2.2 Instrument Transformer Burdens, Saturation Curves & Ratio Correction Factors
PE Electrical and Computer: Power Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Exam Overview, Strategy & Reference Handbook
1.1 PE Power Exam Format, CBT Navigation & Reference Handbook 1.2 2026 Reference Standards (NEC 2020, NFPA 70E-2021, NESC) & Scoring Mechanics 1.3 CBT Pacing, AIT Question Formats & Formula Sheet Mastery
2 Chapter 2: Measurement, Metering & Field Testing
2.1 Current Transformers (CTs), Potential Transformers (PTs) & Meter Connections 2.2 Instrument Transformer Burdens, Saturation Curves & Ratio Correction Factors 2.3 Insulation Resistance Testing (Megger, Polarization Index, Dielectric Absorption) 2.4 Ground Resistance Testing (Fall-of-Potential 62% Rule & Clamp-on Methods)
3 Chapter 3: General Applications — Grounding & Surge Protection
3.1 Substation Ground Grid Design & IEEE 80 Touch/Step Voltage Criteria 3.2 Lightning Protection Systems & Rolling Sphere / Cone of Protection Methods 3.3 Surge Protective Devices (SPDs) & Voltage Surge Arresters
4 Chapter 4: General Applications — Lighting & Energy Management
4.1 Illumination Engineering & Zonal Cavity / Lumen Method Calculations 4.2 Energy Management, Demand Factors & Load Factor Calculations 4.3 Economic Dispatch, Energy Efficiency & Load Profile Analysis
5 Chapter 5: Electrical Safety & NFPA Standards
5.1 NFPA 70E Shock Protection, Approach Boundaries & PPE Requirements 5.2 Arc-Flash Hazard Analysis & IEEE 1584-2018 Incident Energy Calculations 5.3 Hazardous (Classified) Locations (Class I, II, III & Division/Zone Systems) 5.4 Special Occupancies & Critical Systems (NEC Articles 517 Health Care, 700/701/702 Emergency)
6 Chapter 6: NEC Wiring Methods & Installation Requirements
6.1 Conductor Ampacity & NEC Table 310.16 Derating Adjustments 6.2 Raceway Fill, Box Sizing & Conduit Bending Calculations (Chapter 9 Tables) 6.3 Equipment Grounding Conductors & Grounding Electrode Sizing (NEC Article 250)
7 Chapter 7: Circuit Analysis — Fundamentals & Symmetrical Components
7.1 DC & Single-Phase AC Network Analysis (Thevenin, Norton, Superposition) 7.2 Balanced Three-Phase Circuits (Wye-Delta Configurations & Power Formulas) 7.3 Symmetrical Components & Fortescue Sequence Transformation Matrices 7.4 Sequence Impedances & Positive, Negative, Zero Sequence Network Construction
8 Chapter 8: Circuit Analysis — Per-Unit & Phasor Analysis
8.1 Per-Unit System Fundamentals & Base Conversion Formulas 8.2 Three-Phase Per-Unit Network Modeling & Equipment Impedance Conversion 8.3 Phasor Diagrams, Complex Power & Power Triangle Relationships
9 Chapter 9: Power Electronics & Logic Controls
9.1 Power Electronic Converters (Rectifiers, Inverters & DC-DC Topologies) 9.2 Inverter-Based Resources (IBRs), Grid-Forming & Grid-Following Controls 9.3 Variable Frequency Drives (VFDs), PWM Operation & Harmonic Mitigation 9.4 Boolean Algebra, Logic Gates, De Morgan's Laws & Ladder Logic Control Diagrams
10 Chapter 10: Rotating Machines — Induction & Synchronous
10.1 Three-Phase Induction Motors (Equivalent Circuits, Slip & Performance) 10.2 Induction Motor Torque-Speed Characteristics & NEMA Design Classes 10.3 Synchronous Machines (Operating Principles, Power-Angle Curves & V-Curves) 10.4 Motor Starting Methods (DOL, Wye-Delta, Autotransformer, Soft-Start) & Voltage Dip
11 Chapter 11: Electric Power Devices & Renewable Energy
11.1 Power Transformers (Equivalent Circuits, Efficiency & Voltage Regulation) 11.2 Power Factor Correction Capacitors & Shunt Bank Sizing 11.3 Battery Energy Storage Systems (BESS) & Ultracapacitors 11.4 Renewable Energy Generation (Solar Photovoltaic Systems & Wind Turbines)
