Circuits, Efficiency & Voltage Regulation) 11.2 Power Factor Correction Capacitors & Shunt Bank Sizing 11.3 Battery Energy Storage Systems (BESS) & Ultracapacitors 11.4 Renewable Energy Generation (Solar Photovoltaic Systems & Wind Turbines)

12 Chapter 12: Transmission & Distribution — Steady-State & Power Quality

12.1 Transmission Line Modeling, Voltage Drop & Conductor Sizing 12.2 Voltage Regulation, Reactive Power Support & Tap-Changer Controls 12.3 Power Quality, Harmonics, THD & IEEE 519 Compliance 12.4 Power Flow Analysis & System Stability (Steady-State, Transient & Swing Equation)

13 Chapter 13: Transmission & Distribution — Fault Analysis & Transformer Shifts

13.1 Symmetrical Three-Phase Bolted Fault Calculations 13.2 Unsymmetrical Fault Analysis (SLG, L-L, DLG Fault Calculations) 13.3 Transformer Connection Types, Zero-Sequence Paths & 30-Degree Phase Shifts

14 Chapter 14: Protection Systems & Device Coordination

14.1 Overcurrent Protection & Time-Current Characteristic (TCC) Curves 14.2 Protective Relaying Schemes (Differential 87, Distance 21, Undervoltage 27) 14.3 Circuit Breakers, Fuses & Automatic Reclosers 14.4 Protection Coordination, Selectivity & Coordination Time Intervals (CTI)

3.1 Substation Ground Grid Design & IEEE 80 Touch/Step Voltage Criteria

Key Takeaways Explain This Topic AI

Substation grounding design balances personnel safety (limiting touch, step, and transfer voltages below ventricular fibrillation thresholds) with equipment protection and low-impedance fault clearing paths.

Dalziel's body current limits for 50 kg (0.116 / sqrt(t_s)) and 70 kg (0.157 / sqrt(t_s)) establish tolerable body current thresholds assuming a standard 1000-ohm hand-to-feet or foot-to-foot internal body resistance.

A 3- to 6-inch high-resistivity surface layer (typically crushed rock with resistivity 2000 to 5000 ohm-meters) elevates foot contact resistance via the surface derating factor C_s, significantly increasing tolerable touch and step voltage limits.

Ground Potential Rise (GPR = I_g * R_g) represents the maximum theoretical grid voltage elevation; if GPR exceeds tolerable touch voltage, rigorous mesh (E_m) and step (E_s) calculations per IEEE 80 are mandatory.

Conductor sizing for thermal fusing is governed by Onderdonk's equation based on maximum fault current magnitude and duration to prevent conductor annealing or melting.

Last updated: August 2026

Substation Ground Grid Design & IEEE 80 Safety Criteria

Substation grounding is one of the most heavily tested subjects on the NCEES PE Electrical: Power examination. An engineered grounding system must accomplish two primary, non-negotiable objectives: providing a safe environment to protect personnel from lethal electric shock during fault conditions, and establishing a low-impedance path to ground for power system fault currents, lightning discharges, and switching surges to ensure reliable operation of protective relays.

1. Fundamentals of Ground Potential Rise (GPR)

When a single line-to-ground (SLG) or double line-to-ground (DLG) fault occurs inside or near an electrical substation, a large fault current enters the earth through the substation ground grid. Because the earth and the ground grid have finite electrical resistance ( R g R_g R g ​ ), this current injection raises the electrical potential of the entire grid and the surrounding soil relative to a remote, undisturbed earth reference. GPR = I g × R g \text{GPR} = I_g \times R_g GPR = I g ​ × R g ​

Where:

GPR \text{GPR} GPR = Ground Potential Rise (Volts, V \text{V} V )

I g I_g I g ​ = Maximum symmetrical grid fault current flowing between the grid and earth (Amperes, A \text{A} A )