12 Chapter 12: Transmission & Distribution — Steady-State & Power Quality
12.1 Transmission Line Modeling, Voltage Drop & Conductor Sizing 12.2 Voltage Regulation, Reactive Power Support & Tap-Changer Controls 12.3 Power Quality, Harmonics, THD & IEEE 519 Compliance 12.4 Power Flow Analysis & System Stability (Steady-State, Transient & Swing Equation)
13 Chapter 13: Transmission & Distribution — Fault Analysis & Transformer Shifts
13.1 Symmetrical Three-Phase Bolted Fault Calculations 13.2 Unsymmetrical Fault Analysis (SLG, L-L, DLG Fault Calculations) 13.3 Transformer Connection Types, Zero-Sequence Paths & 30-Degree Phase Shifts
14 Chapter 14: Protection Systems & Device Coordination
14.1 Overcurrent Protection & Time-Current Characteristic (TCC) Curves 14.2 Protective Relaying Schemes (Differential 87, Distance 21, Undervoltage 27) 14.3 Circuit Breakers, Fuses & Automatic Reclosers 14.4 Protection Coordination, Selectivity & Coordination Time Intervals (CTI)
2.2 Instrument Transformer Burdens, Saturation Curves & Ratio Correction Factors
Key Takeaways Explain This Topic AI
ANSI/IEEE C-class relaying CTs (e.g., C100, C200, C400, C800) designate the secondary terminal voltage the CT can deliver to a standard burden at 20 times rated secondary current (100 A for a 5 A CT) without exceeding a 10% ratio error.
Total CT secondary burden comprises the internal CT secondary winding resistance (Rct), the round-trip interconnecting lead wire resistance (2*Rlead for single-phase/line-to-line loops), and the connected relay/meter input impedances (Zdevice).
Severe CT core saturation during short-circuit faults is driven by high fault current magnitudes, DC offset transients characterized by the system X/R ratio (oversizing factor = 1 + X/R), and residual remanent flux (Phi_r).
When using lower taps on a multi-ratio CT (e.g., 600:5 tap on a 1200:5 C400 CT), the available secondary terminal voltage derates in direct proportion to the turns ratio (C200 at the half-tap).
Instrument transformer metering accuracy is defined by the Ratio Correction Factor (RCF) and Phase Angle Error (beta), combined into the Transformer Correction Factor (TCF = RCF +/- beta/2600 * tan(theta)) to adjust billed energy.
Last updated: August 2026
ANSI/IEEE Relaying Accuracy Classes (C vs. T Class)
Protective relaying CTs must maintain transformation fidelity under severe fault currents that reach 10 to 30 times normal load current. The standard ANSI/IEEE C57.13 classification system describes a CT's capability to deliver secondary voltage without excessive ratio error.
C-Class (Calculated) vs. T-Class (Test)
C-Class (Calculated Accuracy): Designates CTs with low internal leakage flux , such as bushing or toroidal (donut) CTs with uniformly distributed secondary windings. For C-class CTs, the secondary ratio error can be accurately calculated directly from the manufacturer's secondary excitation curve.
T-Class (Test Accuracy): Designates CTs with significant internal leakage flux , such as wound-primary CTs. Because leakage flux varies non-linearly with burden and current, performance cannot be purely calculated and must be empirically determined through physical laboratory testing.
Decoding the ANSI C-Rating (e.g., C100, C200, C400, C800)
An ANSI CT rating consists of a letter and a voltage rating:
The Letter 'C': Indicates that the ratio error will not exceed 10% at any secondary current from 1 to 20 times rated secondary current ( I s = 20 × 5 A = 100 A I_s = 20 \times 5\text{ A} = 100\text{ A} I s = 20 × 5 A = 100 A ) with standard burden connected.
The Voltage Number ( V t V_t V t ): The secondary terminal voltage that the CT can deliver to a standard burden at 100 A 100\text{ A} 100 A secondary current while remaining within the 10% ratio error limit. Maximum Allowable External Burden Z b = V rating 100 A \text{Maximum Allowable External Burden } Z_b = \frac{V_{\text{rating}}}{100\text{ A}} Maximum Allowable External Burden Z b = 100 A V rating
ANSI Rating Terminal Voltage ( V t V_t V t ) @ 100 A Max External Burden ( Z b Z_b Z b ) Standard Burden Designation (0.9 PF)
- C100 100 V 100\text{ V} 100 V 1.0 Ω 1.0\ \Omega 1.0 Ω B-1.0 ( 25 VA 25\text{ VA} 25 VA )
- C200 200 V 200\text{ V} 200 V 2.0 Ω 2.0\ \Omega 2.0 Ω B-2.0 ( 50 VA 50\text{ VA} 50 VA )
- C400 400 V 400\text{ V} 400 V 4.0 Ω 4.0\ \Omega 4.0 Ω B-4.0 ( 100 VA 100\text{ VA} 100 VA )
- C800 800 V 800\text{ V} 800 V 8.0 Ω 8.0\ \Omega 8.0 Ω B-8.0 ( 200 VA 200\text{ VA} 200 VA )
- Multi-Ratio CT Tap Derating Rule
Many substation CTs are multi-ratio (e.g., MR 1200:5 with taps at 300:5, 400:5, 600:5, 800:5, 900:5, 1000:5, and 1200:5). When a lower tap is selected, the available secondary turns ( N t a p N_{tap} N t a p ) are reduced. Because induced voltage is proportional to turns, the effective C-voltage rating derates proportionally with the tap ratio : V tap = V full × ( N tap N full ) V_{\text{tap}} = V_{\text{full}} \times \left( \frac{N_{\text{tap}}}{N_{\text{full}}} \right) V tap = V full × ( N full N tap )
For example, if a 1200:5 C800 CT is tapped at 600:5, its effective rating drops to: V tap = 800 V × ( 600 1200 ) = 400 V ⟹ C400 V_{\text{tap}} = 800\text{ V} \times \left( \frac{600}{1200} \right) = 400\text{ V} \implies \text{C400} V tap = 800 V × ( 1200 600 ) = 400 V ⟹ C400
Secondary Excitation Curves & The Knee-Point Voltage
A CT's magnetic performance is characterized by its Secondary Excitation Curve , plotted on logarithmic scales showing secondary excitation RMS voltage ( V s V_s V s ) versus secondary excitation current ( I e I_e I e ).
Knee-Point Voltage ( V k V_k V k )
ANSI/IEEE Definition: The point on the log-log excitation curve where the tangent makes a 45 ∘ 45^\circ 4 5 ∘ angle with the coordinate axes.
IEC Definition: The point where a 10% increase in secondary voltage causes a 50% increase in excitation current ( I e I_e I e ).
Below the knee-point, the core operates in its linear magnetic region where excitation current I e I_e I e is negligible (< 0.05 A), ensuring faithful reproduction of primary current. Above the knee-point, the iron core saturates, drawing massive magnetizing current and clipping secondary current peaks.
Required Knee-Point Voltage Sizing Equation
To prevent saturation during symmetrical fault conditions, the CT knee-point voltage must exceed the total internal and external voltage drop under maximum primary fault current: V k ≥ I s (max) × Z total = ( I f (primary) N s ) × ( R c t + R leads + Z burden ) V_k \ge I_{s\text{(max)}} \times Z_{\text{total}} = \left( \frac{I_{f\text{(primary)}}}{N_s} \right) \times (R_{ct} + R_{\text{leads}} + Z_{\text{burden}}) V k ≥ I s (max) × Z total = ( N s I f (primary) ) × ( R c t + R leads + Z burden )
Burden Calculations in Protection & Metering Circuits
The burden of an instrument transformer is the total opposing impedance connected across its secondary terminals, expressed in ohms ( Ω \Omega Ω ) or volt-amperes (VA at rated secondary current, where VA = I s 2 Z b = 25 × Z b \text{VA} = I_s^2 Z_b = 25 \times Z_b VA = I s 2 Z b = 25 × Z b ).