  • R g R_g R g ​ = Substation ground grid resistance to remote earth (Ohms, Ω \Omega Ω )
  • Grid Current Division Factor ( S f S_f S f ​ ) and Decrement Factor ( D f D_f D f ​ )

The total fault current ( I f I_f I f ​ ) at a substation bus does not entirely flow through the ground grid into the earth. A portion of the current returns through overhead ground wires (OHGW / static wires), neutral conductors, and underground cable sheaths. The design current is calculated as: I g = D f × S f × I f I_g = D_f \times S_f \times I_f I g ​ = D f ​ × S f ​ × I f ​

Where:

S f S_f S f ​ = Fault current division factor ( 0 < S f ≤ 1 0 < S_f \le 1 0 < S f ​ ≤ 1 ), representing the fraction of fault current conducted directly into the earth by the grid.

D f D_f D f ​ = Decrement factor accounting for the DC offset component during subtransient fault conditions (typically 1.0 1.0 1.0 to 1.25 1.25 1.25 depending on fault clearing time t f t_f t f ​ and system X / R X/R X / R ratio).

I f I_f I f ​ = Symmetrical root-mean-square (RMS) phase-to-ground fault current (Amperes, A \text{A} A ). +-------------------------+

  • | Substation Ground Grid |
  • Remote Earth (0 V) <--------| Resistance Rg |<------- Fault Current (Ig)
  • | +-------------------------+
  • | |
  • +================ GPR = Ig x Rg ==+

Exam Tip: If GPR ≤ E t o u c h , t o l \text{GPR} \le E_{touch,tol} GPR ≤ E t o u c h , t o l ​ , the grounding installation is unconditionally safe because even the maximum theoretical potential of the substation structure cannot exceed the tolerable shock limit. However, in almost all high-voltage substations, GPR \text{GPR} GPR exceeds several kilovolts ( 5 – 25 kV 5\text{--}25\text{ kV} 5 – 25 kV ), requiring detailed mesh voltage ( E m E_m E m ​ ) and step voltage ( E s E_s E s ​ ) verification.

2. Voltage Definitions Under IEEE Std 80

IEEE Std 80 ( IEEE Guide for Safety in AC Substation Grounding ) defines four distinct spatial potential differences that can appear across a human body during a fault:

Voltage Parameter Symbol Physical Description Shock Circuit Path

Touch Voltage E t o u c h E_{touch} E t o u c h ​ Potential difference between a grounded metallic structure (touched by a hand) and a point on the ground surface 1.0 m 1.0\text{ m} 1.0 m away. Hand to both feet in parallel.

Step Voltage E s t e p E_{step} E s t e p ​ Potential difference between two points on the earth surface separated by a distance of 1.0 m 1.0\text{ m} 1.0 m (one pace), with no contact with any metallic structure. Foot to foot in series.

Mesh Voltage E m E_m E m ​ The maximum touch voltage within a grid mesh (usually located in the corner mesh of the ground grid). Hand to both feet in parallel at worst-case mesh location.

Transfer Voltage E t r a n s f e r E_{transfer} E t r an s f er ​ Potential difference between a grounded metallic object grounded inside the substation and a conductor (e.g., fence, pipeline, neutral wire) extending outside the substation fence. Hand to feet, potentially exposing a person to the full GPR \text{GPR} GPR .

3. Human Body Impedance & Dalziel Shock Model

Electrocution hazard analysis relies on the extensive ventricular fibrillation research performed by Charles F. Dalziel. The human body is modeled as an internal electrical resistance in series with contact resistances at the points of entry and exit.