Components of Total Secondary Loop Burden ( Z total Z_{\text{total}} Z total ) Z total = R c t + R lead_loop + Z device Z_{\text{total}} = R_{ct} + R_{\text{lead\_loop}} + Z_{\text{device}} Z total = R c t + R lead_loop + Z device
Internal Secondary Resistance ( R c t R_{ct} R c t ): The DC resistance of the CT secondary copper winding itself, typically 0.1 Ω 0.1\ \Omega 0.1 Ω to 0.8 Ω 0.8\ \Omega 0.8 Ω . (Must be included when evaluating internal induced EMF E s E_s E s ).
Lead Wire Resistance ( R lead_loop R_{\text{lead\_loop}} R lead_loop ): The resistance of the control cable connecting the CT junction box to the control panel:
For a phase-to-phase or single-phase fault , current must travel out and back: R lead_loop = 2 × L × r wire R_{\text{lead\_loop}} = 2 \times L \times r_{\text{wire}} R lead_loop = 2 × L × r wire .
For a balanced three-phase fault , return currents cancel in the neutral: R lead_loop = 1 × L × r wire R_{\text{lead\_loop}} = 1 \times L \times r_{\text{wire}} R lead_loop = 1 × L × r wire .
For a single line-to-ground fault through a residual ground relay in the neutral leg, the neutral conductor carries 3 I 0 3I_0 3 I 0 , making effective neutral resistance 3 × R neutral 3 \times R_{\text{neutral}} 3 × R neutral .
Connected Device Impedance ( Z device Z_{\text{device}} Z device ): Modern microprocessor relays present very small burdens ( < 0.05 Ω < 0.05\ \Omega < 0.05 Ω ), whereas electromechanical induction-disc relays presented significant inductive burdens ( 0.5 Ω 0.5\ \Omega 0.5 Ω to 3.0 Ω 3.0\ \Omega 3.0 Ω ).
Conductor Size (AWG) DC Resistance @ 75°C ( Ω / 1000 ft \Omega / 1000\text{ ft} Ω/1000 ft ) Loop Resistance for 200 ft Run ( 400 ft total 400\text{ ft total} 400 ft total )
#12 AWG Copper 1.98 Ω / 1000 ft 1.98\ \Omega / 1000\text{ ft} 1.98 Ω/1000 ft 400 ft × 0.00198 = 0.792 Ω 400\text{ ft} \times 0.00198 = 0.792\ \Omega 400 ft × 0.00198 = 0.792 Ω
#10 AWG Copper 1.24 Ω / 1000 ft 1.24\ \Omega / 1000\text{ ft} 1.24 Ω/1000 ft 400 ft × 0.00124 = 0.496 Ω 400\text{ ft} \times 0.00124 = 0.496\ \Omega 400 ft × 0.00124 = 0.496 Ω
#8 AWG Copper 0.778 Ω / 1000 ft 0.778\ \Omega / 1000\text{ ft} 0.778 Ω/1000 ft 400 ft × 0.000778 = 0.311 Ω 400\text{ ft} \times 0.000778 = 0.311\ \Omega 400 ft × 0.000778 = 0.311 Ω
- CT Saturation Under Fault Conditions
- Asymmetrical Faults and DC Offset
When a short circuit occurs at an instant other than the voltage peak, Faraday's Law requires an asymmetrical DC offset current to maintain flux continuity. This DC component decays exponentially with the primary system time constant: τ = L R = X ω R = X 2 π f R \tau = \frac{L}{R} = \frac{X}{\omega R} = \frac{X}{2\pi f R} τ = R L = ω R X = 2 π f R X
The DC component acts as a unidirectional current that continuously injects flux of one polarity into the core without alternating reversal. To avoid saturation during the initial cycles of an asymmetrical fault, IEEE C37.110 recommends an over-sizing factor : V k ≥ I s (fault) × ( 1 + X R ) × ( R c t + R leads + Z burden ) V_k \ge I_{s\text{(fault)}} \times \left( 1 + \frac{X}{R} \right) \times (R_{ct} + R_{\text{leads}} + Z_{\text{burden}}) V k ≥ I s (fault) × ( 1 + R X ) × ( R c t + R leads + Z burden )
In systems with high X / R X/R X / R ratios (e.g., X / R = 20 X/R = 20 X / R = 20 near generation stations), the required CT saturation voltage is 21 times larger than for a pure AC fault of identical steady-state RMS magnitude!
Remanent Flux ( Φ r \Phi_r Φ r )
When a circuit breaker clears a heavy fault, the sudden interruption leaves residual magnetic flux (remanence) trapped in the iron core, which can persist indefinitely at 60% to 80% of saturation flux density . If a subsequent fault occurs with polarity matching the remanent flux, the CT enters deep saturation within 0.25 to 0.5 cycles , severely blinding differential and overcurrent relays.
Ratio Correction Factor (RCF) & Transformer Correction Factor (TCF)
In high-accuracy revenue metering, instrument transformer non-idealities are adjusted mathematically:
Ratio Correction Factor (RCF): The ratio of the true transformation ratio to the marked (nominal) ratio: RCF = True Ratio Marked Ratio = I p / I s Nominal Ratio \text{RCF} = \frac{\text{True Ratio}}{\text{Marked Ratio}} = \frac{I_p / I_s}{\text{Nominal Ratio}} RCF = Marked Ratio True Ratio = Nominal Ratio I p / I s True Primary Current I p = I s × Marked Ratio × RCF \text{True Primary Current } I_p = I_s \times \text{Marked Ratio} \times \text{RCF} True Primary Current I p = I s × Marked Ratio × RCF
Phase Angle Error ( β \beta β ): The angular displacement (in minutes or milliradians) by which the secondary current phasor leads the reversed primary current phasor due to core excitation.
Transformer Correction Factor (TCF): For active power revenue metering at load power factor angle θ \theta θ : TCF = RCF − β 2600 tan θ ( for lagging PF with β in minutes ) \text{TCF} = \text{RCF} - \frac{\beta}{2600} \tan \theta \quad (\text{for lagging PF with } \beta \text{ in minutes}) TCF = RCF − 2600 β tan θ ( for lagging PF with β in minutes ) Billed Power P true = P meter × ( PT Ratio × CT Ratio ) × TCF \text{Billed Power } P_{\text{true}} = P_{\text{meter}} \times (\text{PT Ratio} \times \text{CT Ratio}) \times \text{TCF} Billed Power P true = P meter × ( PT Ratio × CT Ratio ) × TCF
- Worked Calculation Example
- Problem Statement
A 1200:5 multi-ratio CT rated C400 is connected on its 800:5 tap to protect an outdoor 13.8 kV feeder. The secondary winding resistance at the 800:5 tap is R c t = 0.28 Ω R_{ct} = 0.28\ \Omega R c t = 0.28 Ω . The CT is connected to a microprocessor relay ( Z relay = 0.04 Ω Z_{\text{relay}} = 0.04\ \Omega Z relay = 0.04 Ω ) located in a control house 350 ft away via #10 AWG solid copper wire ( r = 1.24 Ω / 1000 ft r = 1.24\ \Omega / 1000\text{ ft} r = 1.24 Ω/1000 ft ).
The maximum symmetrical 3-phase bus fault current is 16,000 A 16{,}000\text{ A} 16 , 000 A primary with an X / R X/R X / R ratio of 8 8 8 .
Determine:
The derated ANSI C-voltage rating at the 800:5 tap.
The total secondary loop resistance ( R total R_{\text{total}} R total ) for a 3-phase fault (assuming no neutral return drop).
The secondary fault current ( I s I_s I s ) and the required secondary terminal voltage ( V s V_s V s ) under symmetrical conditions.
Whether the CT will saturate under symmetrical fault conditions.
The required voltage including DC offset ( 1 + X / R 1 + X/R 1 + X / R ) and evaluate whether saturation will occur during an asymmetrical fault.