Standard Body Resistance ( R b R_b R b ​ )

IEEE Std 80 standardizes the internal resistance of the human body from hand to both feet, or foot to foot, as a constant: R b = 1000 Ω R_b = 1000\ \Omega R b ​ = 1000 Ω

Foot Contact Resistance ( R f R_f R f ​ )

A human foot is modeled as a flat metallic circular disc of radius b = 0.08 m b = 0.08\text{ m} b = 0.08 m ( 8 cm 8\text{ cm} 8 cm ) resting on the surface of the earth. In uniform soil of resistivity ρ s \rho_s ρ s ​ ( Ω ⋅ m \Omega\cdot\text{m} Ω ⋅ m ), the ground contact resistance of a single foot is: R f = ρ s 4 b = ρ s 4 ( 0.08 ) = 3.125 ρ s ≈ 3 ρ s R_f = \frac{\rho_s}{4 b} = \frac{\rho_s}{4(0.08)} = 3.125 \rho_s \approx 3 \rho_s R f ​ = 4 b ρ s ​ ​ = 4 ( 0.08 ) ρ s ​ ​ = 3.125 ρ s ​ ≈ 3 ρ s ​

Equivalent Resistance for Touch and Step Configurations

Step Voltage Configuration (Feet in Series): Current flows into one foot, through the legs and torso, and out of the other foot ( R t o t a l = R b + 2 R f R_{total} = R_b + 2 R_f R t o t a l ​ = R b ​ + 2 R f ​ ): R t h , s t e p = 1000 + 2 ( 3 ρ s ) = 1000 + 6 C s ρ s R_{th,step} = 1000 + 2(3 \rho_s) = 1000 + 6 C_s \rho_s R t h , s t e p ​ = 1000 + 2 ( 3 ρ s ​ ) = 1000 + 6 C s ​ ρ s ​

Touch Voltage Configuration (Feet in Parallel): Current flows into one hand, down through the body, and divides equally across both feet in parallel ( R t o t a l = R b + R f / 2 R_{total} = R_b + R_f / 2 R t o t a l ​ = R b ​ + R f ​ /2 ): R t h , t o u c h = 1000 + 3 ρ s 2 = 1000 + 1.5 C s ρ s R_{th,touch} = 1000 + \frac{3 \rho_s}{2} = 1000 + 1.5 C_s \rho_s R t h , t o u c h ​ = 1000 + 2 3 ρ s ​ ​ = 1000 + 1.5 C s ​ ρ s ​

  • Where C s C_s C s ​ is the surface layer derating factor. TOUCH VOLTAGE CIRCUIT STEP VOLTAGE CIRCUIT
  • (Hand-to-Feet) (Foot-to-Foot)
  • [Hand: 0 V] [Foot 1]
  • | |
  • +----+----+ +----+----+
  • | Rb=1000 | (Body) | Rf1=3Csρ| (Foot 1 Contact)
  • +----+----+ +----+----+
  • | |
  • +----+----+ +----+----+
  • | Rf / 2 | (Parallel Feet) | Rb=1000 | (Body Resistance)
  • | 1.5 Csρ | +----+----+
  • +----+----+ |
  • | +----+----+
  • [Earth Surface] | Rf2=3Csρ| (Foot 2 Contact)
  • +----+----+
  • |
  • [Foot 2]
  • R_total = 1000 + 1.5 Cs ρ_s R_total = 1000 + 6.0 Cs ρ_s
  • 4. Surface Layer Derating Factor ( C s C_s C s ​ )

In substation yards, a layer of high-resistivity material—typically crushed rock or granite gravel with resistivity ρ s = 2000 – 5000 Ω ⋅ m \rho_s = 2000\text{--}5000\ \Omega\cdot\text{m} ρ s ​ = 2000 – 5000 Ω ⋅ m and thickness h s = 0.08 – 0.15 m h_s = 0.08\text{--}0.15\text{ m} h s ​ = 0.08 – 0.15 m ( 3 – 6 inches 3\text{--}6\text{ inches} 3 – 6 inches )—is spread over the native soil (resistivity ρ \rho ρ ).

Because the crushed rock layer is thin relative to the electrical field of a foot, the actual foot resistance is reduced by the underlying lower-resistivity native soil. IEEE Std 80 models this with the surface layer derating factor C s C_s C s ​ : C s = 1 − 0.09 ( 1 − ρ ρ s ) 2 h s + 0.09 C_s = 1 - \frac{0.09 \left(1 - \frac{\rho}{\rho_s}\right)}{2 h_s + 0.09} C s ​ = 1 − 2 h s ​ + 0.09 0.09 ( 1 − ρ s ​ ρ ​ ) ​

Where:

  • h s h_s h s ​ = Surface rock layer thickness in meters ( m \text{m} m )
  • ρ \rho ρ = Native soil resistivity ( Ω ⋅ m \Omega\cdot\text{m} Ω ⋅ m )
  • ρ s \rho_s ρ s ​ = Surface crushed rock layer resistivity ( Ω ⋅ m \Omega\cdot\text{m} Ω ⋅ m )

If no surface layer is present ( h s = 0 h_s = 0 h s ​ = 0 or ρ s = ρ \rho_s = \rho ρ s ​ = ρ ), C s = 1.0 C_s = 1.0 C s ​ = 1.0 .

5. Allowable Body Current & Tolerable Voltage Criteria

Dalziel's empirical formula establishes the 99.5 % 99.5\% 99.5% non-fibrillation threshold current as a function of shock duration ( t s t_s t s ​ , in seconds, for 0.03 s ≤ t s ≤ 3.0 s 0.03\text{ s} \le t_s \le 3.0\text{ s} 0.03 s ≤ t s ​ ≤ 3.0 s ):

Body Weight Standard Allowable Body Current ( I B I_B I B ​ ) Fibrillation Energy Constant ( S B S_B S B ​ )

50 kg Body Weight I B , 50 = 0.116 t s I_{B,50} = \frac{0.116}{\sqrt{t_s}} I B , 50 ​ = t s ​ ​ 0.116 ​ S B = ( 0.116 ) 2 = 0.0135 A 2 ⋅ s S_B = (0.116)^2 = 0.0135\ \text{A}^2\cdot\text{s} S B ​ = ( 0.116 ) 2 = 0.0135 A 2 ⋅ s

70 kg Body Weight I B , 70 = 0.157 t s I_{B,70} = \frac{0.157}{\sqrt{t_s}} I B , 70 ​ = t s ​ ​ 0.157 ​ S B = ( 0.157 ) 2 = 0.0246 A 2 ⋅ s S_B = (0.157)^2 = 0.0246\ \text{A}^2\cdot\text{s} S B ​ = ( 0.157 ) 2 = 0.0246 A 2 ⋅ s

Tolerable Voltage Equations (50 kg Criteria)

Combining Ohm's law ( E = I B × R t o t a l E = I_B \times R_{total} E = I B ​ × R t o t a l ​ ) yields the governing IEEE Std 80 tolerable voltage equations for a 50 kg 50\text{ kg} 50 kg human: E t o u c h , 50 = ( 1000 + 1.5 C s ρ s ) 0.116 t s \mathbf{E_{touch,50}} = \left(1000 + 1.5 C_s \rho_s\right) \frac{0.116}{\sqrt{t_s}} E touch , 50 ​ = ( 1000 + 1.5 C s ​ ρ s ​ ) t s ​ ​ 0.116 ​ E s t e p , 50 = ( 1000 + 6.0 C s ρ s ) 0.116 t s \mathbf{E_{step,50}} = \left(1000 + 6.0 C_s \rho_s\right) \frac{0.116}{\sqrt{t_s}} E step , 50 ​ = ( 1000 + 6.0 C s ​ ρ s ​ ) t s ​ ​ 0.116 ​

For a 70 kg 70\text{ kg} 70 kg body, replace 0.116 0.116 0.116 with 0.157 0.157 0.157 .