Step-by-Step Solution
Step 1: Calculate Derated C-Rating at 800:5 Tap V tap = 400 V × ( 800 1200 ) = 266.67 V ⟹ C266.67 V_{\text{tap}} = 400\text{ V} \times \left( \frac{800}{1200} \right) = 266.67\text{ V} \implies \text{C266.67} V tap = 400 V × ( 1200 800 ) = 266.67 V ⟹ C266.67
Step 2: Calculate Lead and Total Loop Resistance One-way distance = 350 ft \text{One-way distance} = 350\text{ ft} One-way distance = 350 ft R lead = 350 ft × ( 1.24 Ω 1000 ft ) = 0.434 Ω R_{\text{lead}} = 350\text{ ft} \times \left( \frac{1.24\ \Omega}{1000\text{ ft}} \right) = 0.434\ \Omega R lead = 350 ft × ( 1000 ft 1.24 Ω ) = 0.434 Ω R total = R c t + R lead + Z relay = 0.28 + 0.434 + 0.04 = 0.754 Ω R_{\text{total}} = R_{ct} + R_{\text{lead}} + Z_{\text{relay}} = 0.28 + 0.434 + 0.04 = 0.754\ \Omega R total = R c t + R lead + Z relay = 0.28 + 0.434 + 0.04 = 0.754 Ω
Step 3: Calculate Secondary Fault Current and Symmetrical Voltage CT Ratio = 800 5 = 160 \text{CT Ratio} = \frac{800}{5} = 160 CT Ratio = 5 800 = 160 I s = I fault Ratio = 16,000 A 160 = 100.0 A I_s = \frac{I_{\text{fault}}}{\text{Ratio}} = \frac{16{,}000\text{ A}}{160} = 100.0\text{ A} I s = Ratio I fault = 160 16 , 000 A = 100.0 A V s (sym) = I s × R total = 100.0 A × 0.754 Ω = 75.4 V V_{s\text{(sym)}} = I_s \times R_{\text{total}} = 100.0\text{ A} \times 0.754\ \Omega = 75.4\text{ V} V s (sym) = I s × R total = 100.0 A × 0.754 Ω = 75.4 V
Step 4: Evaluate Symmetrical Saturation Available Voltage V tap = 266.67 V > 75.4 V \text{Available Voltage } V_{\text{tap}} = 266.67\text{ V} > 75.4\text{ V} Available Voltage V tap = 266.67 V > 75.4 V
Conclusion: The CT operates well below its knee point and will NOT saturate during a symmetrical fault.
Step 5: Evaluate Asymmetrical Fault Saturation with DC Offset V req(asym) = V s (sym) × ( 1 + X R ) = 75.4 V × ( 1 + 8 ) = 75.4 × 9 = 678.6 V V_{\text{req(asym)}} = V_{s\text{(sym)}} \times \left( 1 + \frac{X}{R} \right) = 75.4\text{ V} \times (1 + 8) = 75.4 \times 9 = 678.6\text{ V} V req(asym) = V s (sym) × ( 1 + R X ) = 75.4 V × ( 1 + 8 ) = 75.4 × 9 = 678.6 V Since V req(asym) ( 678.6 V ) > V tap ( 266.67 V ) \text{Since } V_{\text{req(asym)}} (678.6\text{ V}) > V_{\text{tap}} (266.67\text{ V}) Since V req(asym) ( 678.6 V ) > V tap ( 266.67 V )
Conclusion: The CT will heavily saturate on the initial cycles of an asymmetrical fault due to the DC offset. To prevent saturation, either the CT ratio must be increased to 1200:5 ( V tap = 400 V V_{\text{tap}} = 400\text{ V} V tap = 400 V ) or a higher C-rating (e.g., C800) must be specified.
Common Exam Traps & Pitfalls
Forgetting Tap Derating: Never use the full C-rating on a tapped multi-ratio CT. A C800 CT tapped at half ratio is only a C400 CT.
Ignoring Internal CT Secondary Resistance ( R c t R_{ct} R c t ): When calculating the induced EMF ( E s E_s E s ), the internal winding resistance R c t R_{ct} R c t is in series with the external burden and must always be added to the lead and relay impedances.
Loop Resistance Multiplier Confusion: For single-phase or line-to-line faults, multiply lead wire length by 2 ( 2 × L 2 \times L 2 × L ). For balanced three-phase faults, lead resistance is single-conductor length ( 1 × L 1 \times L 1 × L ) because neutral current is zero.