Key Principle: Notice that E s t e p E_{step} E s t e p ​ is always substantially higher than E t o u c h E_{touch} E t o u c h ​ because R t h , s t e p R_{th,step} R t h , s t e p ​ includes two feet in series ( 6.0 C s ρ s 6.0 C_s \rho_s 6.0 C s ​ ρ s ​ ) whereas R t h , t o u c h R_{th,touch} R t h , t o u c h ​ includes two feet in parallel ( 1.5 C s ρ s 1.5 C_s \rho_s 1.5 C s ​ ρ s ​ ). Consequently, touch voltage is almost always the limiting criterion in substation ground grid design.

6. Ground Grid Resistance Estimation ( R g R_g R g ​ )

For preliminary design and PE exam calculations, simple analytical formulas estimate the total resistance to remote earth of a buried ground grid.

Sverak's Formula (Preferred IEEE 80 Method)

Sverak incorporated the grid burial depth ( h h h ) and total grid buried conductor length ( L T L_T L T ​ ): R g = ρ [ 1 L T + 1 20 A ( 1 + 1 1 + h 20 A ) ] R_g = \rho \left[ \frac{1}{L_T} + \frac{1}{\sqrt{20 A}} \left(1 + \frac{1}{1 + h \sqrt{\frac{20}{A}}}\right) \right] R g ​ = ρ ​ L T ​ 1 ​ + 20 A ​ 1 ​ ​ 1 + 1 + h A 20 ​ ​ 1 ​ ​ ​

Where:

  • ρ \rho ρ = Soil resistivity ( Ω ⋅ m \Omega\cdot\text{m} Ω ⋅ m )
  • L T L_T L T ​ = Total length of buried grid conductors and ground rods ( m \text{m} m )
  • A A A = Area occupied by the ground grid ( m 2 \text{m}^2 m 2 )
  • h h h = Grid burial depth ( m \text{m} m , typically 0.5 – 1.5 m 0.5\text{--}1.5\text{ m} 0.5 – 1.5 m )

Laurent & Niemann Formula (Upper Bound Approximation) R g ≈ ρ 4 r + ρ L T = ρ 4 A / π + ρ L T R_g \approx \frac{\rho}{4 r} + \frac{\rho}{L_T} = \frac{\rho}{4 \sqrt{A / \pi}} + \frac{\rho}{L_T} R g ​ ≈ 4 r ρ ​ + L T ​ ρ ​ = 4 A / π ​ ρ ​ + L T ​ ρ ​

Where r = A / π r = \sqrt{A / \pi} r = A / π ​ is the equivalent circular grid radius.

7. Conductor Sizing for Thermal Fusing (Onderdonk's Formula)

Ground grid conductors must withstand the maximum expected fault current without exceeding the annealing or melting temperature of the material. IEEE Std 80 uses Onderdonk's equation: A k c m i l = I × K f t c A_{kcmil} = I \times K_f \sqrt{t_c} A k c mi l ​ = I × K f ​ t c ​ ​

Or in metric units ( A m m 2 A_{mm^2} A m m 2 ​ ): I = A m m 2 ( TCAP × 10 − 4 t c α r ρ r ) ln ⁡ ( K 0 + T m K 0 + T a ) I = A_{mm^2} \sqrt{\left(\frac{\text{TCAP} \times 10^{-4}}{t_c \alpha_r \rho_r}\right) \ln\left(\frac{K_0 + T_m}{K_0 + T_a}\right)} I = A m m 2 ​ ( t c ​ α r ​ ρ r ​ TCAP × 1 0 − 4 ​ ) ln ( K 0 ​ + T a ​ K 0 ​ + T m ​ ​ ) ​

Where:

  • I I I = Symmetrical fault current magnitude ( kA \text{kA} kA RMS)
  • A A A = Conductor cross-sectional area ( kcmil \text{kcmil} kcmil or mm 2 \text{mm}^2 mm 2 )
  • t c t_c t c ​ = Fault duration / clearing time (seconds)

T m T_m T m ​ = Maximum allowable conductor temperature ( 1083 ∘ C 1083^\circ\text{C} 108 3 ∘ C for copper melting, 450 ∘ C 450^\circ\text{C} 45 0 ∘ C for exothermic welded copper connections, 250 ∘ C 250^\circ\text{C} 25 0 ∘ C for bolted joints)

T a T_a T a ​ = Ambient temperature ( ∘ C ^\circ\text{C} ∘ C , typically 40 ∘ C 40^\circ\text{C} 4 0 ∘ C )

K f K_f K f ​ = Conductor material constant (for annealed copper with 450 ∘ C 450^\circ\text{C} 45 0 ∘ C exothermic weld limit, K f ≈ 7.01 K_f \approx 7.01 K f ​ ≈ 7.01 for t c t_c t c ​ in seconds and A A A in kcmil \text{kcmil} kcmil ).

  • 8. Step-by-Step Worked Calculation Example
  • Problem Statement

A 115 kV 115\text{ kV} 115 kV transmission substation features a ground grid covering an area of 50 m × 50 m 50\text{ m} \times 50\text{ m} 50 m × 50 m ( A = 2500 m 2 A = 2500\text{ m}^2 A = 2500 m 2 ) buried at depth h = 0.5 m h = 0.5\text{ m} h = 0.5 m . The total length of buried grid conductors plus ground rods is L T = 1500 m L_T = 1500\text{ m} L T ​ = 1500 m .

Given site parameters:

Native soil resistivity: ρ = 100 Ω ⋅ m \rho = 100\ \Omega\cdot\text{m} ρ = 100 Ω ⋅ m

Surface crushed rock layer: thickness h s = 0.10 m h_s = 0.10\text{ m} h s ​ = 0.10 m ( 10 cm 10\text{ cm} 10 cm ), resistivity ρ s = 2500 Ω ⋅ m \rho_s = 2500\ \Omega\cdot\text{m} ρ s ​ = 2500 Ω ⋅ m

  • Maximum grid fault current: I g = 6.0 kA = 6000 A I_g = 6.0\text{ kA} = 6000\text{ A} I g ​ = 6.0 kA = 6000 A
  • Fault duration: t s = 0.50 s t_s = 0.50\text{ s} t s ​ = 0.50 s
  • Design basis: 50 kg 50\text{ kg} 50 kg body weight

Calculate:

The surface layer derating factor C s C_s C s ​ .

The tolerable touch voltage ( E t o u c h , 50 E_{touch,50} E t o u c h , 50 ​ ) and tolerable step voltage ( E s t e p , 50 E_{step,50} E s t e p , 50 ​ ).

The ground grid resistance R g R_g R g ​ using Sverak's formula.

The Ground Potential Rise ( GPR \text{GPR} GPR ) and assess whether a full mesh voltage analysis is required.

Solution Walkthrough

Step 1: Calculate Surface Layer Derating Factor ( C s C_s C s ​ ) C s = 1 − 0.09 ( 1 − ρ ρ s ) 2 h s + 0.09 = 1 − 0.09 ( 1 − 100 2500 ) 2 ( 0.10 ) + 0.09 C_s = 1 - \frac{0.09 \left(1 - \frac{\rho}{\rho_s}\right)}{2 h_s + 0.09} = 1 - \frac{0.09 \left(1 - \frac{100}{2500}\right)}{2(0.10) + 0.09} C s ​ = 1 − 2 h s ​ + 0.09 0.09 ( 1 − ρ s ​ ρ ​ ) ​ = 1 − 2 ( 0.10 ) + 0.09 0.09 ( 1 − 2500 100 ​ ) ​ C s = 1 − 0.09 ( 1 − 0.04 ) 0.20 + 0.09 = 1 − 0.09 ( 0.96 ) 0.29 = 1 − 0.0864 0.29 = 1 − 0.2979 = 0.7021 C_s = 1 - \frac{0.09 (1 - 0.04)}{0.20 + 0.09} = 1 - \frac{0.09(0.96)}{0.29} = 1 - \frac{0.0864}{0.29} = 1 - 0.2979 = \mathbf{0.7021} C s ​ = 1 − 0.20 + 0.09 0.09 ( 1 − 0.04 ) ​ = 1 − 0.29 0.09 ( 0.96 ) ​ = 1 − 0.29 0.0864 ​ = 1 − 0.2979 = 0.7021

Step 2: Calculate Tolerable Touch and Step Voltages

First, evaluate the body current factor for t s = 0.50 s t_s = 0.50\text{ s} t s ​ = 0.50 s : I B , 50 = 0.116 0.50 = 0.116 0.7071 = 0.16405 A I_{B,50} = \frac{0.116}{\sqrt{0.50}} = \frac{0.116}{0.7071} = 0.16405\ \text{A} I B , 50 ​ = 0.50 ​ 0.116 ​ = 0.7071 0.116 ​ = 0.16405 A

Now, calculate the equivalent contact resistance for touch and step: R t h , t o u c h = 1000 + 1.5 C s ρ s = 1000 + 1.5 ( 0.7021 ) ( 2500 ) = 1000 + 2632.88 = 3632.88 Ω R_{th,touch} = 1000 + 1.5 C_s \rho_s = 1000 + 1.5(0.7021)(2500) = 1000 + 2632.88 = 3632.88\ \Omega R t h , t o u c h ​ = 1000 + 1.5 C s ​ ρ s ​ = 1000 + 1.5 ( 0.7021 ) ( 2500 ) = 1000 + 2632.88 = 3632.88 Ω E t o u c h , 50 = 3632.88 Ω × 0.16405 A = 596.0 V E_{touch,50} = 3632.88\ \Omega \times 0.16405\ \text{A} = \mathbf{596.0\ \text{V}} E t o u c h , 50 ​ = 3632.88 Ω × 0.16405 A = 596.0 V

For step voltage: R t h , s t e p = 1000 + 6.0 C s ρ s = 1000 + 6.0 ( 0.7021 ) ( 2500 ) = 1000 + 10531.5 = 11531.5 Ω R_{th,step} = 1000 + 6.0 C_s \rho_s = 1000 + 6.0(0.7021)(2500) = 1000 + 10531.5 = 11531.5\ \Omega R t h , s t e p ​ = 1000 + 6.0 C s ​ ρ s ​ = 1000 + 6.0 ( 0.7021 ) ( 2500 ) = 1000 + 10531.5 = 11531.5 Ω E s t e p , 50 = 11531.5 Ω × 0.16405 A = 1891.7 V E_{step,50} = 11531.5\ \Omega \times 0.16405\ \text{A} = \mathbf{1891.7\ \text{V}} E s t e p , 50 ​ = 11531.5 Ω × 0.16405 A = 1891.7 V

Step 3: Calculate Grid Resistance R g R_g R g ​ (Sverak's Formula)

Evaluate intermediate terms for A = 2500 m 2 A = 2500\text{ m}^2 A = 2500 m 2 , h = 0.5 m h = 0.5\text{ m} h = 0.5 m , and L T = 1500 m L_T = 1500\text{ m} L T ​ = 1500 m : 20 A = 20 × 2500 = 50000 = 223.61 m \sqrt{20 A} = \sqrt{20 \times 2500} = \sqrt{50000} = 223.61\text{ m} 20 A ​ = 20 × 2500 ​ = 50000 ​ = 223.61 m 20 A = 20 2500 = 0.008 = 0.08944 m − 1 \sqrt{\frac{20}{A}} = \sqrt{\frac{20}{2500}} = \sqrt{0.008} = 0.08944\text{ m}^{-1} A 20 ​ ​ = 2500 20 ​ ​ = 0.008 ​ = 0.08944 m − 1 1 + h 20 A = 1 + 0.5 ( 0.08944 ) = 1.04472 1 + h \sqrt{\frac{20}{A}} = 1 + 0.5(0.08944) = 1.04472 1 + h A 20 ​ ​ = 1 + 0.5 ( 0.08944 ) = 1.04472 1 1 + h 20 A = 1 1.04472 = 0.9572 \frac{1}{1 + h \sqrt{\frac{20}{A}}} = \frac{1}{1.04472} = 0.9572 1 + h A 20 ​ ​ 1 ​ = 1.04472 1 ​ = 0.9572 R g = 100 [ 1 1500 + 1 223.61 ( 1 + 0.9572 ) ] = 100 [ 0.000667 + 1.9572 223.61 ] R_g = 100 \left[ \frac{1}{1500} + \frac{1}{223.61} (1 + 0.9572) \right] = 100 \left[ 0.000667 + \frac{1.9572}{223.61} \right] R g ​ = 100 [ 1500 1 ​ + 223.61 1 ​ ( 1 + 0.9572 ) ] = 100 [ 0.000667 + 223.61 1.9572 ​ ] R g = 100 [ 0.000667 + 0.008753 ] = 100 [ 0.009420 ] = 0.942 Ω R_g = 100 [0.000667 + 0.008753] = 100 [0.009420] = \mathbf{0.942\ \Omega} R g ​ = 100 [ 0.000667 + 0.008753 ] = 100 [ 0.009420 ] = 0.942 Ω

Step 4: Calculate GPR and Design Compliance GPR = I g × R g = 6000 A × 0.942 Ω = 5652 V \text{GPR} = I_g \times R_g = 6000\text{ A} \times 0.942\ \Omega = \mathbf{5652\ \text{V}} GPR = I g ​ × R g ​ = 6000 A × 0.942 Ω = 5652 V

Compliance Decision: Since GPR = 5652 V > E t o u c h , 50 = 596.0 V \text{GPR} = 5652\text{ V} > E_{touch,50} = 596.0\text{ V} GPR = 5652 V > E t o u c h , 50 ​ = 596.0 V , the grid is not unconditionally safe . A detailed calculation of mesh voltage ( E m E_m E m ​ ) and step voltage ( E s E_s E s ​ ) across each grid quadrant must be conducted to ensure E m ≤ 596.0 V E_m \le 596.0\text{ V} E m ​ ≤ 596.0 V and E s ≤ 1891.7 V E_s \le 1891.7\text{ V} E s ​ ≤ 1891.7 V .

  • 9. Common NCEES Exam Pitfalls
  • Pitfall 1: Mixing up 50 kg vs. 70 kg Constants

The 50 kg 50\text{ kg} 50 kg constant is 0.116 0.116 0.116 , while the 70 kg 70\text{ kg} 70 kg constant is 0.157 0.157 0.157 . Unless a problem specifically instructs you to use the 70 kg 70\text{ kg} 70 kg criterion, IEEE 80 and standard NCEES exam problems default to 50 kg 50\text{ kg} 50 kg .

Pitfall 2: Forgetting the Parallel vs. Series Foot Coefficients

In touch voltage, the two feet are in parallel , giving R f / 2 = 1.5 C s ρ s R_f / 2 = 1.5 C_s \rho_s R f ​ /2 = 1.5 C s ​ ρ s ​ . In step voltage, the two feet are in series , giving 2 R f = 6.0 C s ρ s 2 R_f = 6.0 C_s \rho_s 2 R f ​ = 6.0 C s ​ ρ s ​ . Never confuse the 1.5 1.5 1.5 and 6.0 6.0 6.0 multiplier terms!

Pitfall 3: Total Fault Current vs. Grid Current

Do not use the total bus fault current ( I f I_f I f ​ ) directly to compute GPR \text{GPR} GPR when a current division factor ( S f S_f S f ​ ) is provided. Always apply I g = S f × I f I_g = S_f \times I_f I g ​ = S f ​ × I f ​ .

Loading diagram...